BUILDING HVAC EQUIPMENT SELECTION SUMMARY

SUMMER WINTER ROOM CONDITIONING REQUIREMENTS EQUIPMENT RESULTS


SPACE NO SPACES
INDOOR INDOOR SENSIBLE COOLING LATENT COOLING TOTAL COOLING QTY ROOM ANALYSIS
NOMINAL TOTAL
TOTAL CAPACITY SENSIBLE CAPACITY POWER PROVIDED TOTAL PROVIDED TOTAL
DB RH DB RH LOAD LOAD LOAD REDUNDACY MODEL TYPE INDOOR MODEL NO OUTDOOR MODEL NO CAPACITY @ 35°C ELECTRICAL DATA
@ 40°C OUTDOOR @40°C OUTDOOR CONSUMPTION COOLING CAPACITY SENSIBLE CAPACITY
OUTDOOR
[°C] [%] [°C] [%] [W] [W] [W] [W] [W] [W] [W] V-Ph-Hz [W] [W]

90 BBB

1 MCSet 26 N.C 5 N.C 8,963 0 8,963 2 (1+1) CEILING TYPE PCA - M125 KA PUZ - M125VKA 12,500 12,230 7,580 4,330.00 230V-1Ph-50Hz 12,230 7,580

2 TR 26 N.C 5 N.C 5,043 0 5,043 3 (2+1) HIGH WALL TYPE MSZ - AP 60 VG MUZ - AP60VG 6,000 5,800 4,536 1,915.00 230V-1Ph-50Hz 11,600 9,072

3 TR 26 N.C 5 N.C 5,043 0 5,043 3 (2+1) HIGH WALL TYPE MSZ - AP 60 VG MUZ - AP60VG 6,000 5,800 4,536 1,915.00 230V-1Ph-50Hz 11,600 9,072

4 UPS 26 N.C 5 N.C 2,750 0 2,750 2 (1+1) HIGH WALL TYPE MSZ - AP 60 VG MUZ - AP60VG 6,000 5,800 4,536 1,915.00 230V-1Ph-50Hz 5,800 4,536

21,799 0 21,799 41,230 30,260