You are on page 1of 1

1

DESIGN SPECIFICATION
DWG.: REV.:
09A-012-193 01
ORIGINAL ISSUE DATE: 02/23/05 02/23/05
PRODUCT TYPE: BCT-OIL INSULATION CLASS: 0.60 kV 105 °C

CUSTOMER P/N: 400050210 DWG. MOST RECENT REV.


IN ADDITION TO THE INFORMATION CONTAINED HEREIN, ADDITIONAL REQUIREMENTS MAY BE SPECIFIED.
FOR THOSE SPECIFIC DETAILS REFER TO THE CUSTOMER DWG (WHEN STATED).

CURRENT RATIO: 50 : 5 SR RATED FREQUENCY: 60 Hz

ACCURACY: C100 @ 50:5

STANDARD: IEEE C57.13 MEASUREMENT CANADA APPROVAL:

TAPS: 50:5 CONTINUOUS RATING FACTOR (RF): 1.00 @ 95 °C AMB.

SEC. WINDING RESISTANCE: 0.0032 Ohms / T @ 75°C LEAD RESISTANCE: 0.0014 Ohms / ft @ 75°C

SHORT-TIME CURRENT RATINGS


These ratings are based strictly on the secondary winding alone, and may be different than the equipment for which the CT is being installed on.
APPLIED TO FULL WINDING ANY TAP
MECHANICAL (I dyn): 20.4 kA peak, 1 cycle asymmetrical 407.5 X nominal ratio

THERMAL (Ith): 7.5 kA RMS sym, 1 sec 4.4 kA RMS sym, 3 sec 150.9 X nominal ratio, 1 sec

PHYSICAL PARAMETERS
FINISHED I.D. FINISHED O.D. FINISHED HT FINISHED WT
4.25 in 14.00 in 10.00 in 299 lbs
108 mm 356 mm 254 mm 135 kgs
MIN. tolerance MAX. tolerance MAX. tolerance

WINDING ARRANGEMENT
RATIO TURNS CONNECTION
H1
50:5 10 X1-X2

X1 / S1 X2 / S2

LEADS / TERMINALS: #10 AWG TEFZEL, 10 FT [3048mm] LENGTH


COLOR CODE (IF APPLICABLE)
X1 GREY
X2 GREY

RATING PLATE
Due to limited space on the nameplate, additional accuracy details may be referenced and found on Meramec's published curves.
Part No.: 400050210 X1 - GREY
Freq.: 60 Hz X2 - GREY
Type: B.C.T. R.F.: 1.0
Mfg. Date: mm-yy Ratio: 50:5SR
Ser. No.: xxxxxx-1 AC. CL.: C100 @ 50:5

MADE IN THE USA


*xxxxxx-xxx*

TRANSIENT RESPONSE PARAMETERS


Tp: 1.00 sec. Ts >: 2 sec. Kr <: 10 %
t' : 0.000 sec. tfr : 0.000 sec. t" : 0.000 sec.
Ipsc: 40000 A Issc: 4000.0 A Ktd: 0.0
Rb: 1.80 Ohms Rct: 5.5 Ohms error: 10 %
Ual >=: 0 V RMS Ial @ Ual <=: 160.0 A RMS Ial @ Ual <=: 400.0 A peak

QUALIFICATIONS / COMMENTS
It is Meramec's policy to comply to the most current release of any referenced standard, unless noted below. In addition and when applicable, unit shall also comply
with purchaser's drawing and/or technical specification as referenced above under "Customer Dwg". Construction materials and methods are Meramec's standard.

QUALIFICATIONS:
1. Construction suitable for use in or above hot transformer oil.