Professional Documents
Culture Documents
Depending on the mix (specially the water-cement ratio) and the time and quality of curing,
compressive strengths of concrete can be obtained up to 97 MPa or more. Commercial
production of concrete with ordinary aggregates is usually in the 21 to 83 MPa range with the
most common ranges for cast-in-place buildings from 21 to 41 MPa. On the other hand, precast
and prestressed applications often expect strengths of 27.6 to 55.1 MPa
The 28-day compressive strength of concrete can be estimated from the 7-day strength by a
formula proposed by W.A. Sater:
Concrete strength may increase significantly after 28 days, particularly when cement is mixed
with fly ash.
The stress drain diagram for concrete of a specialized compressive strength is a curved line as
shown in Figure 1.1. Maximum stress is reached at a strain of 0.002 mm/mm, after which the
curve descends.
According to Section 5.7.6 of NSCP, the minimum clear spacing between parallel bars in a layer
should be db but not less than 25 mm. Where parallel reinforcement is placed in two or more
layers, bars in the upper layers should be placed directly above bars in the bottom layer with
clear distance between layers not less than 25 mm. In spirally reinforced or tied reinforced
compression members, clear distance between longitudinal bars shall be not less than 1.5 d b nor
40 mm.
In walls and slabs other than concrete joist construction, primary flexard reinforcement shall be
spaced not farther apart than three times the wall or slab thickness, nor 450 mm.
Group of parallel reinforcing bars bundled in contact to act as a unit shall be limited to four in any one
bundle. Bundled bars shall be enclosed within stirrups or ties and bars larger than 32 mm shall not be
bundled in beams. The individual bars within a bundle terminated within the span of flexural members
should terminate at different points with at least 40d ι stagger. Since spacing limitations and minimum
concrete cover of most members are based on a single bar diameter d b , bundled bars shall be treated as a
single bar of a diameter derived from the equivalent total area.
Diameter of single bar equivalent to bundled bars according to NSCP to be used for spacing limitation
and concrete cover.
3- 25 mm Equivalent diameter, D
π π
( 25 )2 x 3= D 2
4 4
D=43.3 mm
Bundled Bars
For bundled bars, the minimum concrete cover shall be equal to the equivalent diameter of the bundle, but
need not be greater than 50 mm, except for concrete cast against and permanently exposed to earth, the
minimum cover shall be 75 mm.
STANDARD HOOKS
The term standard hook refers to one of the following:
(a) 180° bend plus 4d ι extension but not less than 65 mm at free end,
(b) 90° bend plus 12d ι extension, at free end bar,
(c) For stirrups and tie hooks:
(1) 16 mm bar and smaller, 90° bend plus 6d ι extension at free end of bar, or
(2) 20 mm and 25 mm bar, 90° bend plus 12d ι extension at free end of bar, or
(3) 25 mm bar and smaller, 135° bend plus 6d ι extension of free end of bar.
UNDERREINFORCED DESIGN
Underreinforced design is a design in which the steel reinforcement is lesser than what is
required for balanced condition. If the ultimate load is approached, the steel will begin to yield
although the compression concrete is still under-stressed. If the load is further increased, the steel
will continue to elongate, resulting in appreciable deflections and large visible cracks in the
tensile concrete. Failure under this condition is ductile and will give warning to the user of the
structure to decrease the load.
OVERREINFORCED DESIGN
Overreinforced design is a design in which the steel reinforcement is more than what is required
for balanced condition. If the beam is overreinforced, the steel will not yield before failure. As
the load is increased, deflections are not noticeable although the compression concrete is highly
stressed, and failure occurs suddenly without warning to the user of the structure.
Overreinforced as well as balanced design should be avoided in concrete because of its brittle
property, that is why the Code limits the tensile steel percentage ( ρmax = 0.75 ρb) to ensure
underreinforced beam with ductile type of failure to give occupants warning before failure
occurs.
Structure and structural members should be designed to have design strengths at all sections at
least equal to required strengths calculated for the factored loads and forces in any combination
of loads.
The required strength U to resist dead load DL and live load LL is
If resistance to structural effects of a specified wind load W are included in design where
load combinations includes both full value and zero value of LL to determinate the more
severe condition,
If resistance to loading due to weight and pressure of fluids with well-defined densities
and controllable maximum height F is included in design, such loading shall have a load
factor of 1.4 and be added to all loading combinations that included live load.
if resistance to impact effect is taken into account in design, such effects shall be included
with live load LL.
Note: The assumptions made in steps II, V, and VIII are the author’s recommendation based on
his experience.
I. Identify the values of the dead load and live load to be carried by the beam. (DL &
LL)
II. Approximate the weight of beam (DL) between 20%-25% of (DL+LL). This weight
is added to the dead load.
0.85 pB 600
p=
f y (600+f y )
B= 0.85 for f=≤ 30 MPa
B= 0.85-0.008 (f-30) for f≥ 30 MPa
pmin= 1.4/ f y
fy
VI. Compute the value of w, w= p
f
VIII. Try a ratio d/b (from d=1.5b to d=2b), and solve for d. (round off this value to
reasonable dimension) Check also the minimum thickness of beam required by the
code as given in Table 2.1 in page 36.
After solving for d, substitute its value to step VII and solve for b.
Compute the weight of the beam and compare it to the assumption made in step II.
IX. Solve for the required steel area and number of bars.
A= pbd
Number of bars (diameter = D)
π 2
D x number of bars = A
4
I. Solve for p
p= A/bd
II. Check if steel yields by computing pb
0.85 pB 600
pb =
f y (600+f y )
If p ≤ p bsteel yields. Proceed to step III
If p¿ pb steel does not yield. Proceed to step IV
Note: If p¿ pmin, the given A is not adequate for the beam dimension
III. p ≤ p b
fy
w= p
f
M= ∅ fw bd 2 ¿0.59w)
IV. p ¿ pb
Positive moment
End spans
Discontinuous and unrestrained…………….………………w u=L y 2 /11
Discontinuous end integral with support……………..……..w u=L y 2 / 14
Interior spans…………………………………………….………….w u=L y 2 /16
Negative moment at exterior face of first interior support
Two spans……………………………………………….……………w u=L y 2 / 9
More than two spans…………………...……………………………w u=L y 2 /10
Negative moment at other faces of interior supports……….………………w u=L y 2 /11
Negative moment at face of all supports for:
Slabs with spans not exceeding 3m; and beams
Where ration of sum of column stiffness to beam
Stiffness exceeds eight at each end of the span……….……….……w u=L y 2 /12
Negative moment at interior face of exterior
Support for members built integrally with supports
Where support is a spandrel beam…………….…………………….w u=L y 2 /24
Where support is a column………………………………….w u=L y 2 /16
Shear in end members at face of
First interior support……………………………………………………………1.5 wu L y /2
Where Lu=¿ clear span for positive moment or shear and average of adjacent clear spans
for negative moment.
Figure 2.3: Shear and moment for continuous beam or slab with spams and discontinuous end
integral with support.
Figure 2.4: Shear and moment for continuous beam or slab with more than two beams and
discontinuous end integral with support
Figure 2.5: Shear and moment for continuous beam or slab with more than two spans and
discontinuous end unrestrained.
Problem 2.5
Design a rectangular beam reinforced for tension only to carry a dead load moment of 56 kN-m
(including its own weight) and a live load moment of 47 kN-m. Use
f ' c =20.7 MPa∧f y =276 MPa .
Solution:
M u=1.4 M DL=1.7 M ¿
M u=1.4 (56)=1.7 ( 47 )
M y =158.3 kN −m
(Note: this already includes the weight of the beam)
ρb =0.0371
1.4
[ ρmin >
fy ]
1.4
ρmin =
276
ρmin =0.00507
ρ=0.6 ( 0.0371 )
ρ=0.02226
ρf y
[ w=
f 'c ]
0.02226 ( 276 )
w=
20.7
w=0.2968
Ru=5.068
[ M c =ϕ Ru b d 2 ]
158.3 x 106 =0.90 ( 5.068 ) b d2
b d 2=34,705,779
Try d=1.75 b
2
b ( 1.75 b ) =34,705,779
Note: we can not check for the minimum beam thickness since there is no given beam length and
type of support.
A s=1,997 m m2
Summary :b=230 mm
d=390 mm
A s=1,997 m m2
Problem 2.7
Design a rectangular beam for a 10-m simple span to support a dead load of 18 kN/m (not
including its own weight) and a live load of 24 kN/m. Use f ' c =21 MPa∧f y =276 MPa . Assume
weight of concret is 23.5 kN / m3.
Solution
Assume weight of beam to be 21% of (DL +LL)
Assume weight of beam = 0.21(18 + 24) = 8.82 kN/m
ω DL =18+8.82
ω DL =26.82 kN / m
[ ω u=1.4 ωDL =1.7 ω ¿ ]
ω u=1.4 ( 26.82 ) +1.7 ( 24 )
ω u=78.348 kN /m
ωu L2
Maximum moment: M u=
8
78.348 (10 )2
M u=
8
M u=979.35 kN −m
Try p=0.5 pb
0.85 f ' c β 1 600
p=0.5
f y ( 600+ f y )
0.85 ( 21 ) ( 0.85 ) 600
p=0.5
276 ( 600+276 )
p=0.0188
pmin =1.4 /f y
pmin =1.4 /276
pmin =0.0051
pfy
[ w=
f 'c ]
0.0188 ( 276 )
w=
21
m=0.247
[ Ru =f 'c w ( 1−0.59 w ) ]
Ru= ( 21 )( 0.247 ) ( 1−0.59 ( 0.247 ) )
Ru=4.431 MPa
[ M u=ϕ R u b d2 ]
979.35 x 106 =0.90 ( 4.431 ) b d 2
b d 2=245,580,381
Try d=1.75 b
2
b ( 1.75 b ) =245,580,381
b= 431 mm say 430 mm
430d 2= 245,580,381
d= 755 say 760 mm
d=755 say 760 mm
approximate dept h of beam ,h=760+100=860 mm
Note: The value 100 is the distance (estimated) from the e.g. of the bars to extreme concrete
fiber.
10,000 276
h=
16
0.4 +(700 )
=496 mm OK
Solution
π
A s= ¿
4
A s=1473mm2
As
[ ρ=
bd ]
1473
ρ=
300(500)
ρ=0.00982
1.4
ρmin =
fy
ρmin =0.0034
Solution
π
A s= ¿
4
A s=4825 mm2
As
[ ρ=
bd ]
4825
ρ=
300(500)
ρ=0.0322
1.4
ρmin =
fy
1.4
¿
414
ρmin =0.0034
0.85 f ' c β 1 600
[ ρ b=
f y (600+ f y ) ]
ρb =0.85(27.6)¿ ¿
Since ρ> ρ b, the tension steel does not yield, and thus the steel stress f s is lower than f y
and it has to be computed.
[ ƩF =0 ] T =C
A s f s=0.85 f ' c a−b
a=β 1 c=0.85 c
500−c
( 4825 ) 600 =0.85 ( 27.6 ) ( 0.85 c )( 300 )
c
c 2 +484 c−241,964=0
Problem 2.14
A rectangular beam reinforced for tension only has b = 300 mm, d = 490 mm. The
tension steel area provided is 7.25 mm diameter bars with f y =415 MPa , f ' c= 21 MPa.
Use NSCP Specifications. Calculate the ultimate moment capacity of the beam.
Solution
π
A s= ¿
4
A s=3436mm2
As
[ ρ=
bd ]
3436
ρ= =0.02337 ( ρmin =0.0034 )
300(490)
0.85 (21)( 0.85)(600)
ρb =
415 (600−415)
ρb =0.0216 f < 0.02337
f s=1.325 c
0.003 0.003+f s / Es
=
c d
0.003 0.003+1.325 c /200000
=
c 490
0.003 600+ 1.325 c
=
c 98000000
[ a=β 1 c ]
a=0.85 ( 296.2 )
a=251.77 mm
f s=1.325(296.2)
f s=392.465< f y
a
M u=ϕ T (d− )
2
a
¿ ϕ A s f y (d− )
2
251.77
¿ 0.90(3426)(392.465)(490− )
2
¿ 440,625,240 N−mm
M u=440.6 kN−m
ONE-WAY SLAB
Reinforced concrete slabs are large flat are supported at its sides by reinforced concrete beams,
walls, columns, steel beams, or by the ground. If a slab is supported on two opposite sides only,
they are referred to a one0-way slabs since the bending occurs in one direction only.If the slab is
supported on all four sides, it is called two-way slab since the bending occurs in both direction.
If the rectangular slab is supported in al four sides but the long side is two or more times the
short side, the slab will, for all practical purposes, act as a one way slab, with bending occurring
in the short direction.
A one-way slab is considered as a wide, shallow rectangular beam. The reinforcing steel is
usually spaced uniformly over its width. One-way slabs are analyzed by considering a one-meter
strip, which is assumed independent of the adjacent strips. This method of analysis is somewhat
conservative because we neglected the lateral restraint provided by the adjacent strips.
(a) Where Grade 275 deformed bars are used ………………….…………………. 0.0020
(b) Where Grade 415 deformed bars or welded wire fabric (plain or deformed)are used
……………………………………………………………..…………………... 0.0018
(c) Where reinforcement with ❑❑ measured at yield strain of 0.35% are used
❑
………………………………………………………………….………….. ❑
❑
Shrinkage and temperature reinforce may not be spaced not farther apart than 5 times the slab
thickness nor 450mm (Section 5.7.12.2.2).
,❑❑
' c ❑u
[√ ]
f ❑ 'c
Solve for ❑❑ and ❑❑
If is less than ❑❑ and greater than ❑❑ use
If is greater than ❑❑ and increase the depth of slab to ensure ductile failure
If is less than ❑❑ use ❑❑
Design a one-way slab to carry a service live load of 400 Pa. The slab has a length of 4 m width
both ends continuous. Assume f x = 21 MPa and f y = 415 MPa for main bars and f y = 276 MPa
for temperature bars.
SOLUTION
Live Load = 4000 Pa
Dead Load (Weight of slab)
DL = 23.5 (0.15)
= 3.525 kPa
At midspan :
W u Ln 2
[ Mu =
16 ]
11.735(4)2
M u=
16
M u=11.735 kN .m
[ M u=ϕ R u bd 2 ]
11.735 x 106 = 0.90 Ru (1000)(124)2
Ru = 0.848 MPa
0.85 f e 2 Ru
ρ=
fy [ √
1− 1− ]
0.85 f e
0.85(21)
¿ ¿
415
ρ=0.0021
ρmin = 1.4/415
ρmin = 0.00337 > 0.0021
A sb
Spacing, S = x 1000
As
π
(12)2
Spacing, S = 4 x 1000
418
S = 271 say 270 mm
At support:
w u Ln2
[Mu =
10 ]
11.735(4)2
M u=
10
M u=18.776 kN −m
[ M u=ϕ R u bd 2 ]
18.776 x106 =0.90 R u (1000)(124)2
Ru=1.357 MPa
0.85 f ' c 2 Ru
ρ=
fy [
1−
0.85 f ' c ]
0.85(21) 2(1.357)
=
415
1− [
0.85(21) ]
ρ=0.0162>0.0034
Use ρ=0.0034
A sb
Spacing= x 1000
As
π
( 12 )2
Spacing= 4 x 1000
422
Spacing= 268 say 265 mm
A st =0.002 b h
=0.002(1000)(150)
A st= 300mm2
A st
Spacing= x 1000
As
π
(10)2
= 4
x 1000
300
Spacing= 261 say 260 mm