SWEP International AB

Box 105, Hjalmar Brantings väg 5


SE-261 22 Landskrona, Sweden
www.swep.net

SSP G8 -
Date : 2019-06-10
EVAPORATOR - PRINTOUT ON ARTICLE NO.
Heat Exchanger : B250ASHx64/1P-NC-H (28U+66.8+2x2 1/2")

Art No : 17563-064

Connection Data F1 - SOLDER 66.85NON-CASTED(54)


F2 - ISO-G 2 1/2" A ASME-approved (54)
F3 - SOLDER 28U NON-CASTED(54)
F4 - ISO-G 2 1/2" A ASME-approved (54)

Connection Locations Side 1: F3/F1 (In / Out)


Side 2: F2/F4 (In / Out)

Fluid Side 1 : R744 (Carbon Dioxide)


Fluid Side 2 : Water

Side 1 : Inner circuit, Narrow side


Side 2 : Outer circuit, Wide side

Flow Type : Counter-Current


SSP Alias : B250AS

DUTY REQUIREMENTS Side 1 Side 2


Heat load kW 150.0
Inlet vapor quality 0.000
Outlet vapor quality 1.000
Inlet temperature °C 2.00 12.00
Evaporation temperature (dew) °C 2.00
Superheating K 5.00
Outlet temperature °C 7.00 6.00
Flow rate kg/h | kg/s 2310 5.959
- inlet vapor kg/h 0.0000
Fluid vaporized kg/h 2310

PLATE HEAT EXCHANGER Side 1 Side 2


Total heat transfer area m² 8.05
Heat flux kW/m² 18.6
Mean temperature difference K 7.07
O.H.T.C. (available/required) W/m²,°C 3020/2640
Pressure drop -total* kPa 7.62 51.5
- in ports kPa 0.185 1.73
Pressure drop in fluid distribution kPa 0.000 - 0.000
Operating pressure - outlet kPa 3670
Number of channels per pass 31 32
Number of plates 64
Oversurfacing % 14
Fouling factor m²,°C/kW 0.048
Port diameter mm 63.0/42.0 63.0/63.0
(up/down) (up/down)
Recommended inlet connection diameter mm From 5.98 to 9.45
Recommended outlet connection diameter mm From 17.7 to 39.6
Reynolds number 1393
Outlet port velocity m/s 1.98 1.91

Date Page
www.swep.net 2019-06-10 1(3)
SWEP International AB
Box 105, Hjalmar Brantings väg 5
SE-261 22 Landskrona, Sweden
www.swep.net

SSP G8 -

PHYSICAL PROPERTIES Side 1 Side 2


Reference temperature °C 2.04 8.88
Liquid - Dynamic viscosity cP 0.0959 1.35
- Density kg/m³ 915.2 999.8
- Heat capacity kJ/kg,°C 2.609 4.195
- Thermal conductivity W/m,°C 0.1080 0.5779
Vapor - Dynamic viscosity cP 0.0150
- Density kg/m³ 104.1
- Heat capacity kJ/kg,°C 1.965
- Thermal conductivity W/m,°C 0.02038
- Latent heat kJ/kg 224.7
Film coefficient W/m²,°C 11100 10200
Minimum wall temperature °C 3.95 4.22
Maximum wall temperature °C 10.52 10.69
Largest wall temperature difference K 0.68
Channel velocity m/s 0.609 0.570
Shear stress Pa 77.5

TOTALS Side 1 Side 2


Total weight kg 29.97
Hold-up volume, inner circuit dm³ 5.332
Hold-up volume, outer circuit dm³ 6.464
Port size F1/P1 mm 63
Port size F2/P2 mm 63
Port size F3/P3 mm 42
Port size F4/P4 mm 63
NND F1/P1 mm 65
NND F2/P2 mm 65
NND F3/P3 mm 42
NND F4/P4 mm 65
Carbon footprint kg 210.61
Plate Material 304 Stainless Steel
Braze material Copper
Max operating pressure bar 50/44 / 31/27
Test pressure bar 87 / 53
Max working temperature °C 135/225

DIMENSIONS
A mm 620 +/-2
B mm 202 +/-1
C mm 538 +/-1
D mm 112 +/-1
E (F-side) mm 54
E (P-side) mm 0
F mm 136.24
G mm 0 +/-1
H mm 530 +/-1
I mm 120 +/-1
K mm 45
N mm 45
R mm 45

Date Page
www.swep.net 2019-06-10 2(3)
SWEP International AB
Box 105, Hjalmar Brantings väg 5
SE-261 22 Landskrona, Sweden
www.swep.net

SSP G8 -

Note :
Thermosyphon option used.
Very high heat flux not experimentally certified (18 kW/m²).
Evaporator performance prediction does not use two phase correction factors.

Disclaimer: Data used in this calculation is subject to change without notice. SWEP strives to use ”best practice” for the calculations leading to the
above results. Calculation is intended to show thermal and hydraulic performance, no consideration has been taken to mechanical strength of the
product. Product restrictions - such as pressure, temperatures and corrosion resistance- can be found in SWEP product sheets and other
technical documentation. SWEP may have patents, trademarks, copyrights or other intellectual property rights covering subject matter in this
document. Except as expressly provided in any written license agreement from SWEP, the furnishing of this document does not give you any
license to these patents, trademarks, copyrights, or other intellectual property. To the maximum extent permitted by applicable law, the software,
the calculations and the results are provided without warranties of any kind, whether express or implied. No advice or information obtained through
use of the software (including information provided in the results), will create any warranty not expressly stated in the applicable license terms.
Without limiting the foregoing, SWEP does not warrant that the content (including the calculations and the results) is accurate, reliable or correct.
SWEP does not warrant that any system comprising heat exchanger and other components, installed on the basis of calculations in this software,
will meet your requirements or function to your satisfaction or expectations.

*Excluding pressure drop in connections.

ee0efa26-0146-4f49-8491-
f3f45c41fc11

Date Page
www.swep.net 2019-06-10 3(3)