NSF Lead Free
Function/Installation position
Function
Type 6320 LF
The Type 6320 LF thermostatic balancing valve is intended for
use in hot water circulating systems utilizing circulation
advantages
pumps. The valve regulates the flow rate by continuously
•• Simple regulator operation
sensing the water temperature with a thermostat. The
•• Virtually maintenance-free
hydraulic balancing is thus automatically maintained.
•• Automatic adjustment of the flow volume (hydraulic
Materials balance)
All wetted parts are made of lead free brass, copper, stainless •• Shorter heat-up phase after temperature drop
steel or high-grade plastic. •• Energy saving
Installation position
The Type 6320 LF thermostatic balancing valve can be installed
in the vertical or horizontal position.
Operating Parameters
Standards
• NSF Standard 61 - Drinking Water System Components -
Health Effects
• NSF 372 - Drinking Water System Components – Lead
Content
2
Construction
Scale ring
O-Ring, EPDM
Thermostat
Working spring
Planning instruction
Even with thermostatic balancing waves such as the Type 6320 flow rate and the necessary pressure drop lies within the
LF, it is necessary to configure the system with a simple piping acceptable flow range area in Table 1.1.
layout.
In the appropriate configuration, with the most hydraulically
In order to select the suitable pump, the heat loss of the entire remote pipe line, the installation of a Type 6320 LF flow regu-
system has to be determined, in accordance with good engi- lator can be avoided and it can be replaced by a isolation valve.
neering practice, and converted to gpm for each branch and The isolation valve should be fully opened in the most hydrauli-
the mains. The pressure (head) loss is calculated from the cally remote branch.
elevation and friction loss of the most hydraulically remote
The installation of check valves are recommended to prevent
pipe line. The pressure loss of the Type 6320 LF in this pipe line
backflow into branches during maintenance or repair
is measured on the cVmax line on Table 1.1.
operations.
The pump performance of excessively strong pumps are to be
For questions and information on application technology,
throttled at the pump. The Type 6320 LF must not be used to
please contact our technical advisors or the technical customer
throttle the pump (maximum differential pressure = 5.8 psi).
service.
The thermostatic balancing valves in the remaining pipe lines
are to be selected in such a way that the intersection of the
3
Table 1.1 - Pressure Loss through Type 6320 LF
5.8
5
4
2
1.5
al
3
.3
p (PSI)
*
0.2
=2
tim
v=
Cv
C
x.
n.
Ma
Op
Mi
0.1
0.01
0.04 0.1 0.15 0.25 0.35 0.5 0.75 1 1.5 2 3 4 5 8.8
GPM
Optimal design area
Acceptable design area
Maximum admissible differential pressure 5.8 PSI
*Design Cv = 1.27
4
Sample installation upper distribution conventional
ft3
single circulation
Text SIA
Cold water
Hot water
Circulation
Stop valve
Non-return valve
Swing check valve
Type 6320 LF balancing valve
Circulation pump
Drain cock
Ball valve
5
Type 6320 LF/Screw connections
6
Adjustment/Setting ranges of the Type 6320 LF thermostatic
balancing valve
Setting of the balancing valve Adjusting the balancing valve
All balancing valve in the system must be adjusted to the same The factory setting of the Type 6320 LF balancing valve can be
scale values. The settings value are shown in the table below. changed as follows:
The calibration of the individual circulation lines takes place Put Allen key into the hexagon socket. Turning the key clock-
automatically. wise lowers the circulation set point temperature, turning it
counterclockwise raises the circulation set point temperature.
Transport packaging
The packing of the Type 6320 LF balancing valve also serves as
thermal insulation.
Maintenance
• The Type 6320 LF balancing valve operates virtually
maintenance-free.
• The instruction booklet supplied with the valve should
be given to the building owner after installation and
commissioning.
7
GF Piping Systems
The technical data are not binding. They neither constitute expressly
warranted characteristics nor guaranteed properties nor a
guaranteed durability.
They are subject to modification. Our General Terms of Sale apply.
Contact us
Tel. (714) 731-8800, Toll Free (800) 854-4090
Fax (714) 731-6201
us.ps@georgfischer.com
www.gfpiping.com