Professional Documents
Culture Documents
Outdoor Condenser
D irect Feed to Space
Outdoor Condenser
D HGR
O/A
D
D HGR D
X
O/A X
S/A Rate of energy removal required (BTU/hr) =
Dehumidifier Main Air Handler
E/A
CONDITIONED SPACE This energy removal rate is then compared to the capacities for
various dehumidification systems to help determine the best sys-
tem for the application.
Figure 2) Direct Feed of Pretreated Air to Interior Space Note that the total enthalpy method simplifies the sizing discus-
sion by focusing on total energy removal (combined latent and
sensible) rather than on a moisture load (often presented in lb/hr)
to be handled by the dehumidifier. Instead of trying to develop a
C alculating Energy Removal Requirements moisture load from dewpoint and wet bulb values, the values are
used directly to arrive at the required dehumidifier capacity.
The air entering the dehumidification system is 100% outside air.
Proper system size is selected by calculating the amount of ener- The ASHRAE guidelines in Table 1 state the design condition sim-
gy that must be removed from entering air at the maximum ply as a peak wet bulb temperature. Associated with that temper-
design condition to achieve a desired leaving air dewpoint (LAD). ature is a wet bulb line on the psychrometric chart. Sizing for the
The most direct calculation method is known as the total enthalpy enthalpy difference between the peak wet bulb and the leaving air
method. It is based on the enthalpy difference (BTU/lb) between dewpoint will ensure that the dehumidifier can handle the wide
the maximum design condition and the specified leaving air con- variety of dry bulb temperature / RH combinations that fall along
dition, multiplied by the air flow.
WET BULB TEMPERATURES (°F)
Rate of energy removal required (BTU/hr) =
City 1% City 1% City 1% City 1%
AK Anchorage 60 Fort Wayne 77 Las Vegas 71 Lubbock 73
Enthalpy difference ∆H (BTU/lb) x air flow Birmingham 78
IN
Indianapolis 78
NV
Reno 64 TX Odessa 73
AL
(cu ft/min) x 4.5 (min/hr x lb/cu ft) Mobile 80 KS Wichita 77 Albany 75 San Antonio 77
AR Little Rock 80 KY Louisville 79 Buffalo 74 UT Salt Lake City 66
AZ Phoenix 76 Baton Rouge 80 NY New York 76 Norfolk 79
The 4.5 is a conversion factor of 60 min- Long Beach 70 LA New Orleans 81 Rochester 75 VA Richmond 79
utes/hour divided by 13.5 cu ft/lb (of air), Los Angeles AP 70 Shreveport 79 Syracuse 75 Roanoke 75
Sacramento 72 MA Boston 75 Cincinnati 77 VT Burlington 74
and CFM is the specified outside air volume. CA
San Diego 71 MD Baltimore 80 OH Cleveland 76 Seattle 69
Since the weight of air varies with tempera- San Francisco AP 65
ME
Caribou 71 Columbus 77 WA Spokane 65
Santa Barbara 68 Portland 74 OK Oklahoma City 78 Yakima 68
ture, further accuracy could be gained by Stockton 71 Detroit 76 Eugene 69 Green Bay 76
OR
using the precise weights for the two differ- CO Denver 64 Flint 76 Portland 69 WI Madison 77
MI
ent temperatures involved, but this approxi- CT Hartford 77 Grand Rapids 75 Erie 75 Milwaukee 76
DC Washington Nat’l 78 Sault St. Marie 72 Philadelphia 77 WV Charleston 76
mation is nearly always sufficient for sizing DE Wilmington 77 Duluth 72
PA
Pittsburgh 74 WY Cheyenne 65
purposes. Daytona Beach 80 MN Rochester 77 Scranton 74
CANADA
Fort Myers 80 St. Paul 77 RI Providence 75
Jacksonville 79 Kansas City 78 Charleston 81 AL Calgary 65
MO SC
The enthalpy difference is calculated by tak- Miami 79 St. Louis 78 Columbia 79 BC Vancouver 68
FL
Orlando Jackson
ing the enthalpy value (BTU/lb) at the enter- 79
MS
79 SD Sioux Falls 76 MN Winnipeg 75
Pensacola 80 Meridian 80 Bristol 75 NB Saint John 70
ing wet bulb temperature and subtracting the Tallahassee 79 MT Billings 67 Chattanooga 78 NF St. John’s 69
enthalpy value at the design dewpoint. Table Tampa 79 Wilmington 81 TN Knoxville 77 NS Halifax 69
Atlanta 77 NC Charlotte 77 Memphis 80 Ottawa 75
1 provides typical design wet bulb values for GA
Augusta 79 Raleigh 78 Nashville 78 Sudbury 72
major cities. (The data in Table 1 is taken HI Honolulu 76 ND Fargo 76 Brownsville 80 ON Thunder Bay 72
Des Moines 78 Omaha 78 Corpus Christi 80 Toronto
from Table 1B of ASHRAE 97 Fundamentals.) IA
Dubuque 77
NE
Concord Dallas 78
75
NH 74 Windsor 77
Table 2 lists enthalpy values at various dew- ID Boise 68 Atlantic City 78
TX
El Paso 69 Montreal 75
NJ QC
point temperatures. IL
Chicago 79 Newark 77 Fort Worth 78 Quebec 74
Rockford 77 NM Albuquerque 66 Houston 80 SK Regina 72
or beneath the wet bulb line. (See Figure 3.) A dehumidifier sized 80 14 55 10 60
to remove the necessary energy to meet a 78°F wet bulb require- 78 12 55 9 59
ment for St. Louis, for example, will also handle 85°F up to 70%
76 10 55 - -
RH or 90°F up to 60% RH. If the dehumidifier was tested at dif-
ferent points along the wet bulb line, the amounts of latent versus 74 9 54 7-1/2 59
sensible heat removed would change significantly, but the total 72 7-1/2 57 6 59
heat removed would not. 70 7-1/2 55 6 57
rh(%)
80 60
160
68 6 55 - -
66 5 55 5 60
h(Btu/lbm)
40 140
Table 3) Dehumidifier Sizing
Total
120 The total energy removal required, and therefore the dehumidifi-
Enthalpy 35
BTU/LB O/A Wet Bulb Line cation capacity needed, is directly proportional to air flow.
100 Conversely, for the same air flow, a lower leaving air dewpoint can
30 be achieved by moving to a dehumidification system with greater
80 capacity.
25 W
(grains/lbm)
For example, compare the performance of two dehumidifiers with
60
20
entering air at 78°F wet bulb, a 2000 CFM air flow requirement to
Dew Point of Leaving meet ASHRAE 62, and a required leaving air dewpoint of 55°F or
15 40 lower to match the original design conditions for an existing air
handler. (See Table 3 for the capacities.) At an air flow of 2000
20 CFM, the smaller unit can only produce a leaving air dewpoint of
60°F, which will not meet our 55°F requirement. The larger unit, at
the 2000 CFM air flow, can produce a leaving air dewpoint of
40 50 60 70 80 90 100 55°F, and would be acceptable for this application.
t(°F)
55
Thus, the designer can specify the dry bulb temperature (or tem-
perature range) and the RH of the pretreated outside air going
into the air handler. Any energy required to warm the dehumidi-
fied air is recovered from the moisture removal process rather
than being added using a heater. In contrast, when a standard air
conditioner is used to remove large amounts of moisture from air,
the leaving air is unacceptably cold unless a substantial amount of
electric reheat is used. The result of using air conditioning for
moisture removal is significantly increased operating costs. (Refer
to Desert Aire Technical Bulletin 16 for a detailed analysis of
reheat technologies and energy savings.)