You are on page 1of 8

CHAPTER 19

EVAPORATIVE AIR COOLING EQUIPMENT


Direct Evaporative Air Coolers ..................................................................................................... 19.1
Indirect Evaporative Air Coolers................................................................................................... 19.2
Indirect/Direct Combinations ....................................................................................................... 19.4
Air Washers ................................................................................................................................... 19.5
Humidification/Dehumidification .................................................................................................. 19.6
Maintenance and Water Treatment ............................................................................................... 19.7

T HIS CHAPTER addresses direct and indirect evaporative


equipment, air washers, and their associated equipment used
for air cooling, humidification, dehumidification, and air cleaning.
eliminating the need for terminal reheat in some applications. In
such systems, air may exit below the initial wet-bulb temperature.
Direct evaporative coolers for a residences in desert regions typ-
Residential and industrial humidification equipment are covered in ically require 70% less energy than direct expansion air condition-
Chapter 20. ers. For instance, in El Paso, Texas, the typical evaporative cooler
Principle advantages of evaporative air conditioning include: consumes 609 kWh per cooling season as compared to 3901 kWh
per season for a typical vapor compression air conditioner with a
• Substantial energy and cost savings
SEER 10. This equates to an average demand of 0.51 kW based on
• Reduced peak power demand 1200 operating hours, as compared to an average demand of
• Improved indoor air quality 3.25 kW for a vapor compression air conditioner.
• Life cycle cost effectiveness Depending on climatic conditions, many buildings can use indi-
• Easily integrated into built-up systems rect/direct evaporative air conditioning to provide comfort cooling.
• Wide variety of packages available Indirect/direct systems realize a 40 to 50% energy savings in mod-
• Provide humidification and dehumidification when needed erate humidity zones (Foster and Dijkstra 1996).
• Easy to use with direct digital control (DDC)
• Reduced pollution emissions DIRECT EVAPORATIVE AIR COOLERS
• No chlorofluorocarbon (CFC) usage
In direct evaporative air cooling, air is drawn through porous
Packaged direct evaporative air coolers, air washers, indirect wetted pads or a spray and its sensible heat energy evaporates some
evaporative air coolers, evaporative condensers, vacuum cooling water; the heat and mass transfer between the air and water lowers
apparatus, and cooling towers exchange sensible heat for latent the air dry-bulb temperature and increases the humidity at a constant
heat. This equipment falls into two general categories: (1) apparatus wet-bulb temperature. The dry-bulb temperature of the nearly satu-
for air cooling and (2) apparatus for heat rejection. This chapter rated air approaches the ambient air’s wet-bulb temperature. The
addresses air-cooling equipment. process is adiabatic, so no sensible cooling occurs.
Adiabatic evaporation of water provides the cooling effect of Saturation effectiveness is a key factor in determining the perfor-
evaporative air conditioning. In direct evaporative cooling, water mance of an evaporative cooler. The extent to which the leaving air
evaporates directly into the airstream, thus reducing the air’s dry- temperature from a direct evaporative cooler approaches the ther-
bulb temperature while humidifying the air. Direct evaporative modynamic wet-bulb temperature of the entering air or the extent to
equipment cools air by direct contact with the water, either by an which complete saturation is approached is expressed as the direct
extended wetted-surface material (as in packaged air coolers) or saturation effectiveness, which is defined as:
with a series of sprays (as in an air washer).
In indirect evaporative cooling, secondary air removes heat t1 – t 2
from primary air via a heat exchanger. In one indirect method of εe = 100 -------------- (1)
cooling, water is evaporatively cooled by a cooling tower and cir- t 1 – t’
culates through a heat exchanger. Supply air to the space passes over
the other side of the heat exchanger. In another common method, where
one side of an air-to-air heat exchanger is wetted and removes heat εe = direct evaporative cooling or saturation effectiveness, %
from the conditioned supply airstream on the dry side. Even in t1 = dry-bulb temperature of entering air, °C
regions with high wet-bulb temperatures, indirect evaporative cool- t2 = dry-bulb temperature of leaving air, °C
ing can be economically feasible. t′ = thermodynamic wet-bulb temperature of entering air, °C
Direct and indirect evaporative processes can be combined
(indirect/direct). The first stage (indirect) sensibly cools the air, An efficient wetted pad (with a high saturation effectiveness) can
which is then passed through the second stage (direct) and evapora- reduce the air dry-bulb temperature by as much as 95% of the wet-
tively cooled further. Combination systems use both direct and indi- bulb depression (ambient dry-bulb temperature less wet-bulb tem-
rect evaporative principles as well as secondary heat exchangers perature), while an inefficient and poorly designed pad may only
and cooling coils. The secondary heat exchangers enhance both reduce this by 50%, or less.
cooling and heat recovery (in winter), and the coils provide addi- Although direct evaporative cooling is simple and inexpensive, it
tional cooling/dehumidification as needed. The secondary heat has the disadvantage that if the ambient wet-bulb temperature is
exchanger has been used in both dual duct systems and in unitary higher than about 21°C, the cooling effect is not sufficient for indoor
packages. The secondary heat exchanger can also save energy by comfort cooling; however, cooling is still sufficient for relief cool-
ing applications (e.g., greenhouses, industrial cooling, etc.). Direct
The preparation of this chapter is assigned to TC 5.7, Evaporative Cooling. evaporative coolers should not recirculate indoor air.

19.1
19.2 2000 ASHRAE Systems and Equipment Handbook (SI)

Fig. 1 Typical Random-Media Evaporative Cooler

Random-Media Air Coolers


These coolers contain evaporative pads, usually of aspen wood
or absorbent plastic fiber/foam (Figure 1). A water-recirculating
pump lifts the sump water to a distributing system, and it flows Fig. 2 Typical Rigid-Media Air Cooler
down through the pads back to the sump.
A fan in the cooler forces air through the evaporative pads and absorb water yet resist the weathering effects of water. The medium
delivers it to the space to be cooled. The fan discharges either is cross-corrugated to maximize mixing of air and water. In the
through the side of the cooler cabinet or through the sump bottom. direction of airflow, the depth of medium is commonly 300 mm, but
Random-media packaged air coolers are made as small tabletop it may be between 100 and 600 mm. The medium has the desirable
coolers (0.02 to 0.09 m3/s), window units (0.05 to 2.1 m3/s), and characteristics of low resistance to airflow, high saturation effec-
standard duct-connected coolers (2.4 to 8.5 m3/s). Cooler selection tiveness, and self-cleaning by flushing the front face of the pad. The
should be based on a capacity rating from an independent agency. rigid medium is usually designed for a face velocity of 2 to 3 m/s.
When clean and well maintained, commercial random-media air Direct evaporative air coolers using this material are built to han-
coolers operate at an effectiveness of approximately 80% and dle as much as 280 m3/s with or without fans. Saturation effective-
remove 10 µm and larger particles from the air. In some units, sup- ness varies from 70 to over 95%, depending on media depth and air
plementary filters ahead of or following the evaporative pads keep velocity. Air flows horizontally while the recirculating water flows
particles from entering the cooler, even when it is operated without vertically over the medium surfaces by gravity feed from a flooding
water to circulate fresh air. The evaporative pads may be chemically header and water distribution chamber. The header may be con-
treated to increase wettability. An additive may be included in the nected directly to a pressurized water supply for once through oper-
fibers to help them resist attack by bacteria, fungi, and other micro- ation (i.e. gas turbines and clean rooms), or a pump may recirculate
organisms. the water from a lower reservoir, which is constructed of heavy gage
Random-media coolers are usually designed for an evaporative corrosion-resistant material. The reservoir is also fitted with over-
pad face velocity of 0.5 to 1.3 m/s, with a pressure drop of 25 Pa. flow and positive flowing drain connections. The upper media
Aspen fibers are packed to approximately 1.5 to 2 kg/m2 of face area enclosure is fabricated of reinforced galvanized steel or other cor-
based on a 50 mm thick pad. Pads are mounted in removable lou- rosion-resistant sheet metal, or of plastic.
vered frames, which are usually made of painted galvanized steel or Flanges at the entering and leaving faces allow the unit to be con-
molded plastic. Troughs distribute water to the pads. A centrifugal nected to ductwork. In recirculating water systems, a float valve
pump with a submerged inlet pumps the water through tubes that maintains proper water level in the reservoir, makes up water that
provide an equal flow of water to each trough. It is important that has evaporated, and supplies fresh water for dilution to prevent an
pumps used are thermally protected. The sump or water tank has a overconcentration of solids and minerals. Because the water recir-
water makeup connection, float valve, overflow pipe, and drain. culation rate is low and because high pressure nozzles are not
Provisions to bleed water to prevent the buildup of minerals, dirt, needed to saturate the medium, pumping power is low when com-
and microbial growth are typically incorporated in the design. pared to spray-filled air washers with equivalent evaporative cool-
The fan is usually a forward-curved, centrifugal fan, complete ing effectiveness.
with motor and drive. The V-belt drive may include an adjustable
pitch motor sheave to allow the fan speed to be increased to use the Remote Pad Evaporative Cooling Equipment
full motor capacity at higher airflow resistance. The motor enclo- Greenhouses, poultry buildings, hog buildings, and similar
sure may be drip-proof, totally enclosed, or a semi-open type spe- applications use exhaust fans installed in the wall or roof of the
cifically designed for evaporative coolers. structure. Air is evaporatively cooled as it is drawn through pads
located on the other end of the building. The pads are wetted from
Rigid-Media Air Coolers above by a perforated pipe and excess water is collected for recir-
Blocks of corrugated material make up the wetted surface of culation. In some cases, the pads are wetted with high pressure fog-
rigid-media direct evaporative air coolers (Figure 2). Materials ging nozzles. In this case, the fog provides additional cooling. Water
include cellulose, plastic, and fiberglass that have been treated to from fogging nozzles must never be recirculated. The pad should be
Evaporative Air Cooling Equipment 19.3

sized for an air velocity of approximately 0.8 m/s for random-media


pads, 1.3 m/s for 100 mm rigid media, and 2.2 m/s for 150 mm rigid
media.

INDIRECT EVAPORATIVE AIR COOLERS


Indirect Packaged Air Coolers
In indirect evaporative air coolers, outdoor air or exhaust air
from the conditioned space passes through one side of a heat
exchanger. This air (the secondary airstream) is cooled by evapora-
tion by one of several methods: (1) direct wetting of the heat
exchanger surface, (2) passing through evaporative cooling media,
(3) atomizing spray, (4) disk evaporator, etc. The surfaces of the
heat exchanger are cooled by the secondary airstream. On the other
side of the heat exchanger surface, the primary airstream (condi- Fig. 3 Indirect Evaporative Cooler Used as Precooler
tioned air to be supplied to the space) is sensibly cooled by the heat
exchanger surfaces.
Although the primary air is cooled by secondary air, no moisture indirect evaporative cooling stage is less than the energy saved from
is added to the primary air. Hence, the process is known as indirect reducing the load on the refrigeration apparatus. As a result, for
evaporative air cooling. The supply (primary) air may be recircu- existing refrigeration and air conditioning, the overall efficiency
lated room air, outside air, or a mixture of these. The enthalpy of the may increase because the energy cost and demand are reduced. For
primary airstream decreases because no moisture is added to it. This new installations the refrigeration unit may be downsized resulting
process contrasts with direct evaporative cooling, which is essen- in (1) lower overall cost for the project, and (2) lower operational
tially adiabatic (constant wet-bulb temperature). The usefulness of cost and peak demand. Indirect evaporative cooling may also reduce
indirect evaporative cooling is related to the depression of the wet- the total time the refrigeration equipment must be operated during a
bulb temperature of the secondary air below the dry-bulb tempera- year, which reduces wear and tear on the refrigeration equipment.
ture of the entering primary air. Because the secondary airstream is Evaporatively cooled air can be discharged across air-cooled
evaporatively cooled rather than the primary airstream, indirect refrigeration condenser coils to improve the efficiency of the con-
evaporative cooling is effective in almost any air conditioning denser. Chapter 50 of the 1999 ASHRAE Handbook—Applications
application regardless of geographic location (Mathur 1990, 1991). includes sample evaporative cooling calculations. Manufacturers’
Because the enthalpy of the primary air decreases in an indirect data should be followed to select equipment for cooling perfor-
evaporative cooler, the leaving dry-bulb temperature of the primary mance, pressure drop, and space requirements.
air must always be above the entering wet-bulb temperature of the Indirect evaporative cooling effectiveness εIe is defined as
secondary airstream. Dehumidifying in the primary airstream can
occur only when the dew point of the primary airstream is several t1 – t 2
ε Ie = 100 --------------- (2)
degrees higher than the wet-bulb temperature of the secondary air- t 1 – t s’
stream. This condition exists only when the secondary airstream is
drier than the primary airstream, such as when building exhaust air where
is used for the secondary air. εe = indirect evaporative cooling effectiveness, %
A packaged indirect evaporative air cooler includes a heat t1 = dry-bulb temperature of entering primary air, °C
exchanger, a wetting apparatus, a secondary air fan assembly, a sec- t2 = dry-bulb temperature of leaving primary air, °C
ondary air inlet louver, and an enclosure. The heat exchanger may ts′ = wet-bulb temperature of entering secondary air, °C
be constructed with folded metal or plastic sheets, with or without a
corrosion-resistant or moisture-retaining coating; or it may be con- Manufacturers’ ratings require careful interpretation. The basis
structed with tubes, so that one airstream flows inside the tubes and of ratings should be specified because, for the same apparatus, per-
the other flows over the exterior tube surfaces. Air filters may be formance is affected by changes in primary and secondary air veloc-
placed upstream of the primary and secondary heat exchangers to ities and mass flow rates, wet-bulb temperature, altitude, and other
minimize fouling by dust, insects, or other airborne contaminants. factors.
Continuous bleed-off and fresh water makeup is necessary to Typically, the air resistance on both primary and secondary sec-
keep the concentration of minerals and contaminants in the water tions ranges between 50 and 500 Pa. The ratio of secondary air to
from rising. In all evaporative cooling systems water quality should conditioned primary air may range from less than 0.3 to greater than
be controlled to avoid scale and other deposits. Water treatment may 1.0 and has an effect on performance (Peterson 1993). Based on
be necessary to control corrosion of heat exchanger surfaces and manufacturers’ ratings, available equipment may be selected for
other metal parts. indirect evaporative cooling effectiveness ranging from 40 to 80%.
The packaged indirect evaporative air cooler may be either self-
contained, with its own primary air supply fan assembly, or part of Heat Recovery
a built-up or more complete packaged air-handling system. The Indirect evaporative cooling has been applied to a number of heat
cooler may include a single stage of indirect evaporative cooling, or recovery systems including plate type heat exchangers (Scofield
it may include indirect evaporative cooling as the first stage, with and DesChamps 1984); heat pipe heat exchangers (Mathur 1991,
additional direct evaporative cooling and/or refrigerated (chilled Scofield 1986); rotary regenerative heat exchangers (Woolridge et
water or direct-expansion) cooling stages. al. 1976); two phase thermosiphon loop heat exchangers (Mathur
When the indirect evaporative cooler is placed in series 1990). Indirect evaporative cooling/heat recovery can be used as a
(upstream) with a conventional refrigerated coil, it reduces the sen- retrofit on existing systems, which results in lower operational cost
sible load on the coil and refrigeration system (Figure 3). Energy and peak demand. For new installations, the equipment can be
required for the indirect cooling stage includes the pump and second- downsized, resulting in lower overall cost of the project as well as
ary air fan motor, as well as some additional fan energy to overcome lower operational cost. Chapter 44 has more information on the use
resistance added in the primary air. The energy consumed by the of indirect evaporative cooling with heat recovery.
19.4 2000 ASHRAE Systems and Equipment Handbook (SI)

Cooling Tower/Coil Systems


The combination of a cooling tower or other evaporative water
cooler with a water-to-air heat exchanger coil and water circulating
pump is another type of indirect evaporative cooling. Water is
pumped from the reservoir of the cooling tower to the coil and
returns to the upper distribution header of the tower. Both open-
water and closed-loop systems are used. Coils in open systems
should be cleanable.
The recirculated water is evaporatively cooled to within a few
degrees of the wet-bulb temperature as it flows over the wetted sur-
faces of the cooling tower. As the cooled water flows through the
tubes of the coil in the conditioned airstream, it picks up heat from
the conditioned air. The temperature of the water increases, and the
primary air is cooled without the addition of moisture to the primary
air. The water is again cooled as it recirculates through the cooling
tower. A float valve controls the fresh-water makeup, which
replaces the evaporated water. Bleed-off prevents excessive con-
centration of minerals in the recirculated water.
One advantage of a cooling tower, especially for retrofit applica-
tions, large built-up systems, and dispersed air handlers, is that it
may be remotely located from the cooling coil. Also, the tower is
more accessible for maintenance. Overall indirect evaporative cool- Fig. 4 Combination Indirect/Direct Evaporative
ing effectiveness εe may range between 55% and 75% or higher. If Cooling Process
return air is sent to the cooling tower of an indirect cooling system
(before being discharged outside), the cooling tower should be spe-
cifically designed for this purpose. These coolers wet a medium that
has a high ratio of wetted surface area per unit of medium volume.
Performance depends on depth of the medium, air velocity over the
medium surface, water flow to airflow ratio, wet-bulb temperature,
and water-cooling range. Because of the close approach of the water
temperature to the wet-bulb temperature, the overall effectiveness
may be higher than that of a conventional cooling tower.

Other Indirect Evaporative Cooling Apparatus


Other combinations of evaporative coolers and heat exchange
apparatus can accomplish indirect evaporative cooling. Heat pipes
and rotary heat wheels, plate and pleated media, and shell-and-tube Fig. 5 Indirect/Direct Evaporative Cooler with Heat
heat exchangers have all been applied in this manner. If the condi- Exchanger (Rotary Heat Wheel or Heat Pipe)
tioned (primary) air and the exhaust or outside (secondary) air-
stream are side by side, a heat pipe or heat wheel can transfer heat This method can lower the supply air dry-bulb temperature by 6 K
from the warmer air to the cooler air. Evaporative cooling of the sec- or more below the secondary air wet-bulb temperature.
ondary airstream by spraying water directly on the surfaces of the In areas where the 0.4% mean coincident wet-bulb design tem-
heat exchanger or by a direct evaporative cooler upstream of the perature is 19°C or lower, average annual cooling power consumption
heat exchanger may cool the primary air indirectly by transferring of indirect/direct systems may be as low as 0.06 kW/kW of refrigera-
heat from it to the secondary air. tion. When the 0.4% mean coincident wet-bulb temperature is as high
as 23°C, indirect/direct cooling can have an average annual cooling
INDIRECT/DIRECT COMBINATIONS power consumption as low as 0.23 kW/kW. By comparison, the typi-
In a two-stage indirect/direct evaporative cooler, a first-stage cal refrigeration system with an air-cooled condenser may have an
indirect evaporative cooler lowers both the dry- and wet-bulb tem- average annual power consumption greater than 0.28 kW/kW.
perature of the incoming air. After leaving the indirect stage, the In dry environments, indirect/direct evaporative cooling is usu-
supply air passes through a second-stage direct evaporative cooler; ally designed to supply 100% outdoor air to the conditioned spaces
Figure 4 shows the process on a psychrometric chart. First-stage of a building. In these once-through applications, space latent loads
cooling follows a line of constant humidity ratio because no mois- and return air sensible loads are exhausted from the building rather
ture is added to the primary airstream. The second stage follows the than returned to the conditioning equipment. Consequently, the
wet-bulb line at the condition of the air leaving the first stage. cooling capacity required from these systems may be less than that
The indirect evaporative cooler may be any of the types required from a conventional refrigerated cooling system.
described previously. Figure 5 shows a cooler using a rotary heat In areas with a higher wet-bulb design temperature or where the
wheel. The secondary air may be exhaust air from the conditioned design requires a supply air temperature lower than that attainable
space or outdoor air. When the secondary air passes through the using indirect/direct evaporative cooling, a third cooling stage may
direct evaporative cooler, the dry-bulb temperature is lowered by be required. This stage may be a direct-expansion refrigeration unit
evaporative cooling. As this air passes through the heat wheel, the or a chilled water coil located either upstream or downstream from
mass of the medium is cooled to a temperature approaching the wet- the direct evaporative cooling stage, but always downstream from
bulb temperature of the secondary air. The heat wheel rotates so that the indirect evaporative stage. Refrigerated cooling is energized
its cooled mass enters the primary air and, in turn, sensibly cools the only when evaporative stages cannot achieve the required supply
primary (supply) air. Following the heat wheel, a direct evaporative air temperature. Figure 6 shows a schematic of a three-stage con-
cooler further reduces the dry-bulb temperature of the primary air. figuration (indirect/direct, with optional third-stage refrigerated
Evaporative Air Cooling Equipment 19.5

Makeup air cooling with an indirect/direct evaporative unit can


be applied both to standard packaged units and to large built-up sys-
tems. Either outside air or building exhaust air can be used as the
secondary air source, whichever has the lower wet-bulb tempera-
ture. Outside air is generally easier to cool, and in some cases it is
the only option because the building exhaust is so remote from the
makeup air inlet. If building exhaust air can be used, it has the
potential of heat recovery during cold weather. In general, outside
air cooling has higher energy savings and lower electrical demand
savings than return air cooling. These systems can reduce the out-
side air load a minimum of 50%, depending on climate and ventila-
tion requirements.
Fig. 6 Three-Stage Indirect/Direct Evaporative Cooler
AIR WASHERS
cooling). The third-stage refrigerated cooling coil is located down-
stream from the direct evaporative cooler. Spray-Type Air Washers
A single coil may be used to cool return chilled water with cooling
tower water and a plate heat exchanger (a form of indirect evapora- Spray-type air washers consist of a chamber or casing containing
tive cooling). This hybrid, three-stage configuration permits indirect spray nozzles, a tank for collecting spray water as it falls, and an
cooling when the wet-bulb temperature is low and mechanical cool- eliminator section for removing entrained drops of water from the
ing when the wet bulb is high or when dehumidification is necessary. air. A pump recirculates water at a rate higher than the evaporation
The designer should consider options using building exhaust rate. Intimate contact between the spray water and the air causes
and/or outside air as secondary air for the indirect evaporative cool- heat and mass transfer between the air and the water (Figure 7). Air
ing stage, whichever has the lower wet-bulb temperature. If possi- washers are commonly available from 1 to 120 m3/s capacity, but
ble, the indirect evaporative cooler should be designed to use both specially constructed washers can be made in any size. No standards
outside air and building exhaust as the secondary airstream; which- exist; each manufacturer publishes tables giving physical data and
ever source has the lower wet-bulb temperature would be used. ratings for specific products. Therefore, air velocity, water-spray
Dampers and an enthalpy sensor are used to control this process. If
the latent load in the space is significant, the wet-bulb temperature of
the building exhaust air in the cooling mode may be higher than that
of the outside air. In this case, outside air may be used more effec-
tively as secondary air to the indirect evaporative cooling stage.
Custom indirect/direct and three-stage configurations are avail-
able to permit many choices for location of the return, exhaust, and
outside air; mixing of airstreams; bypass of components, or variable
volume control. The elements that may be controlled include:
• Modulating outside air and return air mixing dampers
• Secondary air fans and recirculating pumps of an indirect evapo-
rative stage
• Recirculating pumps of a direct evaporative cooling stage
• Face and bypass dampers for the direct evaporative stage
• Chilled water or refrigerant flow for a refrigerated stage
• System or individual terminal volume with variable volume ter-
minals, fan variable inlet vanes, adjustable pitch fans, or variable-
speed fans.
For sequential control in indirect/direct evaporative cooling, the
indirect evaporative cooler is energized for first-stage cooling, the
direct evaporative cooler for second-stage cooling, and the refriger-
ation coil for third-stage cooling. In some applications, reversing
the sequence of the direct evaporative cooler and indirect evapora-
tive cooler may reduce the first-stage power requirement.

Precooling and Makeup Air Pretreatment


Evaporative cooling may be used to increase the capacity and
reduce the electrical demand of a direct expansion air conditioner or
chiller. Both the condenser and the makeup air may be evapora-
tively cooled by direct and/or indirect means.
The condenser may be cooled by adding a direct evaporative
cooler (usually without a fan) to the condenser fan inlet. The direct
evaporative cooler must add very little resistance to the airflow to
the condenser, and face velocities must be well below velocities that
would entrain liquid and carry it to the condenser. Maintenance of
condenser coolers should be infrequent and easy to perform. A well-
designed direct evaporative cooler can reduce electrical demand Fig. 7 Interaction of Air and Water in Air Washer
and energy consumption of refrigeration units from 10 to 30%. Heat Exchanger
19.6 2000 ASHRAE Systems and Equipment Handbook (SI)

density, spray pressure, and other design factors must be considered functional components. Such units are self-housed, pre-wired, pre-
for each application. piped, and ready for hoisting into place.
The simplest design has a single bank of spray nozzles with a The number and arrangement of nozzles vary with different
casing that is usually 1.2 to 2.1 m long. This type of washer is capacities and manufacturers. Adequate values of saturation effec-
applied primarily as an evaporative cooler or humidifier. It is some- tiveness and heat transfer effectiveness are achieved by using higher
times used as an air cleaner when the dust is wettable, although the spray density.
air-cleaning efficiency is relatively low. Two or more spray banks Eliminator blades come in varying shapes, but most are a series
are generally used when a very high degree of saturation is neces- of aerodynamically clean, sinusoidal shapes. Collected moisture
sary and for cooling and dehumidification applications that require flows down grooves or hooks designed into their profiles, then
chilled water. Two-stage washers are used for dehumidification drains into the storage tank. Washers may be built with shallow
when the quantity of chilled water is limited or when the water tem- drain pans and connected to a central storage tank. High-velocity
perature is above that required for the single-stage design. Arrang- washers are rectangular in cross section and, except for the elimina-
ing the two stages for counter-flow of the water permits a small tors, are similar in appearance and construction to conventional
quantity of water with a greater water temperature rise. lower velocity types. Pressure loss is in the range of 120 to 380 Pa.
The lengths of washers vary considerably. Spray banks are These washers are available either as freestanding separate devices
spaced from 0.8 to 1.4 m apart; the first and last banks of sprays are for incorporation into field-built central stations or in complete pre-
located about 0.3 to 0.5 m from the entering or leaving end of the assembled central station packages from the factory.
washer. In addition, air washers may be furnished with heating or
cooling coils in the washer chamber, which may affect the overall HUMIDIFICATION/DEHUMIDIFICATION
length of the washer.
Some water (even very soft water) should always be bled off to Humidification with Air Washers and Rigid Media
prevent mineral buildup and to retard microbial growth. When the Air can be humidified with air washers and rigid media in three
unit is shut down, all water should drain from the pipes. Low spots ways: (1) using recirculated water without prior heating of the air,
and dead ends must be avoided. Because an air washer is a direct (2) preheating the air and humidifying it with recirculated water,
contact heat exchanger, water treatment is critical for proper opera- and (3) preheating recirculated water. Precise humidity control may
tion as well as good hygiene. Algae and bacteria can be controlled be achieved by arranging rigid media in one or more banks in depth,
by a chemical or ozone treatment program and/or regularly sched- height, or width, or by providing a controlled bypass. Each bank is
uled mechanical cleaning. activated independently of the others to achieve the desired humid-
The resistance to airflow through an air washer varies with the ity. In any evaporative humidification application, air should not be
type and number of baffles, eliminators, and wetted surfaces; the permitted to enter the process with a wet-bulb temperature of less
number of spray banks and their direction and air velocity; the size than 4°C, otherwise the water may freeze.
and type of other components, such as cooling and heating coils; Recirculation Without Preheating. Except for the small
and other factors, such as air density. Pressure drop may be as low amount of energy added by the recirculating pump and the small
as 60 Pa or as high as 250 Pa. The manufacturer should be consulted amount of heat leakage into or from the apparatus (including the
regarding the resistance of any particular washer design combina- pump and its connecting piping), the process is adiabatic. The tem-
tion. perature of the water in the collection basin closely approaches the
The casing and the tank may be constructed of various materials. thermodynamic wet-bu1b temperature of the entering air, but it can-
One or more doors are commonly provided for inspection and not be brought to complete saturation. The psychrometric state
access. An air lock must be provided if the unit is to be entered while point of the leaving air is on the constant thermodynamic wet-bulb
it is running. The tank is normally at least 400 mm high with a 350 temperature line with its end state determined by the saturation
mm water level; it may extend beyond the casing on the inlet end to effectiveness of the device. Control over leaving humidity condi-
make the suction strainer more accessible. The tank may be parti- tions may be achieved by controlling the saturation effectiveness of
tioned by a weir (usually in the entering end) to permit recirculation the process by bypassing air around the evaporative process.
of spray water for control purposes in dehumidification work. The Preheating Air. Preheating the air entering an evaporative
excess then returns over the weir to the central water chilling humidifier increases both the dry-and the wet-bulb temperatures
machine. and lowers the relative humidity, but it does not alter the humidity
Eliminators consist of a series of vertical plates that are spaced ratio (mass ratio of water vapor to dry air) of the air. As a result, pre-
about 20 to 50 mm on centers at the exit of the washer. The plates are heating permits more water to be absorbed per unit mass of dry air
formed with a number of bends to deflect the air and obtain passing through the process at the same saturation effectiveness.
impingement on the wetted surfaces. Hooks on the edge of the Control is achieved by varying the amount of air preheating at a
plates improve moisture elimination. Perforated plates may be constant saturation effectiveness. Control precision is a direct func-
installed on the inlet end of the washer to obtain more uniform air tion of saturation effectiveness and a high degree of correlation may
distribution through the spray chamber. Louvers, which prevent the be achieved between leaving air and leaving dew-point tempera-
backlash of spray water, may also be installed for this purpose. tures when high saturation effectiveness devices are used.
Heated Recirculated Water. If heat is added to the water, the
High-Velocity Spray-Type Air Washers process state point of the mixture moves toward the temperature of
High-velocity air washers generally operate at air velocities in the heated water (Figure 7A). Elevating the water temperature
the range of 6 to 9 m/s. Some have been applied as high as 12 m/s, makes it possible to raise the air temperature, both dry bulb and wet
but 6 to 8 m/s is the most accepted range. The reduced cross-sec- bulb, above the dry-bulb temperature of the entering air with the
tional area of high-velocity air washers allows them to be used in leaving air becoming fully saturated. Relative humidity of the leav-
smaller equipment than those operating with lower air velocities. ing air can be controlled by (1) bypassing some of the air around the
High capacities per unit of space available from high-velocity spray media banks and remixing the two airstreams downstream by using
devices permit practical packaging of prefabricated central station dampers or (2) by automatically reducing the number of operating
units in either completely assembled and transportable form or, for media banks through pump staging or by operating valves in the dif-
large capacity units, easily handled modules. Manufacturers supply ferent distribution branches.
units with capacities of up to 70 m3/s shipped in one piece, including The following table shows the saturation or humidifying effec-
spray system, eliminators, pump, fan, dampers, filters, and other tiveness of a spray air washer for various spray arrangements. The
Evaporative Air Cooling Equipment 19.7

degree of saturation depends on the extent of contact between air Air Cleaning
and water. Other conditions being equal, a low-velocity airflow is
Air washers and rigid-media direct evaporative cooling equip-
conducive to higher humidifying effectiveness.
ment can remove particulate and gaseous contaminants with vary-
ing degrees of effectiveness through wet scrubbing (which is
Bank Arrangement Length, m Effectiveness, % discussed in Chapter 25). The particulate removal efficiency of rigid
1 downstream 1.2 50 to 60 media and air washers differ due to the differences in equipment
1 downstream 1.8 60 to 75 construction and principles of operation. Removal also depends
1 upstream 1.8 65 to 80 largely on the size, density, wettability, and/or solubility of the con-
2 downstream 2.4 to 3 80 to 90 taminants to be removed. Large, wettable particles are the easiest to
remove. The primary mechanism of separation is by impingement
2 opposing 2.4 to 3 85 to 95
of particles on a wetted surface, which includes eliminator plates in
2 upstream 2.4 to 3 90 to 98
air washers and the corrugations of wetted rigid media. The spray
process is relatively ineffective in removing most atmospheric
Dehumidification with Air Washers and Rigid Media dusts. Because the force of impact increases with the size of the
solid, the impact (together with the adhesive quality of the wetted
Air washers and rigid-media direct evaporative coolers may also surface) determines the device’s usefulness as a dust remover.
be used to cool and dehumidify air (Figure 7B). The heat and mois- In practice, the air-cleaning results of air washers and rigid-
ture removed from the air causes the water temperature to rise. If the media direct evaporative coolers are typical of comparable
entering water temperature is below the entering air dew point, both
impingement filters. Air washers are of little use in removing soot
the dry- and wet-bulb temperatures of the air is reduced, resulting in particles because of the absence of an adhesive effect from a greasy
cooling and dehumidification. The air is typically saturated as it surface. They are also relatively ineffective in removing smoke
leaves. The vapor pressure difference between the entering air and
because the particles are too small (less than 1 µm) to impact and be
the water cools the air. Moisture is transferred from the air to the retained on the wet surfaces.
water and condensation occurs. The air leaving an evaporative
Despite its air cleaning performance, rigid media should not be
dehumidifier is typically saturated, usually with less than 0.5 K dif-
used as a primary filtering device. When a rigid-media cooler is
ference between leaving dry- and wet-bulb temperatures.
placed in an unfiltered airstream, it can quickly become fouled with
The difference between the leaving air and leaving water temper- airborne dust and fibrous debris. When wet, debris can collect in the
atures depends on the difference between entering dry- and wet- recirculation basin and in the media where they can become nutri-
bulb temperatures and the effectiveness of the process, which may ents for bacteria. Bacteria in the air can propagate in waste materials
be affected by such factors as length and height of the spray cham- and debris and cause microbial slimes. Filtering of the entering air
ber, air velocity, quantity of water flow, and character of the spray is the most effective way to keep debris from accumulating in rigid
pattern. Final water conditions are typically 0.5 to 1 K below the media. When high efficiency filters are placed upstream from the
leaving air temperature, depending on the saturation effectiveness cells, most microbial agents and nutrients can be removed from the
of the device used. airstream. Rigid media should be replaced if the corrugations are
The common design value for the rise in water temperature usu- filled with contaminants when they are dry.
ally falls between 3 and 7 K for refrigerant chilled water and nor-
mal air conditioning applications, although higher rises are MAINTENANCE AND WATER TREATMENT
possible and have been used successfully. A smaller temperature
rise may be considered when water is chilled by mechanical refrig- Regular inspection and maintenance of evaporative coolers, air
eration. If warmer water is used, less mechanical refrigeration is washers, and ancillary equipment ensures proper service and effi-
required; however, a larger quantity of chilled water is needed to do ciency. Manufacturers’ recommendations for maintenance and
the same amount of sensible cooling. An economic analysis may be operation should be followed to help ensure safe and efficient oper-
required to determine the best alternative. For humidifiers receiv- ation. Water lines, water distribution troughs or sumps, pumps, and
ing water from a thermal storage or other low-temperature system, pump filters must be clean and free of dirt, scale, and debris. They
a design with a high temperature rise and minimum water flow may must be constructed so that they can be easily flushed and cleaned.
be desirable. Inadequate water flow causes dry areas on the evaporative media,
which reduces the saturation effectiveness. Motors and bearings
Performance Factors. A performance factor of 1.0 is assigned should be lubricated and fan drives checked periodically
to an evaporative dehumidifier if the device can cool and dehumid-
Water and air filters should be cleaned or replaced as required.
ify the entering air to a wet-bulb temperature equal to that of the
The sump water level must be maintained such that the bottom of
leaving water temperature. This represents a theoretical maximum
the pads does not contact the water in the sump, yet high enough to
value which is thermodynamically impossible to achieve. Perfor-
prevent air from short circuiting below the pads. Bleeding off some
mance is maximized when both water surface area and air –water
water is the most practical means to minimize scale accumulation.
contact is maximized. The actual performance factor Fp of any
The bleed rate should be 5 to 100% of the evaporation rate, depend-
evaporative dehumidifier will be less than one and would be calcu-
ing on water hardness and airborne contaminant level. The water
lated by dividing the actual air enthalpy change by the theoretical
circulation pump should be used to bleed off water because suction
maximum air enthalpy change where:
by a draw-through fan will otherwise prevent the bleed system from
operating effectively. A flush-out cycle that runs fresh water
h1 – h2 through the pad every 24 h when the fan is off may also be used.
F p = ----------------- (3)
h1 – h3 This water should run for 10 min for every metre of media height.
Regular inspections should be made to ensure that the bleed rate
where is adequate and is maintained. Some manufacturers provide a purge
cycle in which the entire sump is purged of water and accumulated
h1 = enthalpy at wet bulb of entering air, kJ/kg debris. This cycle helps maintain a cleaner system and may actually
h2 = enthalpy at wet bulb of leaving air at actual condition, kJ/kg save water when compared to a standard bleed system. The fre-
h3 = enthalpy of air at wet-bulb temperature leaving a dehumidifier quency of the purge cycle depends on the water quality as well as the
with Fp = 1.0, kJ/kg amount and type of outside contaminants. Sumps should have drain
19.8 2000 ASHRAE Systems and Equipment Handbook (SI)

couplings on the bottom rather than on the side in order to drain the Legionnaire’s Disease
sump completely. Additionally, the sump bottom should slope
toward the drain (approximately 20 mm per metre of sump length) Legionnaire’s disease is contracted by inhaling into the lower
to facilitate complete draining. respiratory system an aerosol (1 to 5 µm in diameter) laden with suf-
Water Treatment. An effective water treatment and biocide ficient Legionella pneumophila bacteria. Evaporative coolers do not
program for cooling towers is not necessarily good practice for provide suitable growth conditions for the bacteria and generally do
evaporative coolers. Evaporative coolers and cooling towers differ not release an aerosol. A good maintenance program eliminates
significantly in that evaporative coolers are directly connected with potential microbial problems and reduces the concern for disease
the supply airstream, whereas cooling towers only indirectly affect transmittal (ASHRAE 1998, Puckorius et al. 1995).
the supply air. The affect a biocide may have on the evaporative The following precautions and maintenance procedures for
media (both direct and indirect evaporative systems) as well as the water systems also improve cooler performance, reduce microbial
potential for offensive and/or harmful residual off-gassing must be growth and musty odors, and prolong the life of the equipment:
considered.
• Run fans after turning off water until the media completely dries.
Pretreatment of a water supply with chemicals intended to hold
dissolved material in suspension is best prescribed by a water treat- • Thoroughly clean and flush the entire cooling water loop regu-
ment specialist. Water treated by a zeolite ion exchange softener larly (minimum monthly). Include disinfection before and after
should not be used because the zeolite exchange of calcium for cleaning.
sodium results in a soft, voluminous scale that may cause dust prob- • Avoid dead end piping, low spots, and other areas in the water dis-
lems downstream. Any chemical agents used should not promote tribution system where water may stagnate during shutdown.
microbial growth or harm the cabinet, media, or heat exchanger • Obtain and maintain the best available mist elimination technol-
materials. This topic is discussed in more detail in Chapter 47 of the ogy, especially when using misters and air washers.
1999 ASHRAE Handbook—Applications. Consider the following
• Do not locate the inlet of an evaporative cooler near the outlet of
factors regarding water treatment
a cooling tower
• Use very pure water from reverse osmosis or deionization pro- • Maintain system bleedoff and/or purge consistent with makeup
cessing with caution in media-based evaporative coolers. This water quality.
water does not wet random media well, and it can deteriorate • Maintain system cleanliness. Deposits from calcium carbonate,
many types of media due to its corrosive nature. The same prob- minerals, and nutrients may contribute to the growth of molds,
lem can occur in a once-through water distribution system if the slime, and other microbes annoying to building occupants.
water is very pure.
• Periodically check for algae, slime, and bacterial growth. If • Develop a maintenance checklist, and follow it on a regular basis.
required, add a biocide. The biocide must be registered for use in • Consult the equipment or media manufacturer for more detailed
evaporative coolers by an appropriate agency, such as the U.S assistance in water system maintenance and treatment.
Environmental Protection Agency (EPA).
Ozone generation systems have been used as an alternative to BIBLIOGRAPHY
standard chemical biocide water treatments. Ozone can be produced Anderson, W.M. 1986. Three-stage evaporative air conditioning versus con-
on-site (eliminating chemical storage) and injected into the water ventional mechanical refrigeration. ASHRAE Transactions 92(1B):358-
circulation system. It is a fast-acting oxidizer that rapidly breaks 70.
down to non-toxic compounds. In low concentrations, ozone is ASHRAE. 1998. Legionellosis: Position statement.
benign to humans and to the materials used in evaporative coolers. Eskra, N. 1980. Indirect/direct evaporative cooling systems. ASHRAE Jour-
Algae can be minimized by reducing the media and sump expo- nal 22(5):21-25.
sure to nutrient and light sources (through the use of hoods, louvers Foster, R.E. and E. Dijkstra. 1996. Evaporative air-conditioning fundamen-
and prefilters), by keeping the bottom of the media out of standing tals: Environmental and economic benefits worldwide. Refrigeration
water in the sump, and by allowing the media to completely dry out Science and Technology Proceedings, ISSN 0151 1637. International
every 24 h. Institute of Refrigeration, Danish Technological Institute, Danish Refrig-
Scale. Units that have heat exchangers with a totally wetted sur- eration Association, Aarhus, Denmark, pp. 101-10.
face and materials that are not harmed by chemicals can be descaled Mathur, G.D. 1991. Indirect evaporative cooling with heat pipe heat ex-
periodically with a commercial descaling agent and then flushed changers. ASME Book No. NE(5):79-85.
out. Mineral scale deposits on a wetted indirect evaporative heat Mathur, G.D. 1990. Indirect evaporative cooling with two-phase thermosi-
exchanger are usually soft and allow wetting through to and evapo- phon coil loop heat exchangers. ASHRAE Transactions 96(1):1241-49.
ration at the surface of the heat exchanger. Excess scale thickness Peterson, J.L. 1993. An effectiveness model for indirect evaporative coolers.
causes a loss in heat transfer and should be removed. ASHRAE Transactions 99(2):392-99.
Air Washers. The air washer spray system requires the most Puckorius, P.R., P.T. Thomas, and R.L. Augspurger. 1995. Why evaporative
attention. Partially clogged nozzles are indicated by a rise in spray coolers have not caused Legionnaires’ disease. ASHRAE Journal
pressure, while a fall in pressure is symptomatic of eroded orifices. 37(1):29-33.
Strainers can minimize this problem. Continuous operation requires Scofield, M. 1986. The heat pipe used for dry evaporative cooling. ASHRAE
either a bypass around pipeline strainers or duplex strainers. Air Transactions 92(1B):371-81.
washer tanks should be drained and dirt deposits removed regularly. Scofield, M. and N.H. DesChamps. 1980. EBTR compliance and comfort
Eliminators and baffles should be periodically inspected and cooling too! ASHRAE Journal 22(6):61-63.
repainted to prevent corrosion damage. Scofield, M. and N.H. DesChamps. 1984. Indirect evaporative cooling using
Freeze Protection. In colder climates, evaporative coolers must plate type heat exchangers. ASHRAE Transactions 90(1):148-53.
be protected from freezing. This is usually done seasonally by sim- Supple, R.G. 1982. Evaporative cooling for comfort. ASHRAE Journal
ply draining the cooler and the water supply line with solenoid 24(8):36.
valves. Often an outside air temperature sensor initiates this action. Watt, J.R. 1986. Evaporative air conditioning handbook. Chapman and
It is important that drain solenoid valves be of the zero differential Hall, London.
design. If a heat exchanger coil is used, the tubes must be horizontal Woolridge, M.J., H.L. Chapman, and D. Pescod. 1976. Indirect evaporative
so that they will drain to the lowest part of their manifold. cooling systems. ASHRAE Transactions 82(1):146-55.

You might also like