Professional Documents
Culture Documents
19.1
19.2 2000 ASHRAE Systems and Equipment Handbook (SI)
density, spray pressure, and other design factors must be considered functional components. Such units are self-housed, pre-wired, pre-
for each application. piped, and ready for hoisting into place.
The simplest design has a single bank of spray nozzles with a The number and arrangement of nozzles vary with different
casing that is usually 1.2 to 2.1 m long. This type of washer is capacities and manufacturers. Adequate values of saturation effec-
applied primarily as an evaporative cooler or humidifier. It is some- tiveness and heat transfer effectiveness are achieved by using higher
times used as an air cleaner when the dust is wettable, although the spray density.
air-cleaning efficiency is relatively low. Two or more spray banks Eliminator blades come in varying shapes, but most are a series
are generally used when a very high degree of saturation is neces- of aerodynamically clean, sinusoidal shapes. Collected moisture
sary and for cooling and dehumidification applications that require flows down grooves or hooks designed into their profiles, then
chilled water. Two-stage washers are used for dehumidification drains into the storage tank. Washers may be built with shallow
when the quantity of chilled water is limited or when the water tem- drain pans and connected to a central storage tank. High-velocity
perature is above that required for the single-stage design. Arrang- washers are rectangular in cross section and, except for the elimina-
ing the two stages for counter-flow of the water permits a small tors, are similar in appearance and construction to conventional
quantity of water with a greater water temperature rise. lower velocity types. Pressure loss is in the range of 120 to 380 Pa.
The lengths of washers vary considerably. Spray banks are These washers are available either as freestanding separate devices
spaced from 0.8 to 1.4 m apart; the first and last banks of sprays are for incorporation into field-built central stations or in complete pre-
located about 0.3 to 0.5 m from the entering or leaving end of the assembled central station packages from the factory.
washer. In addition, air washers may be furnished with heating or
cooling coils in the washer chamber, which may affect the overall HUMIDIFICATION/DEHUMIDIFICATION
length of the washer.
Some water (even very soft water) should always be bled off to Humidification with Air Washers and Rigid Media
prevent mineral buildup and to retard microbial growth. When the Air can be humidified with air washers and rigid media in three
unit is shut down, all water should drain from the pipes. Low spots ways: (1) using recirculated water without prior heating of the air,
and dead ends must be avoided. Because an air washer is a direct (2) preheating the air and humidifying it with recirculated water,
contact heat exchanger, water treatment is critical for proper opera- and (3) preheating recirculated water. Precise humidity control may
tion as well as good hygiene. Algae and bacteria can be controlled be achieved by arranging rigid media in one or more banks in depth,
by a chemical or ozone treatment program and/or regularly sched- height, or width, or by providing a controlled bypass. Each bank is
uled mechanical cleaning. activated independently of the others to achieve the desired humid-
The resistance to airflow through an air washer varies with the ity. In any evaporative humidification application, air should not be
type and number of baffles, eliminators, and wetted surfaces; the permitted to enter the process with a wet-bulb temperature of less
number of spray banks and their direction and air velocity; the size than 4°C, otherwise the water may freeze.
and type of other components, such as cooling and heating coils; Recirculation Without Preheating. Except for the small
and other factors, such as air density. Pressure drop may be as low amount of energy added by the recirculating pump and the small
as 60 Pa or as high as 250 Pa. The manufacturer should be consulted amount of heat leakage into or from the apparatus (including the
regarding the resistance of any particular washer design combina- pump and its connecting piping), the process is adiabatic. The tem-
tion. perature of the water in the collection basin closely approaches the
The casing and the tank may be constructed of various materials. thermodynamic wet-bu1b temperature of the entering air, but it can-
One or more doors are commonly provided for inspection and not be brought to complete saturation. The psychrometric state
access. An air lock must be provided if the unit is to be entered while point of the leaving air is on the constant thermodynamic wet-bulb
it is running. The tank is normally at least 400 mm high with a 350 temperature line with its end state determined by the saturation
mm water level; it may extend beyond the casing on the inlet end to effectiveness of the device. Control over leaving humidity condi-
make the suction strainer more accessible. The tank may be parti- tions may be achieved by controlling the saturation effectiveness of
tioned by a weir (usually in the entering end) to permit recirculation the process by bypassing air around the evaporative process.
of spray water for control purposes in dehumidification work. The Preheating Air. Preheating the air entering an evaporative
excess then returns over the weir to the central water chilling humidifier increases both the dry-and the wet-bulb temperatures
machine. and lowers the relative humidity, but it does not alter the humidity
Eliminators consist of a series of vertical plates that are spaced ratio (mass ratio of water vapor to dry air) of the air. As a result, pre-
about 20 to 50 mm on centers at the exit of the washer. The plates are heating permits more water to be absorbed per unit mass of dry air
formed with a number of bends to deflect the air and obtain passing through the process at the same saturation effectiveness.
impingement on the wetted surfaces. Hooks on the edge of the Control is achieved by varying the amount of air preheating at a
plates improve moisture elimination. Perforated plates may be constant saturation effectiveness. Control precision is a direct func-
installed on the inlet end of the washer to obtain more uniform air tion of saturation effectiveness and a high degree of correlation may
distribution through the spray chamber. Louvers, which prevent the be achieved between leaving air and leaving dew-point tempera-
backlash of spray water, may also be installed for this purpose. tures when high saturation effectiveness devices are used.
Heated Recirculated Water. If heat is added to the water, the
High-Velocity Spray-Type Air Washers process state point of the mixture moves toward the temperature of
High-velocity air washers generally operate at air velocities in the heated water (Figure 7A). Elevating the water temperature
the range of 6 to 9 m/s. Some have been applied as high as 12 m/s, makes it possible to raise the air temperature, both dry bulb and wet
but 6 to 8 m/s is the most accepted range. The reduced cross-sec- bulb, above the dry-bulb temperature of the entering air with the
tional area of high-velocity air washers allows them to be used in leaving air becoming fully saturated. Relative humidity of the leav-
smaller equipment than those operating with lower air velocities. ing air can be controlled by (1) bypassing some of the air around the
High capacities per unit of space available from high-velocity spray media banks and remixing the two airstreams downstream by using
devices permit practical packaging of prefabricated central station dampers or (2) by automatically reducing the number of operating
units in either completely assembled and transportable form or, for media banks through pump staging or by operating valves in the dif-
large capacity units, easily handled modules. Manufacturers supply ferent distribution branches.
units with capacities of up to 70 m3/s shipped in one piece, including The following table shows the saturation or humidifying effec-
spray system, eliminators, pump, fan, dampers, filters, and other tiveness of a spray air washer for various spray arrangements. The
Evaporative Air Cooling Equipment 19.7
degree of saturation depends on the extent of contact between air Air Cleaning
and water. Other conditions being equal, a low-velocity airflow is
Air washers and rigid-media direct evaporative cooling equip-
conducive to higher humidifying effectiveness.
ment can remove particulate and gaseous contaminants with vary-
ing degrees of effectiveness through wet scrubbing (which is
Bank Arrangement Length, m Effectiveness, % discussed in Chapter 25). The particulate removal efficiency of rigid
1 downstream 1.2 50 to 60 media and air washers differ due to the differences in equipment
1 downstream 1.8 60 to 75 construction and principles of operation. Removal also depends
1 upstream 1.8 65 to 80 largely on the size, density, wettability, and/or solubility of the con-
2 downstream 2.4 to 3 80 to 90 taminants to be removed. Large, wettable particles are the easiest to
remove. The primary mechanism of separation is by impingement
2 opposing 2.4 to 3 85 to 95
of particles on a wetted surface, which includes eliminator plates in
2 upstream 2.4 to 3 90 to 98
air washers and the corrugations of wetted rigid media. The spray
process is relatively ineffective in removing most atmospheric
Dehumidification with Air Washers and Rigid Media dusts. Because the force of impact increases with the size of the
solid, the impact (together with the adhesive quality of the wetted
Air washers and rigid-media direct evaporative coolers may also surface) determines the device’s usefulness as a dust remover.
be used to cool and dehumidify air (Figure 7B). The heat and mois- In practice, the air-cleaning results of air washers and rigid-
ture removed from the air causes the water temperature to rise. If the media direct evaporative coolers are typical of comparable
entering water temperature is below the entering air dew point, both
impingement filters. Air washers are of little use in removing soot
the dry- and wet-bulb temperatures of the air is reduced, resulting in particles because of the absence of an adhesive effect from a greasy
cooling and dehumidification. The air is typically saturated as it surface. They are also relatively ineffective in removing smoke
leaves. The vapor pressure difference between the entering air and
because the particles are too small (less than 1 µm) to impact and be
the water cools the air. Moisture is transferred from the air to the retained on the wet surfaces.
water and condensation occurs. The air leaving an evaporative
Despite its air cleaning performance, rigid media should not be
dehumidifier is typically saturated, usually with less than 0.5 K dif-
used as a primary filtering device. When a rigid-media cooler is
ference between leaving dry- and wet-bulb temperatures.
placed in an unfiltered airstream, it can quickly become fouled with
The difference between the leaving air and leaving water temper- airborne dust and fibrous debris. When wet, debris can collect in the
atures depends on the difference between entering dry- and wet- recirculation basin and in the media where they can become nutri-
bulb temperatures and the effectiveness of the process, which may ents for bacteria. Bacteria in the air can propagate in waste materials
be affected by such factors as length and height of the spray cham- and debris and cause microbial slimes. Filtering of the entering air
ber, air velocity, quantity of water flow, and character of the spray is the most effective way to keep debris from accumulating in rigid
pattern. Final water conditions are typically 0.5 to 1 K below the media. When high efficiency filters are placed upstream from the
leaving air temperature, depending on the saturation effectiveness cells, most microbial agents and nutrients can be removed from the
of the device used. airstream. Rigid media should be replaced if the corrugations are
The common design value for the rise in water temperature usu- filled with contaminants when they are dry.
ally falls between 3 and 7 K for refrigerant chilled water and nor-
mal air conditioning applications, although higher rises are MAINTENANCE AND WATER TREATMENT
possible and have been used successfully. A smaller temperature
rise may be considered when water is chilled by mechanical refrig- Regular inspection and maintenance of evaporative coolers, air
eration. If warmer water is used, less mechanical refrigeration is washers, and ancillary equipment ensures proper service and effi-
required; however, a larger quantity of chilled water is needed to do ciency. Manufacturers’ recommendations for maintenance and
the same amount of sensible cooling. An economic analysis may be operation should be followed to help ensure safe and efficient oper-
required to determine the best alternative. For humidifiers receiv- ation. Water lines, water distribution troughs or sumps, pumps, and
ing water from a thermal storage or other low-temperature system, pump filters must be clean and free of dirt, scale, and debris. They
a design with a high temperature rise and minimum water flow may must be constructed so that they can be easily flushed and cleaned.
be desirable. Inadequate water flow causes dry areas on the evaporative media,
which reduces the saturation effectiveness. Motors and bearings
Performance Factors. A performance factor of 1.0 is assigned should be lubricated and fan drives checked periodically
to an evaporative dehumidifier if the device can cool and dehumid-
Water and air filters should be cleaned or replaced as required.
ify the entering air to a wet-bulb temperature equal to that of the
The sump water level must be maintained such that the bottom of
leaving water temperature. This represents a theoretical maximum
the pads does not contact the water in the sump, yet high enough to
value which is thermodynamically impossible to achieve. Perfor-
prevent air from short circuiting below the pads. Bleeding off some
mance is maximized when both water surface area and air –water
water is the most practical means to minimize scale accumulation.
contact is maximized. The actual performance factor Fp of any
The bleed rate should be 5 to 100% of the evaporation rate, depend-
evaporative dehumidifier will be less than one and would be calcu-
ing on water hardness and airborne contaminant level. The water
lated by dividing the actual air enthalpy change by the theoretical
circulation pump should be used to bleed off water because suction
maximum air enthalpy change where:
by a draw-through fan will otherwise prevent the bleed system from
operating effectively. A flush-out cycle that runs fresh water
h1 – h2 through the pad every 24 h when the fan is off may also be used.
F p = ----------------- (3)
h1 – h3 This water should run for 10 min for every metre of media height.
Regular inspections should be made to ensure that the bleed rate
where is adequate and is maintained. Some manufacturers provide a purge
cycle in which the entire sump is purged of water and accumulated
h1 = enthalpy at wet bulb of entering air, kJ/kg debris. This cycle helps maintain a cleaner system and may actually
h2 = enthalpy at wet bulb of leaving air at actual condition, kJ/kg save water when compared to a standard bleed system. The fre-
h3 = enthalpy of air at wet-bulb temperature leaving a dehumidifier quency of the purge cycle depends on the water quality as well as the
with Fp = 1.0, kJ/kg amount and type of outside contaminants. Sumps should have drain
19.8 2000 ASHRAE Systems and Equipment Handbook (SI)
couplings on the bottom rather than on the side in order to drain the Legionnaire’s Disease
sump completely. Additionally, the sump bottom should slope
toward the drain (approximately 20 mm per metre of sump length) Legionnaire’s disease is contracted by inhaling into the lower
to facilitate complete draining. respiratory system an aerosol (1 to 5 µm in diameter) laden with suf-
Water Treatment. An effective water treatment and biocide ficient Legionella pneumophila bacteria. Evaporative coolers do not
program for cooling towers is not necessarily good practice for provide suitable growth conditions for the bacteria and generally do
evaporative coolers. Evaporative coolers and cooling towers differ not release an aerosol. A good maintenance program eliminates
significantly in that evaporative coolers are directly connected with potential microbial problems and reduces the concern for disease
the supply airstream, whereas cooling towers only indirectly affect transmittal (ASHRAE 1998, Puckorius et al. 1995).
the supply air. The affect a biocide may have on the evaporative The following precautions and maintenance procedures for
media (both direct and indirect evaporative systems) as well as the water systems also improve cooler performance, reduce microbial
potential for offensive and/or harmful residual off-gassing must be growth and musty odors, and prolong the life of the equipment:
considered.
• Run fans after turning off water until the media completely dries.
Pretreatment of a water supply with chemicals intended to hold
dissolved material in suspension is best prescribed by a water treat- • Thoroughly clean and flush the entire cooling water loop regu-
ment specialist. Water treated by a zeolite ion exchange softener larly (minimum monthly). Include disinfection before and after
should not be used because the zeolite exchange of calcium for cleaning.
sodium results in a soft, voluminous scale that may cause dust prob- • Avoid dead end piping, low spots, and other areas in the water dis-
lems downstream. Any chemical agents used should not promote tribution system where water may stagnate during shutdown.
microbial growth or harm the cabinet, media, or heat exchanger • Obtain and maintain the best available mist elimination technol-
materials. This topic is discussed in more detail in Chapter 47 of the ogy, especially when using misters and air washers.
1999 ASHRAE Handbook—Applications. Consider the following
• Do not locate the inlet of an evaporative cooler near the outlet of
factors regarding water treatment
a cooling tower
• Use very pure water from reverse osmosis or deionization pro- • Maintain system bleedoff and/or purge consistent with makeup
cessing with caution in media-based evaporative coolers. This water quality.
water does not wet random media well, and it can deteriorate • Maintain system cleanliness. Deposits from calcium carbonate,
many types of media due to its corrosive nature. The same prob- minerals, and nutrients may contribute to the growth of molds,
lem can occur in a once-through water distribution system if the slime, and other microbes annoying to building occupants.
water is very pure.
• Periodically check for algae, slime, and bacterial growth. If • Develop a maintenance checklist, and follow it on a regular basis.
required, add a biocide. The biocide must be registered for use in • Consult the equipment or media manufacturer for more detailed
evaporative coolers by an appropriate agency, such as the U.S assistance in water system maintenance and treatment.
Environmental Protection Agency (EPA).
Ozone generation systems have been used as an alternative to BIBLIOGRAPHY
standard chemical biocide water treatments. Ozone can be produced Anderson, W.M. 1986. Three-stage evaporative air conditioning versus con-
on-site (eliminating chemical storage) and injected into the water ventional mechanical refrigeration. ASHRAE Transactions 92(1B):358-
circulation system. It is a fast-acting oxidizer that rapidly breaks 70.
down to non-toxic compounds. In low concentrations, ozone is ASHRAE. 1998. Legionellosis: Position statement.
benign to humans and to the materials used in evaporative coolers. Eskra, N. 1980. Indirect/direct evaporative cooling systems. ASHRAE Jour-
Algae can be minimized by reducing the media and sump expo- nal 22(5):21-25.
sure to nutrient and light sources (through the use of hoods, louvers Foster, R.E. and E. Dijkstra. 1996. Evaporative air-conditioning fundamen-
and prefilters), by keeping the bottom of the media out of standing tals: Environmental and economic benefits worldwide. Refrigeration
water in the sump, and by allowing the media to completely dry out Science and Technology Proceedings, ISSN 0151 1637. International
every 24 h. Institute of Refrigeration, Danish Technological Institute, Danish Refrig-
Scale. Units that have heat exchangers with a totally wetted sur- eration Association, Aarhus, Denmark, pp. 101-10.
face and materials that are not harmed by chemicals can be descaled Mathur, G.D. 1991. Indirect evaporative cooling with heat pipe heat ex-
periodically with a commercial descaling agent and then flushed changers. ASME Book No. NE(5):79-85.
out. Mineral scale deposits on a wetted indirect evaporative heat Mathur, G.D. 1990. Indirect evaporative cooling with two-phase thermosi-
exchanger are usually soft and allow wetting through to and evapo- phon coil loop heat exchangers. ASHRAE Transactions 96(1):1241-49.
ration at the surface of the heat exchanger. Excess scale thickness Peterson, J.L. 1993. An effectiveness model for indirect evaporative coolers.
causes a loss in heat transfer and should be removed. ASHRAE Transactions 99(2):392-99.
Air Washers. The air washer spray system requires the most Puckorius, P.R., P.T. Thomas, and R.L. Augspurger. 1995. Why evaporative
attention. Partially clogged nozzles are indicated by a rise in spray coolers have not caused Legionnaires’ disease. ASHRAE Journal
pressure, while a fall in pressure is symptomatic of eroded orifices. 37(1):29-33.
Strainers can minimize this problem. Continuous operation requires Scofield, M. 1986. The heat pipe used for dry evaporative cooling. ASHRAE
either a bypass around pipeline strainers or duplex strainers. Air Transactions 92(1B):371-81.
washer tanks should be drained and dirt deposits removed regularly. Scofield, M. and N.H. DesChamps. 1980. EBTR compliance and comfort
Eliminators and baffles should be periodically inspected and cooling too! ASHRAE Journal 22(6):61-63.
repainted to prevent corrosion damage. Scofield, M. and N.H. DesChamps. 1984. Indirect evaporative cooling using
Freeze Protection. In colder climates, evaporative coolers must plate type heat exchangers. ASHRAE Transactions 90(1):148-53.
be protected from freezing. This is usually done seasonally by sim- Supple, R.G. 1982. Evaporative cooling for comfort. ASHRAE Journal
ply draining the cooler and the water supply line with solenoid 24(8):36.
valves. Often an outside air temperature sensor initiates this action. Watt, J.R. 1986. Evaporative air conditioning handbook. Chapman and
It is important that drain solenoid valves be of the zero differential Hall, London.
design. If a heat exchanger coil is used, the tubes must be horizontal Woolridge, M.J., H.L. Chapman, and D. Pescod. 1976. Indirect evaporative
so that they will drain to the lowest part of their manifold. cooling systems. ASHRAE Transactions 82(1):146-55.