ME 425
Psychrometrics & Coil Load
Coils
Coils are the main devices for transferring
energy to/from the airstream in an air-
handling system.
Heat Transfer Media
Hydronic Fluid (Water)
Steam
Direct Expansion
Bypass Factor
1
ME 425 - Psychrometrics & Coil Load Calculation 2
2
ME 425 - Psychrometrics & Coil Load Calculation 3
SHR
3
ME 425 - Psychrometrics & Coil Load Calculation 4
Temp
tlwb
ADP
tlw Metal Surface Temp.
Chilled water
tlew
Surface Area
8-Row Coil
80 fpf /2 fps/44 EWT / WTR = 10
Coil Bypass
4
ME 425 - Psychrometrics & Coil Load Calculation 5
Coil Air
Leaving
Air
Bypass Factor
Some of the air flowing through the coil
impinges on the water tubes or the fins and is
cooled to the ADP. Other air passes through
unchanged.
Coil
Entering
Air
Fin
5
ME 425 - Psychrometrics & Coil Load Calculation 6
Coil Selection
Start With Space Conditions
Find the intersection of the
SHR with desired room
temperature and supply air
temperature
Room
Supply
Air
Room Air
SHR
Temperature
6
ME 425 - Psychrometrics & Coil Load Calculation 7
Coil Selection
Determine Outside Air Requirements Using
ASHRAE Standard 62
Outside Air
Coil
Coil Entering
Leaving Air
Apparatus
Room Air
7
ME 425 - Psychrometrics & Coil Load Calculation 8
Coil Entering
Leaving Air
Apparatus
Room Air
SHR
∆h
Leaving
Air Enthalpy
8
ME 425 - Psychrometrics & Coil Load Calculation 9
9
ME 425 - Psychrometrics & Coil Load Calculation 10
Room Air
SHR=0.70 75°F / 50% RH
55°F
53°F
Mixed Air
∆tfan
10
ME 425 - Psychrometrics & Coil Load Calculation 11
Outside Air
hLA = 20..5 Btu/lb 85°F / 70°F WB
Mixed Air
Outside Air
hLA = 20..5 Btu/lb 85°F / 70°F WB
Mixed Air
11
ME 425 - Psychrometrics & Coil Load Calculation 12
Btu/lbw
= 11.7 GPM
12
ME 425 - Psychrometrics & Coil Load Calculation 13
Unitary Equipment
Homework
Read 05F6.14-6.21
What is the coil load for the following?
Indoor 76 oF/45% RH - Outdoor 82/66oF
Load (Btu/h) 100,000 Sensible - 40,000 Latent
Supply air 55oF through draw-through fan
Fan Total Pressure = 3 in w.c.
Fan Efficiency = 60%
Outside air = 50% of total supply
Be able to work this problem not necessary to
turn in
13