Fronius STATE codes beginning with 1xx

Fronius STATE codes beginning with 1 usually only occur temporarily and are caused by the
power from the electrical mains (grid) being outside the inverters operating parameters. The
Fronius inverter reacts by disconnecting from the grid and attempts to switch on again after
the specified mains monitoring period, as long as no further errors occur during this period.
The STATE code is displayed whilst the grid is being checked.

State Code Description Possible causes Remedy (sequence)

STATE 101 Grid voltage beyond 1. Mains voltage error 1. Check grid voltage, check
permitted limits 2. Incorrect values in the circuit AC breakers are ON
service menu 2. Change values in the
3. Internal fault service menu
3. If problem persists contact
us

STATE 104 Mains frequency beyond 1. Mains frequency error 1. Check mains frequency,
permitted limits 2. Incorrect values in the check AC circuit breakers
service menu are ON
3. Internal fault 2. Change values in the
service menu
3. If problem persists contact
us

STATE 107 Synchronisation with the 1. Mains not connected 1. Connect mains power,
public mains supply not 2. Incorrect values in the check circuit breakers are
possible service menu ON
3. Internal fault 2. Check values in the service
menu
3. If problem persists contact
us

STATE 108 Islanding detected 1. Islanding detected 1. Automatic correction


2. Severe disturbances in 2. Automatic correction
public mains 3. If problem persists contact
3. Internal fault us
Fronius STATE codes beginning with 2xx

Fronius STATE codes beginning with 2 are messages from the grid monitoring device
(ENS) integrated within the inverter and refer to the parameters of the public mains.
Some error checks cross over with the STATE codes beginning with 1, however those
in service class 2 are of a higher importance and are displayed for that reason.

State Code Description Possible causes Remedy (sequence)

STATE 201 Grid voltage is higher 1. Grid voltage error on the 1. Check grid voltage
than the specified limit public mains 2. If problem persists contact
2. Internal fault us

STATE 202 Grid voltage is lower


than the specified limit

STATE 203 Grid frequency is higher 1. Grid frequency error on 1. Check grid frequency
than the specified limit the public mains 2. If problem persists contact
2. Internal fault us

STATE 204 Grid frequency is lower


than the specified limit

STATE 205 Change of public mains 1. Serious disturbances on 1. Reinforce mains cables
impedance the public mains 2. Connect Fronius IG
2. Internal fault inverter to another phase
3. If problem persists contact
us

STATE 206 Absolute value of the 1. Mains impedance too high


impedance is too high 2. Internal fault

STATE 207 Mains relay does not Internal fault If problem persists contact
open in spite of switch us
off signal

STATE 208 Mains relay does not


close in spite of switch
off signal
Fronius STATE codes beginning with 3xx

Fronius STATE codes beginning with 3 are error states that can occur during grid feed
in operation, however they do not indicate damaged electronics and do not lead to a
remaining interruption of the feed in operation. After switching off and passing the
grid monitoring period, the Fronius IG inverter will start feed in operation again. In
case of a temperature excess additional cooling down phase is maintained.

State Code Description Possible causes Remedy (sequence)

STATE 301 Safety circuit detects a 1. Voltage drop on the 1. Automatic correction
current peak on the public mains 2. If problem persists contact
mains supply 2. Internal fault us

STATE 302 Safety circuit detects a


current peak on the PV
generator side

STATE 303 Heat sink temperature 1. Ventilation slot 1. Free ventilation slot
on the DC-AC board is congested 2. Change location of
too high 2. Very high ambient inverter
temperature 3. Increase distance between
STATE 304 Heat sink temperature
3. Distance between inverters
on the DC-DC board is
inverters too small 4. If problem persists contact
too high
4. Internal fault your Fronius Service Partner

STATE 305 Feed-in process not Internal fault If problem persists contact
possible, even though us
public mains parameter
within the limits

STATE 306 Power Low Intermediate circuit voltage 1. Check panels


has dropped below 2. Internal fault
permissible threshold value
for feed in

STATE 307 DC Low 1. DC-input voltage is too


low for feed in
2. Internal fault

STATE 308 Intermediate circuit 1. Public mains disturbances 1. Reinforce mains cable
voltage out of the 2. Internal fault 2. If problem persists contact
maximum limit your Fronius Service Partner
Fronius STATE codes beginning with 4xx

Fronius STATE codes beginning with 4 are error states that require the intervention of
a technician. They are either temporary or lasting and are triggered by faulty hardware
or a software problem. Try switching off the Fronius inverter following the system
shutdown procedure, leave off for a few minutes then attempt to restart. If the fault
continues please contact us for further assistance.

State Code Description Possible causes Remedy (sequence)

STATE 401 Communication error Internal fault If problem persists contact


between IG control and us
the DC-DC board

STATE 402 Write access to the


internal Fronius IG
memory failed

STATE 403 The area in the internal


memory for the country
setting is incomplete

STATE 404 Connection between the 1. Public mains not 1. Check the public mains
control unit and the ENS connected 2.If problem persists contact
is faulty 2. Internal fault us

STATE 405 An old or incorrect Internal fault If problem persists contact


version of the ENS us
microprocessors has
been recognised

STATE 406 Temperature sensor on


the DC-AC board faulty
or not connected

STATE 407 Temperature sensor on


the DC-DC board faulty
or not connected

STATE 408 Unsymmetry on the 1. Public mains disturbances 1. Error is remedied


public mains detected 2. Internal fault automatically
2. If problem persists contact
your Fronius Service Partner
Fronius STATE codes beginning with 4xx (Cont.)

State Code Description Possible causes Remedy (sequence)

STATE 409 Supply of the DC-AC Internal fault If problem persists contact
board not available us

STATE 410 Service plug on the DC-


AC board is not set
correctly

STATE 412 Value for fixed voltage is


set higher than the open
circuit voltage of the PV
generator

STATE 413 Open circuit voltage too


high in the moment of
transformer switching

STATE 414 Memory array for 1. One-off – memory error 1. Error is remedied
Fronius IG type in EE- 2. Internal fault automatically
PROM faulty 2. If problem persists contact
us

STATE 415 No END-enabling signal Internal fault If problem persists contact


despite release by IG- us
control

STATE 416 Communication error 1. One-off – communication 1. Error is remedied


between IG-Control and error automatically
power stack 2. Internal fault 2. If problem persists contact
us
Fronius STATE codes beginning with 4xx (Cont.)

STATE 417 Hardware ID-collision Internal fault If problem persists contact


us

STATE 419 Two or more power


stacks with identical
Unique ID

STATE 420 Incomplete number of


power stacks detected
after reaching online
threshold according to
device type

STATE 421 Hardware ID sequence


error

STATE 425 Receive time-out for 1. One-off error 1. Automatic correction


data exchange with one 2. Internal fault 2.If problem persists contact
or more power stacks us
exceeded

STATE 431 All power stacks are in Internal fault If problem persists contact
boot mode us

STATE 432 Consistent error in 1. One-off error 1. Automatic correction


power stack 2. Internal fault 2.If problem persists contact
management us

STATE 433 Allocation error of


dynamic addresses

STATE 434 Ground fault detected

STATE 435 Wrong configuration for


EE-Prom

STATE 436 Error transmission faulty

STATE 437 Power stack work


around is active

STATE 438 Error during state code 1. One-off error 1. Automatic correction
transmission 2. Permanent error 2.If problem persists contact
us
Fronius STATE codes beginning with 4xx (Cont.)

STATE 441 Power rack fan faulty Power rack fan faulty If problem persists contact
us

STATE 442 Master for one phase 1. Temporary 1. Automatic correction


could not be assigned communication error 2.If problem persists contact
2. Internal fault us

STATE 443 DC-DC energy transfer 1. Error during switching on 1. Automatic correction
failure a power stack 2.If problem persists contact
2. Internal fault us

STATE 444 AC monitoring self test During the self test another Quit the self test by pressing
interrupted error occured ESC and remedy the failure
according to the error code
list

Fronius STATE codes beginning with 5xx

Fronius STATE codes beginning with 5 generally do not stop the feed in operation of
the Fronius IG inverter. The STATE codes will be displayed until the message is
acknowledged by pushing a button on the display (the inverter will work in feed in
operation during this time).

STATE 501 Heat sink temperature 1. Ventilation slot 1. Free ventilation slot
too high, although congested 2.If problem persists contact
Fronius IG is on low 2. Internal fault us
output

STATE 502 An isolation fault Isolation fault at the solar Check cables and solar
between DC+ or DC- to generator generator
earth has been detected

STATE 504 An error occured while Identical Fronius IG address Check address of the
scanning LocalNet used twice inverters and other
addresses components
Fronius STATE codes beginning with 5xx (Cont.)

STATE 505 The area in the internal 1. One-off error 1. Automatic correction
memory for the “Setup” 2. Internal fault 2.If problem persists contact
values is incomplete us

STATE 506 The area in the internal


memory for the “Total”
values is incomplete

STATE 507 The area in the internal


memory for the
“Day/Year” values is
incomplete

STATE 508 The area in the internal


memory for the “WR
number” is damaged

STATE 509 No feed in operation for 1. Snow covered or very 1. Clean solar panels or
24 hours dirty solar panels remove snow
2. Insufficient power from 2. If problem persists contact
the solar panels for feed in us
operation
3.Internal error

STATE 510 Errors detected by 1. One-off error 1. Automatic correction


LocalNet self diagnostic 2. Internal fault 2.If problem persists contact
system us

STATE 511 Errors detected by


LocalNet Sensor Card
self diagnostic system

STATE 512 According to the device


type too many power
stacks have been
detected

STATE 513 Power stacks in boot


mode

STATE 514 Incomplete number of


power stacks detected
after reaching online
threshold – Device type
Fronius STATE codes beginning with 5xx (Cont.)

STATE 515 One or more power Internal fault If problem persists contact
stacks notified STATE us
406/ 407/ 409/ 410

STATE 516 One power stack


exceeds the permitted
limit of error messages
per day (>50x)

STATE 517 Permanent POWER


LOW or DC LOW error