Professional Documents
Culture Documents
Abstract—This paper presents a three-phase Active Power This paper presents an APC used to improve the power
Conditioner to improve power quality in microgrids based on quality in a microgrid. The attention will be mainly focused on
renewable energy. A microgrid is a weak electrical grid which the innovative control strategy, which allows injecting energy
can be easily subject to disturbances. The Active Power in the microgrid, compensating the current harmonics,
Conditioner (APC) presented in this paper acts as an interface correcting the power factor and balancing the supply voltage at
between renewable energy sources and the AC bus of a microgrid the PCC. The validity of the control strategy has been proved
and uses an improved control strategy, which makes possible to through many simulation tests using SimPowerSystems from
inject energy in the microgrid, compensate the current harmonics MATLAB.
and correct the power factor. Moreover, the proposed control
strategy allows the line current at the point of common coupling
(PCC) to be balanced and sinusoidal even when the load is Main Grid
unbalanced. Consequently, the voltage at the PPC becomes
balanced. Simulation results show the validity of the innovative Electrical Loads
control strategy.
I. INTRODUCTION DC DC DC
DC
Technological advances in power electronics have created DC AC
va ia iLa va
vb ib iLb vb
Microgrid ic iLc vc
vc
Non-linear
vN iN iLN vN Loads
ifN ifc ifb ifa
L
IDC
VDC
Renewable
Energy vN vc vb va
Sources
i fa + i fb + i fc = i fN (1) ~
i fx = i1fx + i fx (4)
where: 1
ifx - the fundamental conditioner current component;
ifa, ifb, ifc are phase APC currents and ifN is the APC neutral ~
current. i fx - the deforming component of the current.
Therefore, the total DC voltage will oscillate not only at the As shown in Fig. 2 the current drawn from the grid has to
switching frequency but also at the corresponding frequency of be sinusoidal and moreover, in phase with the voltage at PCC.
the neutral current. As shown in [2], if the current control is Consequently, the control strategy for the APC has to be
made by hysteresis, the above mentioned drawback can be designed in order to ensure a sinusoidal wave for the grid
limited with a dynamic offset level added to both limits of the current:
hysteresis band. ~
For the investigated topology presented in Fig. 2, the ilx1 + ilxk + ilxq + i1fx + i fx = ix (5)
current at (PCC) is:
The APC switches generate undesirable current harmonics
ix = ilx + i fx (2) around the switching frequency and its multiples. Considering
the switching frequency of the APC sufficiently high, these
where: undesirable current harmonics can be filtered with the LR
passive filter.
ix, ilx, ifx are the microgrid side current, the load current, and
the APC current respectively. The x index points the a, b and c
current phases. III. CONTROL OF THE APC
The instantaneous load current is: A. Control Strategy
1
ilx = i + ilxk + ilxq (3) There are many ways to design a control algorithm for an
lx
APC [7] [8]. Generally, the controller design is made
where: considering that the grid voltage at the PCC is balanced. In a
- i1lx the fundamental active current component; microgrid, the supply voltage itself can be distorted and/or
unbalanced. Consequently, the controller of an APC used to
- ilxk the addition of current harmonics; improve the power quality in the microgrid has to be designed
- ilxq the reactive current component. according to the weakness of this kind of grid.
The three-phase APC current is given by:
729
ia va ila
ib vb ilb
Microgrid ic vc ilc
iN vN iN
Non-linear loads
sin(wt-4π/3) ifc ifb ifa iN
PLL vc
sin(wt-2π/3) vb
va
sin(wt)
ia
ia* -
+ IGBT Active
ib Power Filter
*
ib -
+
ic* i-a
+
PI
-
+ VDC
Renewable
V*DC Energy
Control strategy
Figure 3. APC control strategy
The proposed control algorithm is a compensation method Compared with linear controllers, the non-linear ones based
that makes the APC compensate the current of a non-linear on hysteresis strategies allow faster dynamic response and
load by forcing the microgrid side current to become sinusoidal better robustness with respect to the variation of the non-linear
and balanced (Fig. 3). The controller requires the three-phase load. A drawback of the hysteresis strategies is the switching
grid current (ia, ib, ic), the three-phase voltage at the PCC (va, frequency which is not constant and can generate a large side
vb, vc) and the DC-link voltage (VDC). As shown in Fig. 3, the harmonics band around the switching frequency.
sinusoidal waveform and the phase of the grid current reference
(ia*, ib*, ic*) comes from the line voltage thanks to a PLL. The To avoid this drawback, the switching frequency can be
magnitude of the same current is obtained by passing the error fixed using different solutions like variable hysteresis
signal between the DC-link voltage (VDC) and a reference bandwidth [9] or modulated hysteresis [10]. But this is not the
voltage (VDC*) through a PI controller. object of this paper.
Using this magnitude and phase displacement of 120° and IV. SIMULATION RESULTS
240° respectively, the reference three-phase grid currents ia*,
ib* and ic* can be expressed as: To validate the proposed control algorithm, many
simulations have been run in various operating conditions
ia* = ( PI ) ⋅ sin (ω t ) (6) using Matlab, SimPowerSystems toolbox. The investigated
active power conditioner has been simulated with six IGBTs
⎛ 2π ⎞
ib* = ( PI ) ⋅ sin ⎜ ω t − ⎟ (7) controlled by the system illustrated in Fig.3. All the parameters
⎝ 3 ⎠ are shown in Table 1. During all the simulations, the power
⎛ 4π ⎞ coming from the renewable energy sources is considered
ic* = ( PI ) ⋅ sin ⎜ ω t − ⎟ (8) unvarying.
⎝ 3 ⎠
Table 1: Parameters of the APC
B. Switching control Parameters Value
As shown in Fig. 3, the hysteresis control has been used to AC voltage vabc [V] 230
keep the controlled current inside a defined band around the
references. The status of the switches is determined according DC-link voltage (VDC) [V] 750
to the error. When the current is increasing and the error Inductor (L) [mH] 3
exceeds a certain positive value, the status of the switches Capacitor (C) [μF] 20000
changes and the current begins to decrease until the error Hysteresis Band [A] 0.5
reaches a certain negative value. Then, the switches status
changes again.
730
The simulation results are grouped and presented according 100%
Fundamental (50Hz), THD of Ila = 29.95%
Mag (% of Fundamental)
to the following power quality indicators: THD (Total 20
A. Harmonics compensation
0
During this case study, the APC is investigated using a 0 2
100%
4 6 8 10 12 14 16 18 20
Mag (% of Fundamental)
1
with a 0.1 mH inductor at the DC side. The power delivered by
the renewable sources is 3 kW and the load requires 5 kW.
0.5
Mag (% of Fundamental)
rectifier is not sinusoidal and has a THD of 30%. The 0.01
0
0 2 4 6 8 10 12 14 16 18 20
Harmonic order
10
5
i
la
ilb i
lc Figure 5: THD of the microgrid side current and voltage
il,abcn [A]
0
i
ln B. Power factor correction
-5
The second case study shows the ability of the APC to
-10 compensate the power factor.
0.45 0.455 0.46 0.465 0.47 0.475 0.48 0.485 0.49 0.495 0.5
The power factor can be controlled with capacitor banks,
10
but in distorted conditions the results are poor and also the
5 i i i
capacitor life is shorter.
fa
if,abcn [A]
fb fc
0 For this case study, the load is composed by a three-phase
ifn
-5 ia
20 il,a 500
-10
0.45 0.455 0.46 0.465 0.47 0.475 0.48 0.485 0.49 0.495 0.5 va
10
4
il,a, ia [A]
va [V]
i 0 0
ia ib c
2
[A]
0 -10
abcn
in
i
-2 -20 -500
0.45 0.455 0.46 0.465 0.47 0.475 0.48 0.485 0.49 0.495 0.5
-4
0.45 0.455 0.46 0.465 0.47 0.475 0.48 0.485 0.49 0.495 0.5 ib
20 il,b 500
400 vb
va vb v 10
200 c
vabc [V]
il,b, ib [A]
vb [V]
0 0 0
-200
-10
-400
0.45 0.455 0.46 0.465 0.47 0.475 0.48 0.485 0.49 0.495 0.5
Time [s] -20 -500
0.45 0.455 0.46 0.465 0.47 0.475 0.48 0.485 0.49 0.495 0.5
Figure 4. Currents and voltage in the PCC during harmonics compensation test
ic
The proposed control strategy allows the current iabcn on the 20 il,c 500
(Fig. 5). In the same figure 5, it can be seen the THD of the 10
load current (30%) and the voltage THD at the PCC which is
il,c , ic [A]
vc [V]
0 0
1.3%. The voltage THD is lower then the THD imposed by the
EN 50160 Standard (THD<8%) [10]. -10
-20 -500
0.45 0.455 0.46 0.465 0.47 0.475 0.48 0.485 0.49 0.495 0.5
Time [s]
Figure 6. Currents and voltage in the PCC during the power factor correction
test
731
inductor in series with a three-phase resistor and requires about of the load is charged with 1050 W, the phase b with 1311 W
3kW active power and 4 kVAR reactive power. The power and the phase c with 1749 W. The Fig. 7 shows the current and
generated by the renewable sources is about 6 kW. the voltage at the PCC. As shown in the previous section, the
investigated APC is controlled such that the microgrid current
Fig. 6 illustrates the load current, the microgrid side current required by the load (iabcn) is sinusoidal and balanced.
and the supply voltage respectively at the PCC for each phase. Consequently, the voltage in this point is also balanced.
As shown in the figure, the measured power factor between the
load current and the supply voltage is 0.58. Thanks to the To quantify the level of the voltage unbalance, the
proposed control strategy, the APC is able to impose a unity percentage of negative sequence unbalance is expressed in
power factor between the microgrid side currents and the accordance with the definition of the ‘‘degree of unbalance in
supply voltage. The phase of the microgrid side currents is three-phase systems’’ [11]. As shown in Fig. 6, using the APC
inverted relatively to the phase of supply voltages at the PCC equipped with the proposed controller, the degree of the
because the power injected by the APC exceeds the power negative sequence unbalance is lower then 0.8%. It must be
required by the load. Consequently, the surplus renewable noticed that international standards admit unbalances lower
energy is injected into the microgrid. than 2% [11].
il,n
unity power-factor operation.
•
-10
The control of the three-phase line current enables the
0.45 0.455 0.46 0.465 0.47 0.475 0.48 0.485 0.49 0.495 0.5 three-phase voltage balance at the PCC, allowing
excellent regulation characteristics.
10
if,a if,b
if,c
if,n
Different case studies have been investigated with the APC
5
simulated in the Matlab SymPowerSystem and the simulations
if,abcn [A]
4
REFERENCES
[1] H. Ibrahim, A. Ilinca and J. Perron, “Energy Storage Systems –
2 ib
ia ic Characteristics and Comparisons,” Elsevier Renewable & Sustainable
iabcn [A]
0
[4] B. Singh, K. Al-Haddad, A. Chandra “A Review of Active Filters for
-200 Power Quality Improvement” IEEE Transactions on Power Electronics,
vol. 46, pp. 960-971, October 1999.
-400
0.45 0.455 0.46 0.465 0.47 0.475 0.48 0.485 0.49 0.495 0.5 [5] J. Chen, F. Liu , S. Mei, “Nonlinear disturbance attenuation control for
Time [s]
four-leg active power filter based on voltage source inverter,” Journal of
Control Theory and Applications vol. 3 pp. 261–266, August 2006.
Figure 7. Current and voltage at the PCC during unbalance load test [6] M. Ucara and E. Ozdemir “Control of a 3-phase 4-leg active power filter
under non-ideal mains voltage condition,” Electric Power Systems
Research, vol. 78, pp. 58-73, January 2008.
732
[7] A. Zhikang, S. Wenji Z. Ruixiang and F. Chunming Tu “Development Transactions on Industrial Electronics vol. 45, pp. 691–703, October
of Hybrid Active Power Filter Based on the Adaptive Fuzzy Dividing 1998.
Frequency-Control Method,” IEEE Transactions on Power Delivery, vol. [10] M. Nejad, S. Pierfederici, J.P. Martin, F. Meibody-Tabar, “Study of an
24, pp. 424 – 432, January 2009. hybrid current controller suitable for DC–DC or DC–AC applications,”
[8] B.S. Chen and G. Joos, “Direct Power Control of Active Filters With IEEE Transactions on Power Electronics, vol. 22, pp. 2176–2186.
Averaged Switching Frequency Regulation,” IEEE Transactions on November 2007.
Power Electronics, vol. 23, pp. 2729 - 2737, November 2008. [11] Copper Development Association, “Voltage Disturbances. Standard EN
[9] M.P. Kazmierkowski, L. Malesani, “Current control techniques for 50160 Voltage Characteristics in Public Distribution Systems,” 2004.
three-phase voltage source PWM converters: a survey,” IEEE
733