You are on page 1of 12

PW Series Relay Testing System

Substation
Test Object-Device Setting

Station/Bay Information:
Station Name: Central Hidroelectria San Jose II
Bay Name: #1 Generator Protection B

Test Equipment Information:


Type: PW336i Imax: 30.00A
Serial Number: BO146160902 Test Start: 03-01-2019 20:38:22
CommunicationPort: ETHERNET.COM Test End: 03-01-2019 20:38:26
Vmax: 150.00V

Test Object - U,I

Test Module Parameter


Name Version
Quick Check (4V3I) 2.3.0-1909-1552

1. Differential Protect of Generator(87G)

1.1 87G_Inst

Test Result

1.U,I
Va: 0.000V Vc-Freq: 50.000Hz Ib-PH: 0.00°
Va-PH: 0.00° Vz: 0.000V Ib-Freq: 50.000Hz
Va-Freq: 50.000Hz Vz-PH: 0.00° Ic: 0.000A
Vb: 0.000V Vz-Freq: 50.000Hz Ic-PH: 120.00°
Vb-PH: -120.00° Ia: 3.408A Ic-Freq: 50.000Hz
Vb-Freq: 50.000Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 0.000V Ia-Freq: 50.000Hz
Vc-PH: 120.00° Ib: 0.000A

Trip time
0.0350S

Page 1
PW Series Relay Testing System

Test Result Assessing:


Setting:87G.I_Inst=4Ie,Time delay =0s
Test Value: I=3.408A(4Ie)
Test result: Operating time =0.035s
∆t=0.035s

1.2 87G_Biased

Test Result

1.U,I
Va: 0.000V Vc-Freq: 50.000Hz Ib-PH: 0.00°
Va-PH: 0.00° Vz: 0.000V Ib-Freq: 50.000Hz
Va-Freq: 50.000Hz Vz-PH: 0.00° Ic: 0.000A
Vb: 0.000V Vz-Freq: 50.000Hz Ic-PH: 120.00°
Vb-PH: -120.00° Ia: 0.980A Ic-Freq: 50.000Hz
Vb-Freq: 50.000Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 0.000V Ia-Freq: 50.000Hz
Vc-PH: 120.00° Ib: 0.700A

Trip time
0.0370S

Test Result Assessing:


Setting:87G.I_Biased =0.2Ie,Time delay =0s
Test Value: Id=0.33Ie,Ir=0.99Ie
Test result: Operating time =0.0370s
∆t=0.037s

2. Stator Overload Protection (49S)

2.1 49S_IDMT_TRIP

Test Result

1.U,I
Va: 0.000V Vb-PH: -120.00° Vc-Freq: 50.000Hz
Va-PH: 0.00° Vb-Freq: 50.000Hz Vz: 0.000V
Va-Freq: 50.000Hz Vc: 0.000V Vz-PH: 0.00°
Vb: 0.000V Vc-PH: 120.00° Vz-Freq: 50.000Hz

Page 2
PW Series Relay Testing System
Ia: 2.100A Ib-PH: 0.00° Ic-Freq: 50.000Hz
Ia-PH: 0.00° Ib-Freq: 50.000Hz Time After Tigger: 0.000s
Ia-Freq: 50.000Hz Ic: 0.000A
Ib: 2.100A Ic-PH: 120.00°

Trip time
14.823S

Test Result Assessing:


Setting:49S.IDMT.I_Set=0.99A
Test Value:I=2.1A
Calculated time=14.812s
Test result: Operating time =14.823s
∆t=0.011s

2.2 49S_DT_Alarm

Test Result

1.U,I
Va: 0.000V Vc-Freq: 50.000Hz Ib-PH: 0.00°
Va-PH: 0.00° Vz: 0.000V Ib-Freq: 50.000Hz
Va-Freq: 50.000Hz Vz-PH: 0.00° Ic: 0.000A
Vb: 0.000V Vz-Freq: 50.000Hz Ic-PH: 120.00°
Vb-PH: -120.00° Ia: 0.940A Ic-Freq: 50.000Hz
Vb-Freq: 50.000Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 0.000V Ia-Freq: 50.000Hz
Vc-PH: 120.00° Ib: 0.940A

Trip time
6.0870S

Test Result Assessing:


Setting:49S.DT.I_Set=0.94A Time delay =6s
Test Value:I=0.94A
Test result: Operating time =6.087s
∆t=0.087s

Page 3
PW Series Relay Testing System

3. Negative-Sequence Overload Protection (46G)

3.1 46G_IDMT_Trip

Test Result

1.U,I
Va: 0.000V Vc-Freq: 50.000Hz Ib-PH: 0.00°
Va-PH: 0.00° Vz: 0.000V Ib-Freq: 50.000Hz
Va-Freq: 50.000Hz Vz-PH: 0.00° Ic: 0.000A
Vb: 0.000V Vz-Freq: 50.000Hz Ic-PH: 120.00°
Vb-PH: -120.00° Ia: 4.500A Ic-Freq: 50.000Hz
Vb-Freq: 50.000Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 0.000V Ia-Freq: 50.000Hz
Vc-PH: 120.00° Ib: 4.500A

Trip time
11.6260S

Test Result Assessing:


Setting:46G.IDMT.I_Set=0.12A
Test Value:I=4.5A(I2=1.5A)
Calculated time:11.612s
Test result: Operating time =11.6260s
∆t=0.014s

3.2 46G_DMT_Alarm

Test Result

1.U,I
Va: 0.000V Vc-Freq: 50.000Hz Ib-PH: 0.00°
Va-PH: 0.00° Vz: 0.000V Ib-Freq: 50.000Hz
Va-Freq: 50.000Hz Vz-PH: 0.00° Ic: 0.000A
Vb: 0.000V Vz-Freq: 50.000Hz Ic-PH: 120.00°
Vb-PH: -120.00° Ia: 0.330A Ic-Freq: 50.000Hz
Vb-Freq: 50.000Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 0.000V Ia-Freq: 50.000Hz
Vc-PH: 120.00° Ib: 0.330A

Page 4
PW Series Relay Testing System
Trip time
6.0240S

Test Result Assessing:


Setting:49G.DT.I_Set=0.11A Time delay =6s
Test Value:I=0.33A(I2=0.11A)
Test result: Operating time =6.0240s
∆t=0.024s

4. Voltage Protection (59P/27P)

4.1 Overvoltage Protection (59P)

Test Result

1.U,I
Va: 86.370V Vc-Freq: 50.000Hz Ib-PH: 0.00°
Va-PH: 0.00° Vz: 0.000V Ib-Freq: 50.000Hz
Va-Freq: 50.000Hz Vz-PH: 0.00° Ic: 0.000A
Vb: 86.370V Vz-Freq: 50.000Hz Ic-PH: 120.00°
Vb-PH: -120.00° Ia: 0.000A Ic-Freq: 50.000Hz
Vb-Freq: 50.000Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 86.370V Ia-Freq: 50.000Hz
Vc-PH: 120.00° Ib: 0.000A

Trip time
0.3130S

Test Result Assessing:


Setting:Gen.59P1.Upp_Set=149.5V,Time delay =0.3s
Test Value:Upp=149.67V
Test result: Operating time =0.3130s
∆t=0.013s

4.2 Undervoltage Protection (27P)

Test Result

1.U,I
Va: 53.000V Vb: 53.000V Vc: 53.000V
Va-PH: 0.00° Vb-PH: -120.00° Vc-PH: 120.00°
Va-Freq: 50.000Hz Vb-Freq: 50.000Hz Vc-Freq: 50.000Hz

Page 5
PW Series Relay Testing System
Vz: 0.000V Ia-Freq: 50.000Hz Ic-PH: 120.00°
Vz-PH: 0.00° Ib: 0.850A Ic-Freq: 50.000Hz
Vz-Freq: 50.000Hz Ib-PH: 0.00° Time After Tigger: 0.000s
Ia: 0.850A Ib-Freq: 50.000Hz
Ia-PH: 0.00° Ic: 0.850A

Trip time
3.3320S

Test Result Assessing:


Setting:Gen.27P1.Upp_Set=92V,Time delay =3.3s
Test Value:Upp=91.82V
Test result: Operating time =3.332s
∆t=0.032s

5. Phase Overcurrent Protection(50/51P)


Test Result

1.U,I
Va: 46.400V Vc-Freq: 50.000Hz Ib-PH: 0.00°
Va-PH: 0.00° Vz: 0.000V Ib-Freq: 50.000Hz
Va-Freq: 50.000Hz Vz-PH: 0.00° Ic: 0.000A
Vb: 46.400V Vz-Freq: 50.000Hz Ic-PH: 120.00°
Vb-PH: -120.00° Ia: 1.200A Ic-Freq: 50.000Hz
Vb-Freq: 50.000Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 46.400V Ia-Freq: 50.000Hz
Vc-PH: 120.00° Ib: 0.000A

Trip time
3.0290S

Test Result Assessing:


Setting:Gen.50/51P2.I_Set=1.2A,Time delay =3s
Test Value: U=46.4V I=1.2A
Test result: Operating time =3.0290s
∆t=0.0290s

Page 6
PW Series Relay Testing System

6. Reverse Power Protection (32R)

6.1 32R_CONV_Trip

Test Result

1.U,I
Va: 60.000V Vc-Freq: 50.000Hz Ib-PH: -120.00°
Va-PH: 90.80° Vz: 0.000V Ib-Freq: 50.000Hz
Va-Freq: 50.000Hz Vz-PH: 0.00° Ic: 1.000A
Vb: 60.000V Vz-Freq: 50.000Hz Ic-PH: 120.00°
Vb-PH: -29.20° Ia: 1.000A Ic-Freq: 50.000Hz
Vb-Freq: 50.000Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 60.000V Ia-Freq: 50.000Hz
Vc-PH: 210.80° Ib: 1.000A

Trip time
30.1380S

Test Result Assessing:


Setting:32R.CONV.P_Set=1%,Time delay =30s
Test Value:P%= -1.26%
Test result: Operating time =30.138s
∆t=0.138s

6.2 32R_SEQ_Trip

Test Result

1.U,I
Va: 60.000V Vc-Freq: 50.000Hz Ib-PH: -120.00°
Va-PH: 90.80° Vz: 0.000V Ib-Freq: 50.000Hz
Va-Freq: 50.000Hz Vz-PH: 0.00° Ic: 1.000A
Vb: 60.000V Vz-Freq: 50.000Hz Ic-PH: 120.00°
Vb-PH: -29.20° Ia: 1.000A Ic-Freq: 50.000Hz
Vb-Freq: 50.000Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 60.000V Ia-Freq: 50.000Hz
Vc-PH: 210.80° Ib: 1.000A

Trip time
1.0520S

Page 7
PW Series Relay Testing System

Test Result Assessing:


Setting:32R.SEQ.P_Set=1%,Time delay =1s
Test Value: P%= -1.26%
Test result: Operating time =1.052s
∆t=0.052s

7. Frequency Protection (81O/81U)

7.1 Overfrequency Protection (81O)

7.1.1 81O.OF1_Trip

Test Result

1.U,I
Va: 60.000V Vc-Freq: 51.600Hz Ib-PH: 0.00°
Va-PH: 0.00° Vz: 0.000V Ib-Freq: 50.000Hz
Va-Freq: 51.600Hz Vz-PH: 0.00° Ic: 0.000A
Vb: 60.000V Vz-Freq: 50.000Hz Ic-PH: 120.00°
Vb-PH: -120.00° Ia: 0.000A Ic-Freq: 50.000Hz
Vb-Freq: 51.600Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 60.000V Ia-Freq: 50.000Hz
Vc-PH: 120.00° Ib: 0.000A

Trip time
20.1520S

Test Result Assessing:


Setting:81O.OF1.f_Set=51.5Hz,Time delay =20s
Test Value:F=51.59Hz
Test result: Operating time =20.1520s
∆t=0.152s

7.1.2 81O.OF2_Trip

Test Result

1.U,I
Va: 60.000V Va-Freq: 52.100Hz Vb-PH: -120.00°
Va-PH: 0.00° Vb: 60.000V Vb-Freq: 52.100Hz

Page 8
PW Series Relay Testing System
Vc: 60.000V Ia: 0.000A Ic: 0.000A
Vc-PH: 120.00° Ia-PH: 0.00° Ic-PH: 120.00°
Vc-Freq: 52.100Hz Ia-Freq: 50.000Hz Ic-Freq: 50.000Hz
Vz: 0.000V Ib: 0.000A Time After Tigger: 0.000s
Vz-PH: 0.00° Ib-PH: -120.00°
Vz-Freq: 50.000Hz Ib-Freq: 50.000Hz

Trip time
10.1490S

Test Result Assessing:


Setting:81O.OF2.f_Set=52Hz,Time delay =10s
Test Value:F=52.09Hz
Test result: Operating time =10.1490s
∆t=0.1490s

7.2 Underfrequency Protection (81U)

7.2.1 81U.OF1_Trip

Test Result

1.U,I
Va: 60.000V Vc-Freq: 47.900Hz Ib-PH: -120.00°
Va-PH: 0.00° Vz: 0.000V Ib-Freq: 50.000Hz
Va-Freq: 47.900Hz Vz-PH: 0.00° Ic: 1.000A
Vb: 60.000V Vz-Freq: 50.000Hz Ic-PH: 120.00°
Vb-PH: -120.00° Ia: 1.000A Ic-Freq: 50.000Hz
Vb-Freq: 47.900Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 60.000V Ia-Freq: 50.000Hz
Vc-PH: 120.00° Ib: 1.000A

Trip time
20.1520S

Test Result Assessing:


Setting:81U.UF1.f_set=48Hz,Time delay =20s
Test Value:F=47.9Hz
Test result: Operating time =20.1520s
∆t=0.152s

Page 9
PW Series Relay Testing System
7.2.2 81U.OF2_Trip

Test Result

1.U,I
Va: 60.000V Vc-Freq: 47.400Hz Ib-PH: -120.00°
Va-PH: 0.00° Vz: 0.000V Ib-Freq: 47.400Hz
Va-Freq: 47.400Hz Vz-PH: 0.00° Ic: 0.850A
Vb: 60.000V Vz-Freq: 47.400Hz Ic-PH: 120.00°
Vb-PH: -120.00° Ia: 0.850A Ic-Freq: 47.400Hz
Vb-Freq: 47.400Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 60.000V Ia-Freq: 47.400Hz
Vc-PH: 120.00° Ib: 0.850A

Trip time
10.1530S

Test Result Assessing:


Setting:81U.UF2.f_Set=47.5Hz,Time delay =20s
Test Value:F=47.4Hz
Test result: Operating time =10.1530s
∆t=0.1530s

8. Stator Ground Fault Protection (64S)

8.1 64S1.3U0_L _Trip(64S1)

Test Result

1.U,I
Va: 7.100V Vc-Freq: 50.000Hz Ib-PH: 0.00°
Va-PH: 0.00° Vz: 0.000V Ib-Freq: 50.000Hz
Va-Freq: 50.000Hz Vz-PH: 0.00° Ic: 0.000A
Vb: 0.000V Vz-Freq: 50.000Hz Ic-PH: 120.00°
Vb-PH: -120.00° Ia: 0.000A Ic-Freq: 50.000Hz
Vb-Freq: 50.000Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 0.000V Ia-Freq: 50.000Hz
Vc-PH: 120.00° Ib: 0.000A

Trip time
1.0360S

Page 10
PW Series Relay Testing System

Test Result Assessing:


Setting:64S1.3U0_L=7V,Time delay =1s
Test Value:U=7.1V
Test result: Operating time =1.0360s
∆t=0.0360s

8.2 64S1.3U0_L _Alarm(64S1)

Test Result

1.U,I
Va: 7.100V Vc-Freq: 50.000Hz Ib-PH: 0.00°
Va-PH: 0.00° Vz: 0.000V Ib-Freq: 50.000Hz
Va-Freq: 50.000Hz Vz-PH: 0.00° Ic: 0.000A
Vb: 0.000V Vz-Freq: 50.000Hz Ic-PH: 120.00°
Vb-PH: -120.00° Ia: 0.000A Ic-Freq: 50.000Hz
Vb-Freq: 50.000Hz Ia-PH: 0.00° Time After Tigger: 0.000s
Vc: 0.000V Ia-Freq: 50.000Hz
Vc-PH: 120.00° Ib: 0.000A

Trip time
1.0390S

Test Result Assessing:


Setting:64S1.3U0_L=7V Time delay =1s
Test Value:I=7.1V
Test result: Operating time =1.0390s
∆t=0.0390s

8.3 64S1.3U0_H_Trip(64S1)

Test Result

1.U,I
Va: 16.100V Vc-PH: 120.00° Ia-Freq: 50.000Hz
Va-PH: 0.00° Vc-Freq: 50.000Hz Ib: 0.000A
Va-Freq: 50.000Hz Vz: 0.000V Ib-PH: 0.00°
Vb: 0.000V Vz-PH: 0.00° Ib-Freq: 50.000Hz
Vb-PH: -120.00° Vz-Freq: 50.000Hz Ic: 0.000A
Vb-Freq: 50.000Hz Ia: 0.000A Ic-PH: 120.00°
Vc: 0.000V Ia-PH: 0.00° Ic-Freq: 50.000Hz

Page 11
PW Series Relay Testing System
Time After Tigger: 0.000s

Trip time
0.5330S

Test Result Assessing:


Setting:64S1.3U0_H=16V,Time delay =0.5s
Test Value:U=16.1V
Test result: Operating time =0.533s
∆t=0.033s

Page 12

You might also like