Disturbance recording and


fault locating device DRL6600U
Product guide
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

Contents
1. Overview .......................................................................................................................................................... 2
2. Available functions ........................................................................................................................................... 3
4. Recording mode............................................................................................................................................... 7
5. Current recording ............................................................................................................................................. 8
Variation current recording ............................................................................................................................... 8
Delta current recording .................................................................................................................................... 8
Residual overcurrent recording ........................................................................................................................ 8
6. Phase voltage recording .................................................................................................................................. 8
Overvoltage recording ...................................................................................................................................... 8
Delta voltage recording .................................................................................................................................... 8
Third-, fifth-, and seventh-harmonic overvoltage recording .............................................................................. 8
7. Rate-of-change frequency recording ................................................................................................................ 9
8. Binary signal recording .................................................................................................................................... 9
9. Fault Locating .................................................................................................................................................. 9
10. Data analysis ............................................................................................................................................ 9
11. Operation ................................................................................................................................................ 10
Manual recording ........................................................................................................................................... 10
Remote recording .......................................................................................................................................... 10
Local / remote reset ....................................................................................................................................... 10
12. Monitoring ............................................................................................................................................... 10
Analog signal sampling monitoring ................................................................................................................ 10
Binary signal monitoring ................................................................................................................................. 10
Disturbance report ......................................................................................................................................... 10
13. Basic IED functions ................................................................................................................................. 10
Self-supervision with internal event list .......................................................................................................... 10
Self-supervision function ................................................................................................................................ 10
Time Synchronization..................................................................................................................................... 10
Authority management ATMNG ..................................................................................................................... 10
14. HMI (Human-machine-interface) ..............................................................................................................11
15. Communication ........................................................................................................................................11
Station level communication ...........................................................................................................................11
16. Hardware description .............................................................................................................................. 12
17. Connection diagram ................................................................................................................................ 13
18. Mounting method .................................................................................................................................... 15
19. Technical data ......................................................................................................................................... 17
20. Ordering information ............................................................................................................................... 24

ABB 1
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

1. Overview

DRL6600U Disturbance Recording and Fault Locating DRL6600U consist of a recording unit with CPU and
Device for power system is adapted to substations, hard disk and a separate HMI. It uses the CPU and
industrial use, railways, and power generation of each hard disk for recording, and data transfer to the system
voltage level, where recording the disturbance of power data manager or other tasks on the HMI will not
system is necessary. It truthfully records electric obstruct its main function. Also, the separated HMI can
variables during such events as power oscillation, be used in data analysis without obstructing the
frequency collapse or voltage fluctuation, providing disturbance recording.
indispensable data support for incident analysis and
operation maintenance.

2 ABB
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

2. Available functions

Table 1: Main functions

Name Description ANSI IEC60617 IEC61850

I over Phase overcurrent recording 50 I>

I2 over Negative-sequence overcurrent recording 46 I2>

3I0 over Residual overcurrent recording 50N IN>

U over Phase overvoltage recording 59 U>

U1 over Positive-sequence overvoltage recording U1>

U2 over Negative-sequence overvoltage recording U2>

3U0 over Residual overvoltage recording 59N 3U0>

U under Phase undervoltage recording 27 U<

U1 under Positive-sequence undervoltage recording U1<

U sudden change Delta phase voltage recording △U>

3U0 sudden change Delta residual voltage recording △3U0>

I sudden change Delta phase current recording △I>

3I0 sudden change Delta residual current recording △IN>

Current variation Variation current recording

ABB 3
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

Name Description ANSI IEC60617 IEC61850

Over frequency Over frequency recording 81 f>

Low frequency Low frequency recording 81 f<

DF div dt Rate-of-change frequency recording 81R Df/dt>

U3 over Third-harmonic overvoltage recording U3>

U5 over Fifth-harmonic overvoltage recording U5>

U7 over Seventh-harmonic overvoltage recording U7>

DI Binary signal recording

Fault locating Fault locating

4 ABB
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

Table 2: Controlling and monitoring function

Name Description ANSI IEC60617 IEC61850

I over Phase overcurrent recording 50 I>

I2 over Negative-sequence overcurrent recording 46 I2>

3I0 over Residual overcurrent recording 50N IN>

U over Phase overvoltage recording 59 U>

U1 over Positive-sequence overvoltage recording U1>

U2 over Negative-sequence overvoltage recording U2>

3U0 over Residual overvoltage recording 59N 3U0>

U under Phase undervoltage recording 27 U<

U1 under Positive-sequence undervoltage recording U1<

U sudden change Delta phase voltage recording △U>

3U0 sudden change Delta residual voltage recording △3U0>

I sudden change Delta phase current recording △I>

3I0 sudden change Delta residual current recording △IN>

Current variation Variation current recording

Current circuit Monitoring current transformer secondary


87 CCSRDIF
supervision circuits

Voltage circuit Monitoring voltage transformer secondary


SSDRFUF
supervision circuits

When a recording is triggered, the triggering

Event recording reason, name, time stamp, etc. are recorded

and saved.

ABB 5
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

Name Description ANSI IEC60617 IEC61850

Disturbance A disturbance recording will be formed and

recording saved when a trigger is registered.

Manual recording Manual triggering generates a recording file

Remote control triggering generates a


Remote recording
recording file

Local reset Locally reset the LEDs

Remote reset Remotely reset the LEDs

Table 3: Communication function

Name Description ANSI IEC60617 IEC61850

IEC61850 MMS IEC61850 communication protocol function,


IEC 61850-8-1
communication HMI RJ-45

Double-point
Receive a double-point GOOSE value GOOSEDPRCV
GOOSE Receiving

Single-point
Receive a single-point GOOSE value GOOSESPRCV
GOOSE Receiving

6 ABB
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

4. Recording mode

U/I

Trigger

0-25 Cycles 0-50 Cycles 150 Cycles


A B C
1-10KHz 1-10KHz 0.5-10kHz
Start time of T-0 Start time
recording of disturbance

Figure 1: A-B-C Recording and IO time sequence

Period A: record data before the system disturbance The disturbance recorder applies the principle of
(PreTrigger) extendable recording that switches from the A to B and
Period B: record data during the early period of system C periods, ensuring a high resolution during the
disturbance (Trigger) PreTrigger and Trigger periods, and adjusting to a
Period C: record data during the middle and late lower sampling rate during the PostTrigger period in
periods of system disturbance (PostTrigger) order to reduce the long term storage requirements.
When a new disturbance occurs in period C, the
recording rate switches back to the one of period A,
ensuring that the data recorded both before and after
the disturbance is done at a high rate of sampling.
If one recording happens after another within a short
interval, they are recorded in one waveform file.

ABB 7
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

5. Current recording 6. Phase voltage recording

Variation current recording Overvoltage recording

When the power system is disturbed for some reason When supplying power over an underground cable or a
(such as closing a circuit breaker, clearing a network with high capacitance, the phase-to-ground
disturbance, or load shedding), the magnitude and capacitance of the line may contribute to a voltage rise
phase of voltage and current may change over time, (Ferranti effect). Long term operation may pose a threat
which indicates that power system oscillation occurs. to the safety of energized equipment. Thus it's
The recorder can be triggered by the variation of necessary to monitor the voltage in the power system.
current in a time slot and record these power system
oscillation. Delta voltage recording

Delta current recording Large-scale electrical equipment and conversion loads


connected to the grid are frequently powered off and
For some industrial users, the load characteristic is on. A voltage fluctuation will occur when large motors
unstable. During normal operation, the voltage and are started or when large transformer are energized,
current can fluctuate significantly for a long term, under during which the recorder can record the voltage
which circumstance the load characteristic can be fluctuations for users to analyze.
recorded by the recorder for the user to analyze.
Third-, fifth-, and seventh-harmonic
Residual overcurrent recording
overvoltage recording
By using residual current as an operation criterion, it's
possible to show the inrush process of transformer Severe harmonic pollution effects the normal operation
energization. A large 3I0 reflects a three-phase of electrical equipment, and can damage the power
imbalance in the grid as well, which can be used to system. It can lead to capacitor damage due to thermal
monitor open phase operation on the line. overload and insulation breakdown and cause
electrical machine instability. Current and voltage
harmonics in transformers increase copper and iron
losses and in turn causes the temperature to rise,
affecting the insulation and decreasing the overload
capacity margin. Because harmonics also produce
resonance and noise, it's extremely important to record
and analyze harmonics in all segments of the power
system.

8 ABB
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

7. Rate-of-change frequency 10. Data analysis

recording DRL6600U provides a cross-platform waveform


analysis tool, available in both Windows and Linux
Power system operation has a high requirement for operation systems.
frequency stability. Subtle frequency changes can With a convenient and fast channel selecting mode, it's
cause huge damage to generators and other electrical able to show any selected signal on the same page,
equipment. The DRL6600U can truthfully record and to compare and analyze currents and voltages of
abnormal changes of high frequency, low frequency different intervals, and different binary signals.
and frequency change rate in the power system. It is It can display several modes such as showing
widely adopted in power plants, substations, and for instantaneous, RMS or phasor values. It adopts to
industrial use. many advanced analysis functions such as sequence
components, power calculation, harmonics calculation,
8. Binary signal recording location and aperiodic component.
With waveform copy and paste functions it's convenient
Crucial binary signal indication information such as and fast to select and re-save the required channels of
protection operation, reclosing operation and change of the record, and then form new waveform files for
breaker indication can be recorded. Furthermore, the accident analysis and fault location.
recorded information reflects the whole process of one Direct shortcut keys and tool tips bring users
complete disturbance so that crucial operation convenience to operate all software functions.
information such as false tripping, breaker failure or Through the frequency following mode, accurate
reclosing failure can be analyzed. values of analog signals deviating from 50Hz can be
acquired.
9. Fault Locating
Fault location by impedance measurement calculates
the linear impedance between the terminal and the fault
location, and in turn determines the distance to the
disturbance.
When the corresponding parameters like line length
and line impedance have been entered, once a phase-
to-ground or phase-to-phase short circuit happens a
recording will be started. Based on the impedance at
the time the short circuit happens, the DRL6600U
automatically calculates and determines the distance
between the device and the fault point.

ABB 9
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

11. Operation 13. Basic IED functions

Manual recording Self-supervision with internal event list

Manual recording is available on the HMI. The self-supervision (INTERRSIG and


SELFSUPEVLST) will respond to internal system
Remote recording events generated by the different internal self-
supervision functions. Internal events are saved in one
Remote recording is available via MMS client
internal event list.
Local / remote reset
Self-supervision function
After disturbance recording, latched LED indicators
The build-in self-supervision function continuously
and digital outputs can be reset either locally or
monitors the hardware and software operation status.
remotely.
Once a disturbance or abnormality is detected, the
device will send an alarm signal.
12. Monitoring
Time Synchronization
Analog signal sampling monitoring
Clock synchronization makes comparison of events
DRL6600U acquires and stores data from current and and disturbance data among all IEDs in the system
voltage channels with a sampling frequency of 10kHz. possible.
In the IED, the internal time can be synchronized from
Binary signal monitoring the following sources:
• SNTP
Binary signal monitoring can display the status of
• IRIG-B
binary signals.

Disturbance report Authority management ATMNG

All access to device requires authorization. Setting up


Disturbance reports will be formed and saved when a
users and managing authority levels is realized via the
signal triggers recording or when there are fault
HMI. There are 3 levels of operation authority: system
location results
management, equipment maintenance and settings
The disturbance report will show automatically after
modification.
recording, and can also be manually checked.
The disturbance report will record the start time, subsite
number, subsite name, triggering name, triggering file
name, fault line, fault distance, fault phase, tripping
phase, and current and voltage RMS of one cyclic wave
both before and after the disturbance.

10 ABB
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

14. HMI (Human-machine-interface)

The LHMI consists of the IED front panel and an HMI.


There are status and operation indicators on the IED
front panel.

DRL6600U-HMI contains the following: an industrial


PC, a display (LCD), a keyboard, and a mouse.
The HMI is used for setting, monitoring and controlling
of DRL6600U.

15. Communication

Station level communication

The DRL6600U disturbance recorder supports the IEC


61850-8-1 communication protocol.
The device provides 8 Ethernet ports on the
DRL6600U-HMI, so that several independent networks
can be connected simultaneously.
It also provides one Ethernet port on the CPU module
of the IED for horizontal GOOSE communication.

ABB 11
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

16. Hardware description

NET
RESET

NET

RESET
NET
BCODE
SER
RESET
S1
S2
AC IN- S3
AC IN+
S4
DC IN-
DC IN+

POWER
FAULT

Figure 2: Device module

Table 4: Module description

Name SN Location Function

POWER X100 No.1 Power supply module

Signal panel module, providing


SIGNAL X200 No.2 binary output and time
synchronization

CPU X300 No.3 Recording CPU

AD X400 No.5…No.8 Analog signal sampling

DI X500 No.9…No.10 Binary signal sampling

AC X600 No.14…No.16,No.18…No.20 VT/CT connection

DC X610 No.17 DC connection

DRL6600U-HMI X700 External HMI management unit

12 ABB
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

17. Connection diagram

A total of 96 analog inputs can be accommodated. AC current and AC voltage modules can be configured according
to the actual project requirements. The highest permissible voltage for voltage channels is 180V, and largest current
for current channels is 40In (In is 1A or 5A, please note clearly in the order form). Primary and secondary side rated
values can be configured in the analog input channel settings of the device. Up to 192 binary input connections are
supported.

Figure 3: Analog input module sketch diagram

1) No.17 is a DC input module with 8 DC input channels, applicable to for example generator recording. When No. 17 and No. 16 modules exist simultaneously, the first 8 analog signal channels of

No.16 are invalid.

ABB 13
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

Figure 4: Binary input terminal diagram, up to 192 binary input connections are supported

14 ABB
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

18. Mounting method

This device commonly adopts panel mode mounting.

A=465mm

B=450mm

D=133.3mm

C=532.2mm

E=190.6mm

G=Φ8-M5(Or M6)

F=133.3mm

Figure 5: IED mounting cut-out dimension diagram

ABB 15
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

A=465mm

B=450mm

C=89.5mm D=76.2mm
E=Φ9 mm (4-9x9)

Figure 6: Keyboard and mouse carrier cut-out dimension diagram

Figure 7: Display hanging bar cut-out dimension diagram


A=482.6±0.2mm

B=350mm
E=101.6mm
D=354.8±0.15 mm

C=300mm
F=76.2mm
G=101.6mm

I=Φ8-6.8x10.3mm
H=37.7mm

Figure 8: Display mounting cut-out dimension diagram

16 ABB
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

19. Technical data

Table 5: 12U, 19" case IED device dimensions and weights

Description Reference value

Width 465mm

Height 531.8mm

Depth 249.5mm

Case weight <40kg

DRL6600U-HMI weight 1.3kg

Table 6: Power supply

Description Reference value

Rated value 110/220V, DC

Permissible deviation -15%...+10%

Maximum burden 80W

Maximum allowable ripple ≤ 5%

Maximum de-energized time for direct current without IED restart 100ms

ABB 17
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

Table 7: analog input

Description Reference value

Frequency 50Hz ± 5Hz

Linear operating range Voltage circuit: 0.1V...150V


Current circuit: 0.1A…100A

Analog input channel amount 24/48/72/96 channels

Rated current In 1/5A phase current or residual current

Overload capability
• Continuous 4 times the rated value
• 1s 100 times the rated value
I • 10s 10 times the rated value

Dynamic current tolerance


• Half-wave value
1250A

Input impedance <20mΩ

Rated voltage Un 57.74V AC

Rated voltage Udn 300V


U Voltage tolerance
• Continuous RMS 2 times the rated value

Rated voltage overload <0.5VA/phase

Table 8: binary input

Description Reference value

Operating range Maximum input voltage 300V DC

Rated voltage 110/220V DC

Leakage current <5mA

Power loss/input <0.5W

Critical voltage <55%Un: reliable off; >70%Un: reliable on

Binary input channel amount 32/64/96/128/160/192 channels

Binary resolution ≤1ms

18 ABB
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

Table 9: Signal output

Description Reference value

Rated voltage 250V DC/AC

Continuous current-carrying capacity 5A

3 seconds current-carrying capacity 10A

0.5 second current-carrying capacity 30A

Table 10: Data communication Ethernet port

Ethernet port Protocol Cable Data transfer rate

LAN/LHMI port (X0), only for external LHMI - RJ-45 100MBits/s

LAN1(X1) TCP/IP RJ-45 100MBits/s

Table 11: IRIG-B port

Type Protocol Cable

Screw terminal, pin row IRIG-B Shielded twisted pair


header
Recommendation: CAT 5, Belden RS-485 (9841-
9844) or Alpha electric wire (Alpha 6222-6230)

Table 12: IP classification, flush mounting

Description Value

IED front panel IP 40

IED back panel, connecting terminal IP 20

DRL6600U-HMI front panel and side IP 40

Table 13: Ambient conditions

Description Reference value

Operation temperature range -10...+55ºC (continuous)

Short-time service temperature range -25…+70ºC(<16h)

Relative humidity <93%, no moisture condensation

Atmospheric pressure 86...106 kPa

Altitude Maximum 2000m

Transport and storage temperature range -40...+70ºC

ABB 19
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

Table 14: Ambient test

Description Type test Reference standard

Cold test
• Operation 16 hours at -10ºC IEC 60068-2-1/ANSI
• Storage 16 hours at -25ºC C37.90-2006

Dry heat test


• Operation 16 hours at +55ºC IEC 60068-2-2/ANSI
• Storage 16 hours at +70ºC C37.90-2006

Wet heat test


• Fixed status 144 hours at +40ºC, humidity 93% IEC 60068-2-78
6 loops at +25…+55ºC, humidity 93-
95%
• Loop IEC 60068-2-30

Table 15: Electro-magnetic compatibility test

Description Type test value Reference standard

100kHz and 1MHz burst disturbance


test
• Common mode
2.5kV IEC 60255-4-18
• Differential mode
1kV IEC 60255-22-1, level 3

Electrostatic discharge test


• Contact discharge 8kV IEC61000-4-2:2008
• Air discharge 15kV IEC 60255-22-2, level 4

Radio frequency interference tests


• Transmission, common mode 10V(EMF),f=150kHz...80MHz IEC 61000-4-6
20V/m(RMS),f=80...1000MHz IEC 60255-22-6, level 3
and f=1.4...2.7GHz
• Radiated, amplitude-modulated IEC 61000-4-3
IEC 60255-22-3, level 3

Fast transient disturbance tests:


• Communication port 4kV IEC 60255-22-4, level A
• Other ports 4kV

20 ABB
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

Description Type test value Reference standard

Surge immunity test


• Communication 1kV line to ground IEC 61000-4-5
• Other ports 2kV line to ground, 1kV line to IEC 60255-22-5, 3 level
line

Power frequency (50 Hz) magnetic


field
• 3s
1000A/m IEC 61000-4-8, level 4
• Continuously
100A/m

Power frequency immunity test


• Common mode RMS 300V IEC 60255-22-7, level A
• Differential mode RMS 150V

Voltage sag and short interruption IEC 60255-11


• Sag 40%/200ms IEC 61000-4-17
• Interruption 70%/500ms
0-100ms: No restart
0...∞s: Behave normally at
power off

Electromagnetic launch test


• Transmission, radio frequency, EN55011, level A
launch(main terminal)
IEC 60255-25
0.15...0.50MHz
< 79dB(µV) quasi peak
< 66dB(µV) mean value
0.5...30MHz
< 73dB(µV) quasi peak
< 60dB(µV) mean value

• Radiation, radio frequency, launch


30...230MHz

< 50dB(µV/m) quasi peak,


230...1000MHz locate from 3m away
< 57dB(µV/m) mean value,
locate from 3m away

ABB 21
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

Table 16: Insulation test

Description Type test Reference standard

Dielectric strength test


• Test voltage 2kV, 50Hz, 1min IEC 60255-5
1kV, 50Hz, 1min,

Impulse voltage test


• Test voltage 5kV, unipolar impulses, waveform: IEC 60255-5
1.2/50μs, source energy: 0.5J
1kV, unipolar impulses, waveform:
1.2/50μs, source energy: 0.5J

Insulation resistance
measurements
• Isolation resistance
>100MΩ, 500V DC IEC 60255-5

Table 17: Machinery test

Description Reference standard Requirement

Vibration response test (sine) IEC 60255-21-1 Type 2

Vibration durability test IEC 60255-21-1 level 1

Impulse response test IEC 60255-21-2 level 1

Impulse resistance test IEC 60255-21-2 level 1

Crash test IEC 60255-21-2 level 1

Table 18: Product safety

Description Reference standard

Undervoltage control order set 2006/95/EC

Standard EN 60255-27 (2005)

Table 19: EMC compatibility

Description Reference standard

EMC order 2004/108/EC

Standard EN 50263 (2000)


EN 60255-26 (2007)

22 ABB
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

Table 20: Parameters for disturbance recording and fault locating

Name Value (range) Accuracy

Phase overcurrent 0.1…20A Settings ≥ 10%In, accuracy: ±10%

Negative-sequence
0.05…20A Settings ≥ 10%In, accuracy: ±10%
overcurrent

Residual overcurrent 0.05…20A Settings ≥ 10%In, accuracy: ±10%

Phase overvoltage 50…150V ±5%

Positive-sequence
50…150V ±5%
overvoltage

Negative-sequence
0.5…30V Settings ≥ 3%Un, accuracy: ±5%
overvoltage

Residual overvoltage 0.5…200V Settings ≥ 3%Un, accuracy: ±5%

Phase undervoltage 10…120V ±5%

Positive-sequence
10…120V ±5%
undervoltage

Delta phase voltage 0.5…30V Settings ≥ 5%Un, accuracy: ±10%

Delta residual voltage 0.5…30V Settings ≥ 5%Un, accuracy: ±10%

Delta phase current 0.05…10A Settings ≥ 10%In, accuracy: ±20%

Delta residual current 0.05…10A Settings ≥ 10%In, accuracy: ±20%

Variation current 0.05…0.2% ±10%

Over frequency 50…55Hz ±0.01

Low frequency 45…50Hz ±0.01

Rate-of-change frequency 0.05…1Hz/s ±10%

Harmonic overvoltage 0.5…30V Settings ≥ 10%Un, accuracy: ±5%

Last for ≥ 2ms after binary signal


Binary signal ≤1ms
shift, trigger recording

Fault Locating - Outlet fault ≤ 2kM, others ≤ 5%

ABB 23
4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30 Issued: May 2017
Revision: -

20. Ordering information

Product
Ordering code Description PS CT
identification

UAAEAL010100000B24AAAA DRL6600U DC110V 1A

UAAEAH010100000B24AAAA DRL6600U 32 AI (24I, 8U), 8 DC, 192 BI, DC220V 1A

UAAEAL001010000B24AAAA DRL6600U GOOSE DC110V 5A

UAAEAH001010000B24AAAA DRL6600U DC220V 5A

UAAEAL120000000A24AAAA DRL6600U DC110V 1A

UAAEAH120000000A24AAAA DRL6600U DC220V 1A


48 AI (32I, 16U), 192 BI, GOOSE
UAAEAL102000000A24AAAA DRL6600U DC110V 5A

UAAEAH102000000A24AAAA DRL6600U DC220V 5A

UAAEAL220000000A24AAAA DRL6600U DC110V 1A

UAAEAH220000000A24AAAA DRL6600U DC220V 1A


64 AI (32I, 32U), 192 BI, GOOSE
UAAEAL202000000A24AAAA DRL6600U DC110V 5A

UAAEAH202000000A24AAAA DRL6600U DC220V 5A

UAAEAL220100000A24AAAA DRL6600U DC110V 1A

UAAEAH220100000A24AAAA DRL6600U DC220V 1A


80 (40I, 40U) AI, 192 BI, GOOSE
UAAEAL202010000A24AAAA DRL6600U DC110V 5A

UAAEAH202010000A24AAAA DRL6600U DC220V 5A

UAAEAL230100000A24AAAA DRL6600U DC110V 1A

UAAEAH230100000A24AAAA DRL6600U DC220V 1A


96 (56I, 40U) AI, 192 BI, GOOSE
UAAEAL203010000A24AAAA DRL6600U DC110V 5A

UAAEAH203010000A24AAAA DRL6600U DC220V 5A

AE600 AE600 Fault recorder analysis software

MCU MCU Fault recorder configuration software

24 ABB

ABB AB
Grid Automation Products
721 59 Västerås, Sweden
Phone: +46 (0) 21 32 50 00

abb.com/protection-control
4CAE000359 Rev-

© Copyright 2017 ABB. All rights reserved.


Specifications subject to change without notice.