You are on page 1of 48

DesignCriteria for Civil-Structural

25713-220-3DR-S15-00001-00B

TABLE OF CONTENTS

Section Description Page

1.0 INTRODUCTION ....................................................................................................................3


2.0 SOURCE CODE .....................................................................................................................3
3.0 CODES, SPECIFICATIONS AND REFERENCE DOCUMENTS ...........................................3
4.0 SUPPLEMENTARY INFORMATION......................................................................................5
5.0 REQUIREMENTS FOR CIVIL DESIGN..................................................................................7
6.0 REQUIREMENTS FOR STRUCTURAL DESIGN ................................................................10
7.0 DESIGN BASES...................................................................................................................16
8.0 CONSTRUCTION MATERIALS ...........................................................................................21
9.0 TRANSPORTATION LIMIT BY TRUCK...............................................................................25
10.0 FATAL RISK CONTROLS....................................................................................................25

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
2 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

1.0 INTRODUCTION

These criteria will govern the design of all the structures and facilities of the project.

All the designs shall comply with the following criteria:

 Ensure that critical facilities (those that may affect production) have an
appropriate design margin for the risk they involve.
 Maximize safety.
 Minimize risks, using proven technology.
 Minimize field construction tasks and activities.
 Reduce capital expense, by means of innovations, without reducing quality
standards.

2.0 SOURCE CODE


Together with each criteria there is a letter designating the origin of the corresponding
criteria. In some cases a reference to more than one code may be made.

Below there is a list including letters and a description of their meaning:

Code Description
A Criteria defined by the client
B Standard industry practice
C Bechtel recommendation
D Vendor-originated criteria
E Criteria from calculations or previous study
F Engineering handbook data
G Assumed data
H Criteria provided by “Technology Supplier”

3.0 CODES, SPECIFICATIONS AND REFERENCE DOCUMENTS


3.1. GENERAL

Unless otherwise specified, the design of all the structures and facilities shall be based B
on the applicable portion of the following codes, specifications, industry standards,
regulations and other referenced documents, based on the current version at the
contractual start of this project.

Apart from the above mentioned codes and regulations, the design shall comply with B
any other law or regulation of the Chilean authorities. In case of conflict among codes
and standards, the most stringent one shall be applied.

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
3 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

In all sites and facilities operated by BHPB, all the recommendations stated in the Fatal A
Risk Control Standard GLD.010, shall be strictly applied.

3.2. ABBREVIATIONS B

NCh Norma Chilena – Instituto Nacional de Normalización


M.O.P. Ministerio de Obras Públicas
ACI American Concrete Institute
IBC International Code Council
AISC American Institute of Steel Construction
AASHTO American Association of State Highway and Transportation Officials
API American Petroleum Institute

3.3. CODES AND SPECIFICATIONS A/B

NCh 431 Construcción – Sobrecargas de Nieve


NCh 432 Cálculo de la Acción del Viento Sobre las Construcciones
NCh 433 Diseño Sísmico de Edificios
NCh 1537 Diseño estructural de edificios - Cargas Permanentes y Sobrecargas de
uso
NCh 2369 Diseño Sísmico de Edificios Industriales
Manual de Carreteras M.O.P.

ACI-318 Building Code Requirements for Reinforced Concrete


AISC ASD Manual of Steel Construction, Allowable Stress Design, Ninth Edition
AISC 303 Code of Standard Practice for Steel Buildings and Bridges
AISC 360 Specification for Structural Steel Buildings

AISE Std. 13 Guide for the Design and Construction for Mill Buildings
API-650 Welded Steel Tanks for Oil Storage
AWS-D1.1 Structural Welding Code
AASHTO Standard Specification for Highway Bridges

GLD.010 Fatal Risk Control Standard (BHPB Standard)

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
4 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

MSHA Mine Safety and Health Administration


D.S. N° 72/2004 Mining Security Regulation of the Mining Department which
modifies D.S. Nº 132/2002 (Published in the Official Newspaper
on February 7th, 2004)

3.4. OTHER DOCUMENTS A/B

Informe Geotécnico, por E.C. Rowe & Asociados, 1989

Estudio Geotécnico Concentrador Laguna Seca, Informe Final, por E.C. Rowe &
Asociados, 1998.

Informe Geotécnico Planta Molienda y Concentradora Laguna Seca, por ARCADIS


Geotécnica, 2008, 25421-138-30R-8210-GE-INF-114.

ANSI/NAAMM MBG 531/532 National Association of Architectural Metal


Manufacturers
ASCE-7 Minimum Design Loads for Building and Other Structures

IBC 2006, International Building Code

OSHA, Occupation, Safety and Health Administration

Manual ICHA del Instituto Chileno del Acero (Second Edition)


Proyecto de Levantamiento Topográfico para Escondida Fase V mediante Sistema
LIDIAR, Digimap Chile 2008

4.0 SUPPLEMENTARY INFORMATION


4.1. SITE INFORMATION

Site information must be obtained from Bechtel document General Specification for Site A
Conditions No. 25599-240-3PS-G000-00001 (HOLD)

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
5 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

4.2. COORDINATES INFORMATION


The coordinates system information is based in the document for Site Condition indicated in
the previous item.

System of Horizontal Coordinates A


All the coordinates shall be in meters, based on the UTM (Universal Transverse
Mercator) System gotten from WGS84 datum.

Vertical Coordinate System A


All elevations shall be indicated in meters above the sea level.

Project Topographical Controls B


Existing monoliths in the mines site shall be used.

4.3. UNDERGROUND WATER LAVEL

The groundwater level has not been detected in the drilling as required by the end of the A/E
items "5.2 Sondajes" and "6.0 Caracterización Geotécnica”, of “Informe Geotécnico
Planta Molienda y Concentradora Laguna Seca, de ARCADIS Geotécnica, 2008,
25421-138-30R-8210-GE-INF-114”. For more details see Report ARCADIS 25421-138-
30R-8210-GE-INF-114.

4.4. FROST PENETRATION

Consider 0.7 m for the Mine general area. It does not apply for the areas of Punta A
Negra and Coloso.

4.5. SEISMOLOGY

In agreement with the BHPB, the site is considered as seismic zone 3. All seismic B
parameter for this zone must be according to NCh 433 and NCh 2369. This applies for
the Mine Area, Punta Negra and Coloso Sector.

4.6. SOIL CONDITIONS

For soil information required for the Civil/Structural design, refer to “Informe Geotécnico A
Planta Molienda y Concentradora Laguna Seca, de ARCADIS Geotécnica, 2008,
25421-138-30R-8210-GE-INF-114”.

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
6 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

5.0 REQUIREMENTS FOR CIVIL DESIGN


5.1. EARTHWORKS

A
For preliminary designs, where there is no geotechnical information, volumes shall be
estimated considering the following slopes:

Temporary cuts in rock Vertical For cuts not exceeding 1.8


meters, vertically measured.
1(H):3(V) For cuts not exceeding 6
meters vertically measured.
1(H):2(V) For cuts exceeding 6 meters
vertically measured.

Permanent cuts in rock 1(H):2(V) For cuts exceeding 6 to 8


meters, vertically measured, steps having
minimum width of 4 meters, shall be
constructed every 6 to 8 meters of height.

Cuts in mining backfills 1.5(H):1(V)

Temporary cuts in natural soil Vertical For cuts not exceeding 1.0
meters, vertically measured.
1(H):2(V) For cuts not exceeding 4
meters vertically measured.
1(H):1(V) For cuts exceeding 4 meters

Permanent cuts in natural soil 1.5(H):1(V) For cuts exceeding 6 to 8


meters, vertically measured, steps having
minimum width of 4 meters, shall be
constructed every 6 to 8 meters of height.

Compacted backfills 1.5(H):1(V) With steps having 4 meters of


width, every 10 meters of height.

Backfills (ore benches) 2(H):1(V)

5.2. YARD GRADING

Yard finish grading will be a minimum 150 mm below the adjacent floor slabs. B/E

Yard grading will have a finish grade slope of 2% as minimum, moving away B/E
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
7 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

from the structures and toward the storm drainage.

5.3. ROADS

Design maximum speed in plant 60 km/h E


Maximum slopes: E

Main roads 6 %
Secondary roads 10 %

Minimum horizontal curve radius: E

Main roads 50 m
Secondary roads 25 m
Maintenance and inspection roads 25 m

Minimum vertical curve radius (parabola): E

Main roads 30 m

Minimum road widths: E

Main roads (includes 2 berms, 1.65 m wide each) 10 m


Secondary roads (includes 2 berms, 1.20 m wide) 8.4 m
Maintenance and inspection roads (1 lane) 4 m

Road design shall be developed in accordance with the “Manual de Carreteras” by B


M.O.P.- Chile.

They shall have the necessary signs to comply with the safety standards of Minera A
Escondida Ltda. These signs shall be indicated in specific drawings for this
purpose. A

All the roads shall have safety berms in both sides.


If possible, independent roads shall be carried out for pedestrians, light vehicles A
and heavy vehicles and/or equipment.
A/E
The minimum vertical height under an overpass, or other interference, will be of
4.6 meters, except in areas where special equipment operate, where minimum
vertical height shall be adjusted for the traffic of 300 t trucks, with full load, or other
specific requirements.
5.4. PROTECTION OF BURIED PIPES

The main pipes with danger of being frozen, such as, for example, those fire protected, A

shall go buried at a minimum depth of 1 meter under the elevation or ground level.

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
8 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

The minimum depth to cover pipes of fresh water and potable water shall be 0.7 meters

under the ground level.

5.5. STRUCTURES EXPOSED TO SEA ENVIROMENT

The use of FRP-type material shall be considered for covering structures and for floor
grating in platforms.

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
9 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

6.0 REQUIREMENTS FOR STRUCTURAL DESIGN


6.1. LOADS

6.1.1 Dead Loads (D)

Dead loads (D) shall include the weight of the structure, roof, floors, walls, B
partition walls, weight of the finishes (false ceiling, stucco, floor finishes, etc.),
platforms and any other material.

In case of not existing specific information in another project document, weights


shall be obtained from the following specific weights :

Specific Weight
Material
kg/m3
Non-Reinforced Concrete 2400

Reinforced Concrete 2500

Structural Steel 7850

Dry Wood 650

Wet Wood 850

Wood Board 550

Structural Backfill (1) 1900

F. R. P. 1500
(1): Use this value except otherwise indicated in the Geotechnical Report

Ore Properties A/E


For civil/structural design, the ore properties shall be as follows:

Crushed Ore
Angle of repose:
Stockpiled 37.5°
Discharge 70.0°

Density for:
Weight 2.1 t/m3
Volume 1.8 t/m3
Equipment loads, included those of its operation, shall be in accordance with the
drawings of the Vendor and shall include the product to be handled. These
loads shall be treated as dead loads, and therefore estimate of weights must be
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
10 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

conservative.

Design loads for equipment support shall include the following:

a) Equipment dead loads, including pipelines and platforms belonging to the


equipment itself, such as lining for instance.

b) Operation loads shall include the content of the fixed equipment, containers,
belts, pipelines, etc., with weights of materials in normal operation.

c) The maximum operation loads shall include dead loads plus full equipment at
maximum capacity, with maximum density materials, including large
accumulations; e.g. dumps and screws stuck, etc. These loads must be
considered as short-term application.

6.1.2 Live Loads (L) B

They are those loads that may be present or not; therefore, they shall be
analyzed in their most unfavorable locations, taking into account their maximum
and minimum values. The live loads (L) shall include floor area loads, access
ladders, loads of manual equipment, soil active pressure and truck movable
loads. Live loads in floor areas shall be omitted in areas taken up by equipment
whose weight is specifically included in the dead loads. The live load shall not
be omitted under equipment where the access is allowed, for instance under
elevated tanks. Under no circumstance the minimum live load may be lower
than that specified in Section 6.1.3.

This category includes transient-type loads or extreme condition load such as


short-circuit, start or jam. This type of loads shall be obtained from information
of the equipment manufacturer and/or from the Process Design Criteria. The
use of this type of loads shall be analyzed case by case and always together
with the supervising engineer (EGS).

For the case of concurrence of these loads with a seismic event, see NCh 2369,
item 4.5.

Design live loads shall be stated in the calculations.

6.1.3 Minimum Live Loads B

The minimum values are obtained from NCh 1537, except that indicated below:

a) The following minimum uniform live load shall be used in the design,
unless otherwise specified in certain areas, by means of specific
equipment load analyses. Certainly, other applicable loads shall be
defined separately in below sections.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
11 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

 Roofs 100 kgf/m2


 Offices 400 kgf/m2
 Meeting rooms and change rooms 500 kgf/m2
 Laboratories 500 kgf/m2
 Stairs and walkways 250 kgf/m2
(only for pedestrian traffic)
 Platforms and elevated floors 500 kgf/m2
 Mill operation floors and platforms 1250 kgf/m2
around the mills (except in the mill liner
storage area)
 Floors on the ground 1250 kgf/m2
 Discharge areas adjacent to the Plant 1250 kgf/m2
 Control rooms 500 kgf/m2
 Electric rooms 1250 kgf/m2
 Mill liner storage floors 3700 kgf/m2
 Walkways of conveyor galleries 250 kgf/m2
 Concentrated horizontal load applied 100 kgf
at the top of handrail.
 Uniform horizontal load applied 60 kgf/m
at the top of handrail.

 Truck Load AASHTO, HS20-44


increased in 20% or mining
trucks when applicable.
Loads covered in the following items b, c, and d, are considered as operation
live load that shall be concurrent with the rest of the design loads applicable to
the specific element under consideration. This load shall not be brought to the
columns, and shall not be applied in offices, laboratories, change rooms or
similar areas.

b) A load of 1000 kgf concentrated in main beams.


c) A concentrated load on office floor slabs of 1000 kgf shall be applied on
an area of 0.24 m2.
d) A concentrated load on operation floor slabs of 1400 kgf that shall be on
an area of 0.24 m2.
6.1.4 Live Load Reduction B

Live load reduction in floors and roofs may be made as follows:

a) No reduction in areas of deposits, storage and tanks.


b) For other situations item 7 of the standard NCh 1537 shall be applied.

6.1.5 Snow Load (S) A/E

Chilean Standard NCh 431 shall be used.

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
12 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

The minimum load to be considered will be 100 kg/m2.

For seismic analysis purposes, the snow load shall not be considered concurrent
with the seismic action.

6.1.6 Wind Load (W) A/B/


The design shall be based on NCh 432. E

Cases not covered in this standard shall be solved by the standard ASCE 7,
taking into account an exposure coefficient C, with 3 seconds of gust speed of
175 km/h.

6.1.7 Seismic Loads (E) B

Structures shall be designed for seismic loads determined according to Section


4.5

For equipment provided by foreign vendors, these shall be adjusted to the


national standards, especially to that stated in item 4.6 of the code NCh 2369

The importance coefficient for each facilities are defined in Exibit B.

The seismic mass shall be according to item 5.1.3 of the code NCh 2369. The
live loads indicated in item 6.1.3 of this design criteria are operating and
maintenance load which should not be considered in the calculus of the seismic
mass. In the case of warehouses if there is no specific information should be
considered 50% of the live load for the calculus of the seismic mass. These
considerations do not apply for load combinations.

6.1.8 Crane load (G & Gi) and Impact Loads (Vi) B

The minimum increase in the equipment loads by vertical impact (Vi) shall be as
follows:

If there are no specifications of dynamic coefficients from the vendor,


calculations of the supporting structures of the equipment shall include an impact
load determined by the following percentages referred to the maximum load per
wheel:

 Vehicles with pneumatic tires: 30%


 Vehicles with solid tires: 50%
 Conveyor feeders: 25%
 Lifts and hoists: 100%

The loads of the Bridge Crane (G) shall be defined by the equipment vendors
and correspond to the maximum load per wheel in rail/supporting beams,
monorails and other mobile equipment.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
13 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

The vertical impact in cranes (Gi) shall be determined as per AISE Technical
Report Nº 13. According to this document, for the particular case of cranes
aimed at providing maintenance in industrial buildings, the vertical impact is
determined as 20% of the maximum load per wheel. This type of crane
corresponds to the main type this project has.

6.1.9 Thermal Expansion Loads A

All the structures and elements shall be designed to accommodate the loads
produced by temperature differentials of 30 °C.

6.1.10 Minimum Lateral Load (other than Wind and Earthquake) B

Minimum compression load in struts, used in lateral stability of structures, shall


be 2% of the axial load of supporting columns or beams.

6.2 LOADS IN TEMPORARY CONSTRUCTIONS B

For wind, earthquake or temporary loads, caused by potential conditions or non-regular


construction sequences, the allowable stress, or capacity, must be increased by the
factor 1.33.

The effort and deflection of the supporting plate and support structure shall be revised
for the weight of the wet concrete plus 150 kgf/m2 without increase of the allowable
stress.

6.3 MEMBERS SUBJECT TO VIBRATING EQUIPMENT LOADS B

6.3.1 General

Supports for equipment of centrifugal operation type, specially mills, fans,


crushers, vibratory screens or feeders, shall be revised for vibrations considering
the equipment with its whole weight. The design of these supports shall
consider the Bechtel's Standard Design Guidelines N° 3DG-C13-00001 and
3DG-C13-00003.

The unbalanced dynamic forces, for vibration analysis, shall be obtained form
the vendor and the Project Mechanical Group.

Structural elements subject to vibrations shall have as a minimum a ratio


(section height/ element clearance) of 1:12, unless a vibration analysis states
that a lower height may be used.

The operation platforms near to vibratory equipments must expire with the
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
14 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

requirements of stiffness that guarantee a suitable structural behavior and


operation, in front of to the vibrations.

In order to minimize the vibrations caused by the resonance in braced


structures, the following ratios between the first natural frequency (fn) of support
beams and the forced frequency (fo) shall be secured. For the revision by
resonance, elements shall be considered with just one degree of freedom.

The first natural frequency of vibration of the equipment support beam (fn), shall
be moved away from the excitation frequency (fo) of the equipment, in function
of the support conditions of the supporting beam:

Beam joint to the end of Span (m) fn/fo

Column Until 6 0.80 ≥ fn/fo ≥ 1.5


Column Over 6 0.75 ≥ fn/fo ≥ 2.0
Beam Until 6 0.75 ≥ fn/fo ≥ 2.0
Beam Over 6 0.75 ≥ fn/fo ≥ 2.5

The main beams supporting vibratory equipment shall have a slenderness ratio
(section height / element clearance) of 1/12 as a minimum. Lower slenderness
shall be allowed if the dynamic analysis of deformations for cyclic loads allows it.

Structural elements shall be provided with adequate lateral support, braces


and/or elastic supports to minimize vibrations.

Foundations shall be designed so as they have a natural frequency sufficiently


different from the frequency applied to avoid resonance. Foundations shall be
separated from the slabs and foundations of building columns by 20 millimeters
with expansion material where possible.

6.3.2 Loads of Vibratory Equipment B

Unbalanced dynamic forces for the support design per vibratory equipment shall
be obtained from the Vendor.

When a detailed evaluation is required, the designer shall ensure a difference


between the natural frequency of the first vibration mode of the support and the
equipment frequency.

Recommended criteria are as follows:


 Natural frequency lower than 2/3 of the machine frequency.
 Natural frequency higher than 1.5 of the machine frequency.

Particularly, the following equipment supports shall be formally obtained from


Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
15 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

calculations of vibration frequency and amplitude for the support design:


 Gyratory crushers
 Cone crushers
 Mills
 Vibratory screens

The soil/structure interaction shall be considered when calculating the natural


frequencies and displacements.

The vibration effect shall be minimized, using braces or mass dampers. Vibration
isolators may be used where practical.

All recommendations from the manufacturer and those stated in Bechtel’s


experience.

7.0 DESIGN BASES


7.1 GENERAL B
All the steel structures shall be designed by the method of allowable stresses. Soil bearing
pressure shall be checked for the actual loads against allowable pressures. All the
reinforced concrete structures shall be designed by the ultimate strength design method.

7.2 LOAD COMBINATIONS B


For the design of steel structures, based on allowable stresses, recommendations stated in
the IBC standard shall be used. Similarly, for the case when loading coming from the action
of a bridge crane are included, recommendations of the AISE Technical Report No. 13 shall
be used. At least the following load combinations result from these recommendations.

For purposes of load combination, it shall be considered that operation loads are included
in the dead loads (D). Similarly, wind and seismic loads must be considered as acting in all
possible directions.

For NCh 2369 combinations (8 & 9 in table bellow) reduction factor for live loads shall not
be considered (a=1).

For structure design:

Load combinations Reference Factor (*)


standard
1 D+H+L+T IBC, Eq. 16-9 1

2 D + H + (Lr or S) IBC, Eq. 16-10 1

3 D + H + 0.75(L + T) + 0.75(Lr or S) IBC, Eq. 16-11 1

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
16 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Load combinations Reference Factor (*)


standard
4 D+H+W IBC, Eq. 16-12 1

5 D + H + 0.75W + 0.75L + 0.75(Lr or S) IBC, Eq. 16-13 1

6 0.6D + H + W IBC, Eq. 16-14 1

7 0.6D + H IBC, Eq. 16-15 1

8 Ver NCh 2369 NCh2369, 4.5 a)- i) 1.33

9 Ver NCh 2369 NCh2369, 4.5 a)- ii) 1.33

10 D + L + (Lr or S) + G1 TR N° 13, 3.10.2.2 (1) 1

11 D + L + (Lr or S) + G2 + W TR N° 13, 3.10.2.3 (1) 1.33

12 D + L + (Lr or S) + G3 + ½W TR N° 13, 3.10.2.3 (2) 1.33

13 D + L + (Lr or S) + G4 TR Nº 13, 3.10.2.3 (3) 1.33

14 D + L + (Lr or S) + Gd + E TR Nº 13, 3.10.2.3 (4) 1.33


(*): Factor is applied on allowable stresses

When using load combinations as per IBC, it is not allowed the increase of the allowable
stresses resulting in case of occurrence of the combination. The above is due because the
load combination has already considered the possible occurrence. However, when using
load combinations as explicitly defined in NCh 2369 and in AISE Technical Report No. 13, it
is indeed allowed to increase the allowable stresses arising from the possibility of
occurrence of the earthquake.

The seismic action coming from a bridge crane shall be considered as per the item C11.1.3
of the standard NCh2369.

The meaning of the load symbols used is as follows:


D = Dead Loads
L = Live load
Lr = Roof live load
T = Temperature
S = Normal snow load
W = Wind
E = Service level earthquake, including horizontal and vertical effect simultaneously
M = Assembly
G = Crane
H = Earth pressures (it is used only when loading is increased)

Crane loading: G1 = GVS + GI + GSS + GIS (one single crane)


Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
17 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

G1 = GVM + GSS + GIS (more than one crane)


G2 = GVS + GI
G3 = GVS + GI + GSS
G4 = GVS + GI + 0,67 GbS

GVS : Vertical load produced by the bridge crane


GSS : Lateral impact load (transversal) produced by the bridge crane
GI : Vertical impact produced by the bridge crane
GIS : Longitudinal tensile force produced by the bridge crane
Gvm : Vertical load produced by various bridge cranes
Gd : All the bridge cranes stopped together (with own normal weight)
GbS : Longitudinal horizontal impact on extreme limit, 100% travelling speed

For the sizing of foundations, based on the allowable stresses, recommendations stated in
the IBC standard shall be used, from which the following load combinations result at least.
B

In order to verify stability and soil bearing pressure, the following load combinations shall be
used:
Load combinations Reference standard Factor

1 D + H + L + (Lr or S) IBC, Eq. 16-16 1.00

2 D+H+L+W IBC, Eq. 16-17 (*)

3 D + H + L + W + 0.5S IBC, Eq. 16-18 (*)

4 D + H + L + 0.5W + S IBC, Eq. 16-19 (*)

5 See NCh 2369 NCh2369, 4.5 a)- i) (*)

6 See NCh 2369 NCh2369, 4.5 a)- ii) (*)

7 D + L + (Lr or S) + Gvm TR N° 13, 3.12.1.1 1.00

8 D+W TR N° 13, 3.12.1.2 1.00

9 D + L + (Lr or S) + G5 + ½W TR N° 13, 3.12.1.3(1) (*)

10 D + L + (Lr or S) + G6 TR N° 13, 3.12.1.3(2) (*)

11 D + Gd + E TR N° 13, 3.12.1.4 (*)

12 D + G7 TR N° 13, 3.12.1.5 (*)

Crane loading: G5 = Gvm + GSS


G6 = GVS + GI + 0,67 GbS
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
18 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

G7 = Gd + GbS

Note (*): Increase of the soil allowable stresses must match that stated in the
corresponding Geotechnical Report.

 The rebar in reinforced concrete structures shall be determined using load combinations
stated in the ACI-318. Load factors and resistance reduction factors alternatives stated in
the Appendix C of the ACI-318 shall be used, taking into account that NCh2369 considers a
service earthquake, so 1.4E must be considered instead of 1.0 E.

7.3 DEFLECTIONS B
Deflections due to live load and wind or seismic load shall not exceed the following:

a. Beams in general Span/300

b. Truss Span/700

c. Beams supporting vibratory equipment Span/1000

d. Roofs
 Roofing and secondary members
(purlins and joist hanger) Span/240

e. Floors
 Floor plate and grating Span/200
 Concrete Floor slabs Table 9.5 (b) ACI318

f. Walls (wind lateral load)


 Siding and girts Span/180

g. Crane girders and monorail beams (without impact)


 Vertical Span/1000
 Horizontal Span/500

h. Crane girders and monorail beams (with impact)


 Vertical Span/600
 Horizontal Span/500

i. Belt Conveyors
 Grating vertical deformation due to belt
conveyor overload Span/600

 Grating horizontal deformation due to lateral loads Span/600

 Horizontal deformation at the ends of the stacker trusses


Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
19 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

due to lateral loads, (maximum deformation shall be


limited to 150 millimeters). Span/800
 Steel frames for head pulley supports,
speed reducers and drives. Span/800

j. Walls of concrete blocks masonry and


partitions rigid joint to the structure. H/500

k. Flexible walls and partitions


 Firm soil H/250
 Soft soil H/333

l. Piperack
 Vertical Span/250

7.4 CRANE GIRDERS B


Crane girders shall be designed according to the Technical Report N° 13 AISE – Guide for
the Design and Construction of Grinding Buildings.

7.5 CORROSION B
For most structures, corrosion shall be controlled by means of a protection painting. For
special cases, process engineers may indicate an over thickness to take into account the
loss of material due to corrosion.

7.6 FOUNDATIONS B
The design of foundations shall be based on the recommendations of the Project
Geotechnical Report.

The minimum safety factors included in the foundation design shall be as shown as follows:
 Overturning in Retaining Walls 1.5 (1.3 with seismic load)
 Overturning in Foundations according to NCh 2369
 Sliding in Retaining Walls 1.5 (1.3 with seismic load)
 Flotation 1.5

7.7 BOTTOM-SUPPORTED TANKS B


The bottom supported tanks shall be designed to resist seismic forces stated in these
criteria applying the recommendations stated in NCh2369 and API 650.

7.8 STEEL STRUCTURES B


They shall be designed according to the standard AISC 360 and supplemented with the
pertinent recommendations of the standard NCh2369.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
20 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

The structural shapes shall follow the nomenclature stated in the ICHA manual.

7.9 CONCRETE STRUCTURES B


They shall be designed according to the standard ACI-318 and supplemented with the
pertinent recommendations of the standard NCh2369.

7.10 WATER RETAINING STRUCTURES B


Thickener retaining structures, shall be designed as structural items with due regard for
hydraulic considerations, taking into account soil properties, soil settlement, soil saturation,
uplift, seepage paths, piping of fines, etc.

Allowable crack width shall be limited to 0,2 mm (0,008 in).

8.0 CONSTRUCTION MATERIALS

8.1 STRUCTURAL STEEL B


Structural steel shapes, plates and bars shall comply with the requirements of ASTM A36,
A270ES (NCh 203).
The rails shall comply with ASTM A1.
The following minimum thickness shall be used for steel shapes:

MINIMUM THICKNESS GENERAL CORROSIVE


AREAS AREAS
mm mm
Connection and stiffener plates 6 8
Web thickness of built up sections 5 8
or rolled shapes
Flanges of built up sections 6 8
Angles and channels 5 6
Tubular sections 5 6
Purlins 4 6
Checkered plates 5 6
Auxiliary buildings 5 6

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
21 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

8.2 STRUCTURAL STEEL CONNECTIONS B


Shop Connections: Generally, the shop connections shall be welded. In some cases, the
shop connections might be bolted for pre-assembly of components according to drawing
instructions.
Field Connections: bolted; field welding only when stated in drawings.
Every connection shall be of bearing type with thread included in shear plane.
The bolts of each element shall comply with ASTM A325.
When friction type connections are required, the faying surfaces shall be free of scale and
free of coatings in areas closer than one bolt diameter but not less than 1 inch from the
edge of any hole, as defined in Specification for Structural Joints Using High-Strength Bolts
(RCSC, 2009, Chapter 3.2.2). Coated faying surfaces are permitted when are first cleaned
and subsequently coated with a coating that is qualified as Class A or B. This type of
coating shall not be assembled before the coating has cured. Galvanized faying surface are
also permitted when meet the requirements of ASTM A123 and subsequently roughened by
means of hand wire brushing. This type of connection is designated as Class C for design.
Each bolt shall be completely tight unless otherwise stated in drawings.
The bolts for secondary elements (non structural) shall be ASTM A307 or A42-23
(NCh 206).

8.3 GRATING B
 Gratings and fasteners ASTM A1011/A According MBG531
 Supporting flanges 32 x 5 millimeters spaced out to 30 mm
 Transversal bars Area of the transversal section not inferior to
40 mm2 and thickness not inferior to 6
millimeters spaced out to 100 mm.
 Fastening of grating Fastened by HILTI X-FCM discs as defined in
the project standard drawings.
The heavy traffic gratings shall be provided in areas with heavy vehicle flow according to
the Project drawing directions.
Inclined, wet or outdoor walkways and platforms shall be of serrated grating.

8.4 CHECKERED PLATES B


The checkered plate shall be of ASTM A36 steel with a regular pattern of raised diamonds
or lines at least in two in-plant directions.

The ends of the checkered plates shall be welded in field to their supports with welding of
40 mm long with a fillet of 5 mm every 300 mm, and to interval elements, with 15
millimeters of welding at 450 mm.

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
22 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

They can be also fastened to the main supporting beams with HILTI X-FCP discs or other
equivalent.

8.5 ANCHOR BOLTS B


The anchor bolts and plates shall comply with ASTM A36/A36M or A42-23 (NCh 206). The
nuts shall comply with ASTM A563 and the round washers shall comply with ASTM F436.
The minimum bolt diameter shall be ¾ inches.

8.6 HANDRAILS A
According to OSHA Norms (1926.502(b)) handrails must meet:

 Top Rail Top Rail System shall be 1100 mm (42 inches) plus or minus 3
inches (8cm) above the walking/working level

50 mm (2 inches) pipe size as minimum diameter

 Intermediate Rails Intermediate Rail System shall be installed between the top
edge of the guardrail system and the walking/working surface
when there is no wall or parapet wall at least 530mm (21
inches) high

50 mm (2 inches) pipe size as minimum diameter

 Posts Spaced out to 1800 mm maximum

50 mm (2 inches) pipe size as minimum diameter

 Toe Plate 100 x 6 millimeters of minimum thickness

with 10 millimeters of clearance over the floor or platform

8.7 CONCRETE

B/E
Unless otherwise noted in drawings, the concrete design compressive strengths (f 'c) shall
be in accordance with ACI, as follows:

Use Code NCh f 'c

Structural concrete (footing, H35 300 kgf/cm2 (3625psi)


Equipment foundations, etc.)

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
23 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Massive concrete H30 250 kgf/cm2 (3556psi)


(Mill foundations)

Electric ducts H20 150 kgf/cm2(2175psi)

Footing and building H35 300 kgf/cm2(3625psi)


foundations

Slab on grade and elevated slabs H35 300 kgf/cm2(4350psi)


Retaining walls, recovery
tunnel and thickeners

Operating floor at Grinding H35 300 kgf/cm2(4350psi)

Lean concrete fill H10 75 kgf/cm2(1088psi)

Special cases H45 400 kgf/cm2(5690psi)

Compression stress (f 'c) as stated in standard NCh 430 and NCh 170, with level of
confidence will be 90%.

8.8 REINFORCING STEEL B


The reinforcing steel shall be in accordance with ASTM A615 Grade 60 or A630-420H
(NCh 204) in accordance with Chilean code, unless otherwise stated in drawings.

8.9 WELDED WIRE FABRIC B


Welded Wire Fabric shall be in accordance with ASTM A185 or AT56-50H (NCh 218 and
219), with a minimum yield strength of 450 MPa for wire diameters of 3 millimeter and
greater.

This type of mesh shall be basically used in slab on grade.

8.10 CONCRETE MASONRY B


The concrete masonry units shall be in accordance to NCh 181, Class A, with a
minimum compression stress of 70 kgf/cm2 (5 units’ average).

Allowable stresses in concrete masonry shall be determined in accordance with NCh 1928.

8.11 GROUT B
For column and equipment, the grout shall be cementitious non-shrink and non-metallic and
shall be in accordance with the Technical Specification 25599-240-3PS-DB02-00001.

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
24 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

9.0 TRANSPORTATION LIMIT BY TRUCK


Normal dimensions and load limit for transportation by truck should be as follows: B/E

Maximum width m 2.5


Maximum height m 3.0
Maximum length m 14.0
Maximum weight t 35.0

Higher sizes and weights are possible, but subject to special permit, and they shall be
confirmed by the Construction Traffic Department.

10.0 FATAL RISK CONTROLS


All designs must consider the requirements establish in BHP Billiton Standard GLD.010 A

for Fatal Risk Controls. Exhibit A includes a summary of main topics.

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
25 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

EXHIBIT A

FATAL RISK CONTROLS

Summary of Main Topics

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
26 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

SUMMARY OF GLD.010 MAIN TOPICS


Requirement will be reflected
Item Description in design document noted

1 Develop and implement an approved site traffic


Road drawings
management plan (see Appendix 1 and Appendix 2) of
GLD.010 Standard.

1 Provide safe access and egress, including emergency Road & Access drawings
egress, from mobile equipment.

Provide suitable walkways, handrails or other safe


systems of work for operation and maintenance of Road drawings
1
components where there is a potential to fall two or more
meters where a fall could result in a significant incident.

Mitigate risks from storing, handling and maintenance of Road drawings


1
tires.

Set standards for the quality of ground support materials


and the means for assuring the integrity of their
3 Specs
installation, including frequency of examination and
methods for repair.

Set standards for the monitoring and analysis of ground


3 condition data, excavation stability and the effectiveness Specs
of ground support.

Identify vessels, containers or pipes containing hazardous


4 materials by appropriate signage or labels and, where Signage drawings
relevant, clearly indicate the direction of flow.

Locate vessels, containers, bulk stores and process areas


containing hazardous materials within areas of adequate
4 design and size to safely contain spills and allow for CSA Drawings
effective response to spills.

6 CSA Drawings
Design new plant and equipment and plan tasks to
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
27 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

minimize the need to work at height.

Provide, where work at height is unavoidable, a secure


working area of suitable design and strength which
includes:

-flooring securely fastened in place so it cannot be


6 accidentally dislodged; CSA Drawings

-mesh, railings or solid barriers to prevent a person falling;

-toeboards or similar means to prevent tools and materials


falling off the edge of the platform.

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
28 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

EXHIBIT B

SEISMIC DESIGN IMPORTANCE COEFFICIENT

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
29 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
0220-CV-220 220 OVERLAND CONVEYOR CV-2C 1.0
0220-SL-112 220 BELT SCALE 1.0
0220-ST-720 220 DISCHARGE CHUTE CV-220, FROM CRUSHER N° 5 1.0
1220-BN-040 1220 SURGE AND DISTRIBUTION BIN FROM CRUSHER N° 5 1.2
1220-BN-041 1220 SURGE AND DISTRIBUTION BIN FROM CRUSHER N° 2 1.2
1220-CV-010 1220 BELT CONVEYOR CV-010 FROM CRUSHER N° 3 1.0
1220-CV-016 1220 BELT CONVEYOR CV-016 FROM CRUSHER N° 2 1.0
1220-CV-105 1220 OVERLAND CONVEYOR CV-105 1.0
1220-CV-108 1220 OVERLAND CONVEYOR CV-108 1.0
1220-CV-109 1220 OVERLAND CONVEYOR CV-109 1.0
1220-CV-110 1220 OVERLAND CONVEYOR CV-110 1.0
1220-CV-112 1220 OVERLAND CONVEYOR CV-112 1.2
1220-CV-221 1220 BELT CONVEYOR FROM CRUSHER N° 3 TO CV-102 1.0
1220-CV-222 1220 BELT CONVEYOR FROM CRUSHER N° 3 TO CV-108 1.0
1220-DS-020 1220 DUST SUPPRESSION SYSTEM FOR DISCHARGE CV-105 1.0
1220-DS-021 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE BELT FEEDER FE-040 1.0
1220-DS-022 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE BELT FEEDER FE-041 1.0
1220-DS-023 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE BELT FEEDER 5 FEB-3305 1.0
1220-DS-024 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE BELT CONVEYOR CV-016 1.0
1220-DS-025 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE BELT FEEDER FE-042 1.0
1220-DS-026 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE BELT FEEDER FE-043 1.0
1220-DS-027 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE BELT FEEDER FE-005 1.0
1220-DS-028 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE BELT CONVEYOR CV-010 1.0
1220-DS-029 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE PANT LEG CHUTE 1.0
1220-DS-030 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE BELT CONVEYOR CV-221 1.0
1220-DS-031 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE BELT CONVEYOR CV-222 1.0
1220-DS-032 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE OVERLAND CONVEYOR CV-108 1.0
1220-DS-033 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE OVERLAND CONVEYOR CV-109 1.0
1220-DS-034 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE OVERLAND CONVEYOR CV-110 1.0
1220-DS-035 1220 DUST SUPRESSION SYSTEM FOR DISCHARGE BELT CONVEYOR 0221-CV-220 1.0
1220-FE-040 1220 OVERLAND CONVEYOR 0220-CV-102 BELT FEEDER 1.0
1220-FE-041 1220 OVERLAND CONVEYOR 1220-CV-108 BELT FEEDER 1.0
1220-FE-042 1220 OVERLAND CONVEYOR 0220-CV-102 BELT FEEDER FROM CRUSHER N° 2 1.0
1220-FE-043 1220 OVERLAND CONVEYOR 1220-CV-108 BELT FEEDER FROM CRUSHER N° 2 1.0
1220-HU-143 1220 LANCES HYDRAULIC UNIT - BN-040 1.2
1220-HU-146 1220 LANCES HYDRAULIC UNIT - BN-041 1.2
1220-MA-206 1220 SUSPENDED ELECTROMAGNETIC SEPARATOR FOR DISCHARGE BELT FEEDER FE-040 1.0
1220-MA-207 1220 SUSPENDED ELECTROMAGNETIC SEPARATOR FOR DISCHARGE BELT FEEDER FE-041 1.0
1220-MA-208 1220 SUSPENDED ELECTROMAGNETIC SEPARATOR FOR DISCHARGE BELT FEEDER FE-042 1.0
1220-MA-209 1220 SUSPENDED ELECTROMAGNETIC SEPARATOR FOR DISCHARGE BELT FEEDER FE-043 1.0
1220-MA-210 1220 SUSPENDED ELECTROMAGNETIC SEPARATOR FOR DISCHARGE BELT CONVEYOR CV-221 1.0
1220-MA-211 1220 SUSPENDED ELECTROMAGNETIC SEPARATOR FOR DISCHARGE BELT CONVEYOR CV-222 1.0
1220-SL-020 1220 BELT SCALE 1.0
1220-SL-050 1220 BELT SCALE 1.0
1220-SL-051 1220 BELT SCALE 1.0
1220-SL-052 1220 BELT SCALE 1.0
1220-SL-053 1220 BELT SCALE 1.0
1220-SL-118 1220 BELT SCALE 1.0
1220-SL-231 1220 BELT SCALE 1.0
1220-ST-040 1220 BELT FEEDER FE-040 DISCHARGE CHUTE 1.0
1220-ST-041 1220 BELT FEEDER FE-041 DISCHARGE CHUTE 1.0
1220-ST-708 1220 FEED CV-102/CV-108 CHUTE, FROM CRUSHER N° 3 1.0
1220-ST-721 1220 DISCHARGE CHUTE CV-105, FROM CRUSHER N° 5 1.0
1220-ST-722 1220 DISCHARGE CHUTE BIN BN-040 TO FE-040 1.2
1220-ST-723 1220 DISCHARGE CHUTE BIN BN-040 TO FE-041 1.2
1220-ST-724 1220 DISCHARGE CHUTE 5FEB-3305, FROM CRUSHER N° 2 1.0
1220-ST-725 1220 DISCHARGE CHUTE CV-016, FROM CRUSHER N° 2 1.0
1220-ST-726 1220 DISCHARGE CHUTE BIN BN-041 TO FE-042 1.2
1220-ST-727 1220 DISCHARGE CHUTE BIN BN-041 TO FE-043 1.2
1220-ST-728 1220 DISCHARGE CHUTE FE-042, FROM CRUSHER N° 2 1.0
1220-ST-729 1220 DISCHARGE CHUTE FE-043, FROM CRUSHER N° 2 1.0
1220-ST-730 1220 DISCHARGE CHUTE FE-005, FROM CRUSHER N° 3 1.0
1220-ST-731 1220 DISCHARGE CHUTE CV-221, FROM CRUSHER N° 3 1.0
1220-ST-732 1220 DISCHARGE CHUTE CV-222, FROM CRUSHER N° 3 1.0
1220-ST-733 1220 DISCHARGE CHUTE CV-102 A CV-109 1.0

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
30 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1220-ST-734 1220 DISCHARGE CHUTE CV-108 1.0
1220-ST-735 1220 DISCHARGE CHUTE CV-109 1.0
1220-ST-736 1220 DISCHARGE CHUTE CV-110 1.0
1220-ST-737 1220 DISCHARGE CHUTE CV-111 1.0
1220-ST-807 1220 LANCES STORAGE RACK - ST-722 1.0
1220-ST-808 1220 LANCES STORAGE RACK - ST-723 1.0
1220-ST-810 1220 LANCES STORAGE RACK - ST-726 1.0
1220-ST-811 1220 LANCES STORAGE RACK - ST-727 1.0
1230-CH-047 1230 STOCK PILE SERVICE HOIST 1.0
1230-EL-001 1230 STOCKPILE FREIGHT ELEVATOR 1.2
1240-CH-110 1240 BELT FEEDER MANUAL HOIST 1.0
1240-CH-111 1240 BELT FEEDER MANUAL HOIST 1.0
1240-CH-112 1240 BELT FEEDER MANUAL HOIST 1.0
1240-CH-113 1240 BELT FEEDER MANUAL HOIST 1.0
1240-CH-114 1240 BELT FEEDER MANUAL HOIST 1.0
1240-CH-115 1240 BELT FEEDER MANUAL HOIST 1.0
1240-CH-116 1240 BELT FEEDER MANUAL HOIST 1.0
1240-CH-117 1240 BELT FEEDER MANUAL HOIST 1.0
1240-CV-023 1240 SAG MILL FEED CONVEYOR 1.2
1240-DS-016 1240 DUST SUPPRESSION SYSTEM 1.0
1240-DS-016-01 1240 DUST SUPPRESSION - BELT FEEDER FE-014 1.0
1240-DS-016-02 1240 DUST SUPPRESSION - BELT FEEDER FE-015 1.0
1240-DS-016-03 1240 DUST SUPPRESSION - BELT FEEDER FE-016 1.0
1240-DS-016-04 1240 DUST SUPPRESSION - BELT FEEDER FE-017 1.0
1240-DS-016-05 1240 DUST SUPPRESSION - BELT FEEDER FE-018 1.0
1240-DS-016-06 1240 DUST SUPPRESSION - BELT FEEDER FE-019 1.0
1240-DS-016-07 1240 DUST SUPPRESSION - BELT FEEDER FE-020 1.0
1240-DS-016-08 1240 DUST SUPPRESSION - BELT FEEDER FE-021 1.0
1240-DS-017 1240 DUST SUPPRESSION SYSTEM 1.0
1240-DS-017-01 1240 DUST SUPPRESSION CONVEYOR CV-109 1.0
1240-FA-008 1240 RECLAIM TUNNEL VENTILATION SYSTEM 1.0
1240-FA-008-01 1240 CENTRIFUGAL VENTILATOR 1.2
1240-FA-008-02 1240 BAG FILTER 1.0
1240-FA-009 1240 EMERGENCY TUNNEL CENTRIFUGAL VENTILATOR 1.2
1240-FA-011 1240 EMERGENCY TUNNEL CENTRIFUGAL VENTILATOR 1.2
1240-FE-014 1240 COARSE ORE RECLAIM BELT FEEDER 1.2
1240-FE-015 1240 COARSE ORE RECLAIM BELT FEEDER 1.2
1240-FE-016 1240 COARSE ORE RECLAIM BELT FEEDER 1.2
1240-FE-017 1240 COARSE ORE RECLAIM BELT FEEDER 1.2
1240-FE-018 1240 COARSE ORE RECLAIM BELT FEEDER 1.2
1240-FE-019 1240 COARSE ORE RECLAIM BELT FEEDER 1.2
1240-FE-020 1240 COARSE ORE RECLAIM BELT FEEDER 1.2
1240-FE-021 1240 COARSE ORE RECLAIM BELT FEEDER 1.2
1240-HU-138 1240 LANCES HYDRAULIC UNIT 1.0
1240-SL-023 1240 SAG MILL FEED BELT SCALE 1.0
1240-ST-625 1240 SAG MILL FEED CONVEYOR DISCHARGE CHUTE 1.0
1240-ST-626 1240 STOCK PILE SUPPLY CHUTE 1.0
1240-ST-627 1240 STOCK PILE SUPPLY CHUTE 1.0
1240-ST-628 1240 STOCK PILE SUPPLY CHUTE 1.0
1240-ST-629 1240 STOCK PILE SUPPLY CHUTE 1.0
1240-ST-630 1240 STOCK PILE SUPPLY CHUTE 1.0
1240-ST-631 1240 STOCK PILE SUPPLY CHUTE 1.0
1240-ST-632 1240 STOCK PILE SUPPLY CHUTE 1.0
1240-ST-633 1240 STOCK PILE SUPPLY CHUTE 1.0
1240-ST-634 1240 STOCK PILE DISCHARGE CHUTE 1.0
1240-ST-635 1240 STOCK PILE DISCHARGE CHUTE 1.0
1240-ST-636 1240 STOCK PILE DISCHARGE CHUTE 1.0
1240-ST-637 1240 STOCK PILE DISCHARGE CHUTE 1.0
1240-ST-638 1240 STOCK PILE DISCHARGE CHUTE 1.0
1240-ST-639 1240 STOCK PILE DISCHARGE CHUTE 1.0
1240-ST-640 1240 STOCK PILE DISCHARGE CHUTE 1.0
1240-ST-641 1240 STOCK PILE DISCHARGE CHUTE 1.0
1240-ST-642 1240 LANCES STORAGE RACK - ST-626 1.0
1240-ST-643 1240 LANCES STORAGE RACK - ST-627 1.0
1240-ST-644 1240 LANCES STORAGE RACK - ST-628 1.0

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
31 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1240-ST-645 1240 LANCES STORAGE RACK - ST-629 1.0
1240-ST-646 1240 LANCES STORAGE RACK - ST-630 1.0
1240-ST-647 1240 LANCES STORAGE RACK - ST-631 1.0
1240-ST-648 1240 LANCES STORAGE RACK - ST-632 1.0
1240-ST-649 1240 LANCES STORAGE RACK - ST-633 1.0
1310-AC-050 1310 AIR COOLING CHILLER FOR ELECTRICAL ROOM ER-520 1.0
1310-AC-051 1310 AIR COOLING CHILLER FOR ELECTRICAL ROOM ER-520 1.0
1310-AC-052 1310 AIR COOLING CHILLER FOR ELECTRICAL ROOM ER-520 1.0
1310-BN-021 1310 BALL MILL GRINDING BALL STORAGE BINS 1.2
1310-BN-021-01 1310 GATE HYDRAULIC UNIT 1.0
1310-BN-022 1310 BALL MILL GRINDING BALL STORAGE BINS 1.2
1310-BN-022-01 1310 GATE HYDRAULIC UNIT 1.0
1310-BN-026 1310 SAG MILL GRINDING BALL STORAGE BINS 1.2
1310-BN-027 1310 SAG MILL GRINDING BALL STORAGE BINS 1.2
1310-CH-103 1310 ROTARY BALL FEEDER HOIST 1.0
1310-CH-104 1310 ROTARY BALL FEEDER HOIST 1.0
1310-CH-118 1310 ROTARY BALL FEEDER HOIST 1.0
1310-CH-119 1310 ROTARY BALL FEEDER HOIST 1.0
1310-CN-004 1310 SAG MILL BAY BRIDGE CRANE 1.2
1310-CN-005 1310 BALL MILL BAY BRIDGE CRANE 1.2
1310-CN-007 1310 PRIMARY CYCLONE BAY BRIDGE CRANE 1.2
1310-CN-129 1310 SAG LUBRICATION ROOM BRIDGE CRANE 1.0
1310-CN-130 1310 MB5 LUBRICATION ROOM BRIDGE CRANE 1.0
1310-CN-131 1310 MB6 LUBRICATION ROOM BRIDGE CRANE 1.0
1310-CN-132 1310 MB7 LUBRICATION ROOM BRIDGE CRANE 1.0
1310-CN-133 1310 MB8 LUBRICATION ROOM BRIDGE CRANE 1.0
1310-CS-012 1310 PRIMARY CYCLONE CLUSTER N° 5 1.2
1310-CS-013 1310 PRIMARY CYCLONE CLUSTER N° 6 1.2
1310-CS-014 1310 PRIMARY CYCLONE CLUSTER N° 7 1.2
1310-CS-015 1310 PRIMARY CYCLONE CLUSTER N° 8 1.2
1310-CV-042 1310 BALL MILL FEED BALL CONVEYOR No 1 1.0
1310-CV-043 1310 BALL MILL FEED BALL CONVEYOR No 2 1.0
1310-DI-004 1310 BALL MILL DISTRIBUTOR BOX 1.0
1310-DI-004-01 1310 DART VALVE BOX 1.0
1310-DI-004-02 1310 DART VALVE BOX 1.0
1310-DI-004-03 1310 DART VALVE BOX 1.0
1310-DI-004-04 1310 DART VALVE BOX 1.0
1310-DI-176 1310 BALL MILL DISTRIBUTOR BOX 1.0
1310-DI-176-01 1310 DART VALVE BOX 1.0
1310-DI-176-02 1310 DART VALVE BOX 1.0
1310-DI-176-03 1310 DART VALVE BOX 1.0
1310-DI-176-04 1310 DART VALVE BOX 1.0
1310-EL-006 1310 LIFT GRINDING AREA 1.0
1310-FA-241 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-242 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-243 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-244 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-245 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-246 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-247 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-248 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-249 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-250 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-251 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-252 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-253 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-254 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-255 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-256 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-257 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-258 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-259 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-260 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-261 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-262 1310 GRINDING BUILDING VENTILATOR 1.0

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
32 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1310-FA-263 1310 GRINDING BUILDING VENTILATOR 1.0
1310-FA-299 1310 BALL MILL LUBRICATION ROOM AIR EXTRACTOR 1.0
1310-FA-300 1310 BALL MILL LUBRICATION ROOM AIR EXTRACTOR 1.0
1310-FA-301 1310 BALL MILL LUBRICATION ROOM AIR EXTRACTOR 1.0
1310-FA-302 1310 BALL MILL LUBRICATION ROOM AIR EXTRACTOR 1.0
1310-FA-303 1310 SAG MILL LUBRICATION ROOM AIR EXTRACTOR 1.0
1310-FA-312 1310 PACKAGED UNITARY COOLING ROOFTOP FOR ELECTRICAL ROOM ER-522 1.0
1310-FA-313 1310 FAN PRESSURIZATION FOR ELECTRICAL ROOM ER-522 1.0
1310-FA-314 1310 PACKAGED UNITARY COOLING ROOFTOP FOR ELECTRICAL ROOM ER-520 1.0
1310-FA-315 1310 PACKAGED UNITARY COOLING ROOFTOP FOR ELECTRICAL ROOM ER-520 1.0
1310-FA-316 1310 PACKAGED UNITARY COOLING ROOFTOP FOR ELECTRICAL ROOM ER-520 1.0
1310-FA-317 1310 PACKAGED UNITARY COOLING ROOFTOP FOR ELECTRICAL ROOM ER-520 1.0
1310-FA-318 1310 PACKAGED UNITARY COOLING ROOFTOP FOR ELECTRICAL ROOM ER-520 1.0
1310-FA-319 1310 PACKAGED UNITARY COOLING ROOFTOP FOR ELECTRICAL ROOM ER-520 1.0
1310-FE-032 1310 BALL MILL ROTARY BALL FEEDER 1.0
1310-FE-033 1310 SAG MILL ROTARY BALL FEEDER 1.0
1310-FE-034 1310 SAG MILL ROTARY BALL FEEDER 1.0
1310-FE-206 1310 BALL MILL ROTARY BALL FEEDER 1.0
1310-HU-127 1310 VALVE HYDRAULIC UNIT 1.0
1310-HU-128 1310 VALVE HYDRAULIC UNIT 1.0
1310-HU-129 1310 VALVE HYDRAULIC UNIT 1.0
1310-HU-130 1310 VALVE HYDRAULIC UNIT 1.0
1310-HU-131 1310 VALVE HYDRAULIC UNIT 1.0
1310-HU-132 1310 VALVE HYDRAULIC UNIT 1.0
1310-HU-133 1310 VALVE HYDRAULIC UNIT 1.0
1310-LA-040 1310 BALL MILL FEED LAUNDER 1.0
1310-LA-041 1310 BALL MILL FEED LAUNDER 1.0
1310-LA-042 1310 BALL MILL FEED LAUNDER 1.0
1310-LA-043 1310 BALL MILL FEED LAUNDER 1.0
1310-LA-044 1310 CYCLONE OVERFLOW COLLECTOR LAUNDER 1.2
1310-LA-045 1310 CYCLONE UNDERFLOW LAUNDER 1.2
1310-LA-046 1310 CYCLONE UNDERFLOW LAUNDER 1.2
1310-LA-047 1310 CYCLONE UNDERFLOW LAUNDER 1.2
1310-LA-048 1310 CYCLONE UNDERFLOW LAUNDER 1.2
1310-LA-049 1310 SAMPLER DISCHARGE LAUNDER 1.2
1310-LA-050 1310 SAMPLER DISCHARGE LAUNDER 1.2
1310-LA-051 1310 SAMPLER DISCHARGE LAUNDER 1.2
1310-LA-052 1310 SAMPLER DISCHARGE LAUNDER 1.2
1310-LA-054 1310 CYCLONE OVERFLOW SAMPLER DISCHARGE LAUNDER 1.2
1310-LA-073 1310 FEED CYCLONE SAMPLER LAUNDER 1.2
1310-LA-074 1310 FEED CYCLONE SAMPLER LAUNDER 1.2
1310-LA-075 1310 FEED CYCLONE SAMPLER LAUNDER 1.2
1310-LA-076 1310 FEED CYCLONE SAMPLER LAUNDER 1.2
1310-LA-082 1310 EMERGENCY SPILLS PIPE 1.2
1310-LA-087 1310 BALL MILL FEED LAUNDER 1.0
1310-LA-088 1310 BALL MILL FEED LAUNDER 1.0
1310-MB-005 1310 BALL MILL 1.2
1310-MB-005-01 1310 BALL MILL FEED CHUTE 1.2
1310-MB-005-02 1310 BALL MILL BEARING LUBE SYSTEM 1.2
1310-MB-005-03 1310 BALL MILL BRAKE SYSTEM 1.2
1310-MB-005-04 1310 MOTOR BALL MILL CICLOCONVERTER COOLING SYSTEM 1.2
1310-MB-005-05 1310 BALL MILL JACKING SYSTEM 1.0
1310-MB-005-21 1310 LOW PRESSURE LUBE PUMP 1.0
1310-MB-005-22 1310 LOW PRESSURE LUBE PUMP 1.0
1310-MB-005-23 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MB-005-24 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MB-005-25 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MB-005-26 1310 BALL MILL ACCUMULATOR CHARGE PUMP 1.0
1310-MB-005-31 1310 BALL MILL BRAKE CALIPER SYSTEM 1.0
1310-MB-005-32 1310 BALL MILL BRAKE SYSTEM OIL TANK 1.0
1310-MB-005-33 1310 BALL MILL BRAKE SYSTEM PUMP 1.0
1310-MB-005-34 1310 BRAKE HYDRAULIC UNIT MANUAL RELEASE 1.0
1310-MB-005-53 1310 BALL MILL MOTOR COOLING SYSTEM 1.2
1310-MB-005-54 1310 BALL MILL MOTOR COOLING SYSTEM 1.2
1310-MB-005-55 1310 BALL MILL CYCLOCONVERTER COOLING SYSTEM 1.2

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
33 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1310-MB-006 1310 BALL MILL 1.2
1310-MB-006-01 1310 BALL MILL FEED CHUTE 1.2
1310-MB-006-02 1310 BALL MILL BEARING LUBE SYSTEM 1.2
1310-MB-006-03 1310 BALL MILL BRAKE SYSTEM 1.2
1310-MB-006-04 1310 MOTOR BALL MILL CICLOCONVERTER COOLING SYSTEM 1.2
1310-MB-006-05 1310 BALL MILL JACKING SYSTEM 1.0
1310-MB-006-21 1310 LOW PRESSURE LUBE PUMP 1.0
1310-MB-006-22 1310 LOW PRESSURE LUBE PUMP 1.0
1310-MB-006-23 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MB-006-24 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MB-006-25 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MB-006-26 1310 BALL MILL ACCUMULATOR CHARGE PUMP 1.0
1310-MB-006-31 1310 BALL MILL BRAKE CALIPER SYSTEM 1.0
1310-MB-006-32 1310 BALL MILL BRAKE SYSTEM OIL TANK 1.0
1310-MB-006-33 1310 BALL MILL BRAKE SYSTEM PUMP 1.0
1310-MB-006-34 1310 BRAKE HYDRAULIC UNIT MANUAL RELEASE 1.0
1310-MB-006-53 1310 BALL MILL MOTOR COOLING SYSTEM 1.2
1310-MB-006-54 1310 BALL MILL MOTOR COOLING SYSTEM 1.2
1310-MB-006-55 1310 BALL MILL CYCLOCONVERTER COOLING SYSTEM 1.2
1310-MB-007 1310 BALL MILL 1.2
1310-MB-007-01 1310 BALL MILL FEED CHUTE 1.2
1310-MB-007-02 1310 BALL MILL BEARING LUBE SYSTEM 1.2
1310-MB-007-03 1310 BALL MILL BRAKE SYSTEM 1.2
1310-MB-007-04 1310 MOTOR BALL MILL CICLOCONVERTER COOLING SYSTEM 1.2
1310-MB-007-05 1310 BALL MILL JACKING SYSTEM 1.0
1310-MB-007-21 1310 LOW PRESSURE LUBE PUMP 1.0
1310-MB-007-22 1310 LOW PRESSURE LUBE PUMP 1.0
1310-MB-007-23 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MB-007-24 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MB-007-25 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MB-007-26 1310 BALL MILL ACCUMULATOR CHARGE PUMP 1.0
1310-MB-007-31 1310 BALL MILL BRAKE CALIPER SYSTEM 1.0
1310-MB-007-32 1310 BALL MILL BRAKE SYSTEM OIL TANK 1.0
1310-MB-007-33 1310 BALL MILL BRAKE SYSTEM PUMP 1.0
1310-MB-007-34 1310 BRAKE HYDRAULIC UNIT MANUAL RELEASE 1.0
1310-MB-007-53 1310 BALL MILL MOTOR COOLING SYSTEM 1.2
1310-MB-007-54 1310 BALL MILL MOTOR COOLING SYSTEM 1.2
1310-MB-007-55 1310 BALL MILL CYCLOCONVERTER COOLING SYSTEM 1.2
1310-MB-008 1310 BALL MILL 1.2
1310-MB-008-01 1310 BALL MILL FEED CHUTE 1.2
1310-MB-008-02 1310 BALL MILL BEARING LUBE SYSTEM 1.2
1310-MB-008-03 1310 BALL MILL BRAKE SYSTEM 1.2
1310-MB-008-04 1310 MOTOR BALL MILL CICLOCONVERTER COOLING SYSTEM 1.2
1310-MB-008-05 1310 BALL MILL JACKING SYSTEM 1.0
1310-MB-008-21 1310 LOW PRESSURE LUBE PUMP 1.0
1310-MB-008-22 1310 LOW PRESSURE LUBE PUMP 1.0
1310-MB-008-23 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MB-008-24 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MB-008-25 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MB-008-26 1310 BALL MILL ACCUMULATOR CHARGE PUMP 1.0
1310-MB-008-31 1310 BALL MILL BRAKE CALIPER SYSTEM 1.0
1310-MB-008-32 1310 BALL MILL BRAKE SYSTEM OIL TANK 1.0
1310-MB-008-33 1310 BALL MILL BRAKE SYSTEM PUMP 1.0
1310-MB-008-34 1310 BRAKE HYDRAULIC UNIT MANUAL RELEASE 1.0
1310-MB-008-53 1310 BALL MILL MOTOR COOLING SYSTEM 1.2
1310-MB-008-54 1310 BALL MILL MOTOR COOLING SYSTEM 1.2
1310-MB-008-55 1310 BALL MILL CYCLOCONVERTER COOLING SYSTEM 1.2
1310-ME-008 1310 SAG MILL DOUBLE LINER HANDLING MACHINE 1.0
1310-ME-008-01 1310 HYDRAULIC UNIT SAG MILL DOUBLE LINER HANDLING MACHINE 1.0
1310-ME-010 1310 BALL MILL LINER HANDLER 1.0
1310-ME-010-01 1310 HYDRAULIC UNIT BALL MILL LINER HANDLER 1.0
1310-ME-012 1310 SAG AND BALL MILL FEED CHUTE TRANSPORTERS 1.0
1310-ME-021 1310 LINER BOLT REMOVAL HAMMER 1.0
1310-ME-022 1310 LINER BOLT REMOVAL HAMMER 1.0
1310-ME-023 1310 LINER BOLT REMOVAL HAMMER 1.0

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
34 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1310-ME-024 1310 LINER BOLT REMOVAL HAMMER 1.0
1310-ME-025 1310 LINER BOLT REMOVAL HAMMER 1.0
1310-ME-026 1310 LINER BOLT REMOVAL HAMMER 1.0
1310-MS-002 1310 SAG MILL 1.2
1310-MS-002-01 1310 SAG MILL TROMMEL 1.2
1310-MS-002-02 1310 SAG MILL FEEDING CHUTE 1.2
1310-MS-002-31 1310 BEARING LUBE SYSTEM 1.2
1310-MS-002-32 1310 CONDITIONING LUBE PUMP 1.0
1310-MS-002-33 1310 CONDITIONING LUBE PUMP 1.0
1310-MS-002-34 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MS-002-35 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MS-002-36 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MS-002-37 1310 HIGH PRESSURE LUBE PUMP 1.0
1310-MS-002-38 1310 ACCUMULATOR CHARGE PUMP 1.0
1310-MS-002-39 1310 SAG MILL BRAKE CALIPER SYSTEM 1.0
1310-MS-002-40 1310 SAG MILL BRAKE SYSTEM OIL TANK 1.0
1310-MS-002-41 1310 SAG MILL BRAKE SYSTEM PUMP 1.0
1310-MS-002-53 1310 SAG MILL MOTOR COOLING SYSTEM 1.2
1310-MS-002-54 1310 SAG MILL MOTOR COOLING SYSTEM 1.2
1310-MS-002-55 1310 SAG MILL CYCLOCONVERTER COOLING SYSTEM 1.2
1310-MS-002-56 1310 BRAKE HYDRAULIC UNIT MANUAL RELEASE 1.2
1310-PP-019 1310 SAG MILL UNDERSIZE PUMP 1.2
1310-PP-020 1310 SAG MILL UNDERSIZE PUMP 1.2
1310-PP-021 1310 PRIMARY CYCLONE FEED PUMP 1.2
1310-PP-022 1310 PRIMARY CYCLONE FEED PUMP 1.2
1310-PP-023 1310 PRIMARY CYCLONE FEED PUMP 1.2
1310-PP-024 1310 PRIMARY CYCLONE FEED PUMP 1.2
1310-PP-025 1310 PRIMARY CYCLONE FEED PUMP 1.2
1310-PP-026 1310 PRIMARY CYCLONE FEED PUMP 1.2
1310-PP-689 1310 ELECTRIC ROOM ER-520 COOLING PUMP 1.0
1310-PP-690 1310 ELECTRIC ROOM ER-520 COOLING PUMP 1.0
1310-PP-691 1310 ELECTRIC ROOM ER-520 COOLING PUMP 1.0
1310-SA-096 1310 PRIMARY CYCLONE OVERFLOW PARTICLE SIZE ANALYZER 1.0
1310-SA-097 1310 PRIMARY CYCLONE OVERFLOW PARTICLE SIZE ANALYZER 1.0
1310-SA-098 1310 PRIMARY CYCLONE OVERFLOW PARTICLE SIZE ANALYZER 1.0
1310-SA-099 1310 PRIMARY CYCLONE OVERFLOW PARTICLE SIZE ANALYZER 1.0
1310-SA-100 1310 ROUGHER FEED IN STREAM PROBE ANALYZER 1.0
1310-SC-014 1310 SAG MILL VIBRATING SCREEN 1.2
1310-SC-015 1310 SAG MILL VIBRATING SCREEN 1.2
1310-SC-016 1310 SAG MILL VIBRATING SCREEN 1.2
1310-SL-043 1310 BALL MILL FEED BELT SCALE 1.0
1310-ST-001 1310 DIVERSION GATE BALL MILL 1.0
1310-ST-002 1310 DIVERSION GATE BALL MILL 1.0
1310-ST-003 1310 DIVERSION GATE BALL MILL 1.0
1310-ST-033 1310 SAG MILL BALL FEED DISCHARGE CHUTE 1.0
1310-ST-034 1310 SAG MILL BALL FEED DISCHARGE CHUTE 1.0
1310-ST-035 1310 BALL MILL BALL FEED DISCHARGE CHUTE 1.0
1310-ST-036 1310 BALL MILL BALL FEED DISCHARGE CHUTE 1.0
1310-ST-096 1310 CYCLONE OVERFLOW SAMPLER BOX 1.0
1310-ST-097 1310 CYCLONE OVERFLOW SAMPLER BOX 1.0
1310-ST-098 1310 CYCLONE OVERFLOW SAMPLER BOX 1.0
1310-ST-099 1310 CYCLONE OVERFLOW SAMPLER BOX 1.0
1310-ST-100 1310 ROUGHER FEED SAMPLER BOX 1.0
1310-ST-406 1310 UNDER SIZE CHUTE SCREEN DISCHARGE 1.0
1310-ST-407 1310 SAG MILL TROMMEL COVER 1.0
1310-ST-621 1310 BALL MILL BALL LOADING CHUTE 1.0
1310-ST-622 1310 BALL MILL BALL LOADING CHUTE 1.0
1310-ST-623 1310 BALL MILL BALL LOADING CHUTE 1.0
1310-ST-624 1310 BALL MILL BALL LOADING CHUTE 1.0
1310-ST-650 1310 SAG MILL DISCHARGE CHUTE 1.0
1310-ST-651 1310 SAG MILL TROMMEL UNDER SIZE CHUTE 1.0
1310-ST-652 1310 SAG PUMP DISCHARGE TRANSFER BOX 1.0
1310-ST-653 1310 SAG PUMP DISCHARGE TRANSFER BOX 1.0
1310-ST-654 1310 DI-176 DISTRIBUTOR DISCHARGE COLLECTOR BOX 1.0
1310-ST-655 1310 DI-176 DISTRIBUTOR DISCHARGE COLLECTOR BOX 1.0

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
35 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1310-ST-656 1310 DI-176 DISTRIBUTOR DISCHARGE COLLECTOR BOX 1.0
1310-ST-657 1310 DI-176 DISTRIBUTOR DISCHARGE COLLECTOR BOX 1.0
1310-ST-658 1310 BALL MILL FEED TRANSFER BOX 1.0
1310-ST-659 1310 BALL MILL FEED TRANSFER BOX 1.0
1310-ST-660 1310 BALL MILL FEED TRANSFER BOX 1.0
1310-ST-661 1310 BALL MILL FEED TRANSFER BOX 1.0
1310-ST-662 1310 BALL MILL DISCHARGE CHUTE 1.0
1310-ST-663 1310 BALL MILL DISCHARGE CHUTE 1.0
1310-ST-664 1310 BALL MILL DISCHARGE CHUTE 1.0
1310-ST-665 1310 BALL MILL DISCHARGE CHUTE 1.0
1310-ST-676 1310 CYCLONE FEED SUMP OVERFLOW BOX 1.0
1310-ST-677 1310 CYCLONE FEED SUMP OVERFLOW BOX 1.0
1310-ST-678 1310 CYCLONE FEED SUMP OVERFLOW BOX 1.0
1310-ST-679 1310 CYCLONE FEED SUMP OVERFLOW BOX 1.0
1310-ST-680 1310 CYCLONE FEED TRANSFER BOX 1.0
1310-ST-681 1310 CYCLONE FEED TRANSFER BOX 1.0
1310-ST-682 1310 CYCLONE FEED TRANSFER BOX 1.0
1310-ST-683 1310 CYCLONE FEED TRANSFER BOX 1.0
1310-ST-687 1310 DI-004 DISTRIBUTOR DISCHARGE COLLECTOR BOX 1.0
1310-ST-688 1310 DI-004 DISTRIBUTOR DISCHARGE COLLECTOR BOX 1.0
1310-ST-689 1310 DI-004 DISTRIBUTOR DISCHARGE COLLECTOR BOX 1.0
1310-ST-690 1310 DI-004 DISTRIBUTOR DISCHARGE COLLECTOR BOX 1.0
1310-ST-697 1310 CYCLONE SAMPLING POINT BOX 1.0
1310-ST-698 1310 CYCLONE SAMPLING POINT BOX 1.0
1310-ST-699 1310 CYCLONE SAMPLING POINT BOX 1.0
1310-ST-700 1310 CYCLONE SAMPLING POINT BOX 1.0
1310-ST-740 1310 DISCHARGE CHUTE CV-042 1.0
1310-ST-741 1310 DISCHARGE CHUTE CV-043 1.0
1310-ST-742 1310 BALL DISCHARGE CHUTE TO MB-05 1.0
1310-ST-743 1310 BALL DISCHARGE CHUTE TO MB-06 1.0
1310-ST-744 1310 BALL DISCHARGE CHUTE TO MB-07 1.0
1310-ST-745 1310 BALL DISCHARGE CHUTE TO MB-08 1.0
1310-ST-801 1310 PEBBLES CHUTE SCREEN DISCHARGE 1.0
1310-ST-802 1310 PRIMARY COLLECTOR FUNNEL 1.0
1310-ST-803 1310 MILK OF LIME FUNNEL 1.0
1310-ST-809 1310 SAG MILL SUMP OVERFLOW BOX 1.0
1310-SU-002 1310 SAG MILL UNDERSIZE SUMP 1.0
1310-SU-105 1310 PRIMARY CYCLONE FEED SUMP 1.0
1310-SU-106 1310 PRIMARY CYCLONE FEED SUMP 1.0
1310-SU-107 1310 PRIMARY CYCLONE FEED SUMP 1.0
1310-SU-108 1310 PRIMARY CYCLONE FEED SUMP 1.0
1310-SU-109 1310 EMERGENCY SPILLS RECEPTION BOX 1.0
1310-VS-018 1310 BACKUP AIR ACCUMULATOR, GRINDING AREA 1.0
1310-ZM-319 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-320 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-321 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-322 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-323 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-324 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-325 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-326 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-327 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-328 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-329 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-330 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-331 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-332 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-333 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-334 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-335 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-336 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-337 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-338 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-339 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-340 1310 GRINDING BUILDING AIR EXTRACTOR 1.0

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
36 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1310-ZM-341 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-342 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-343 1310 BALL MILL LUBRICATION ROOM LATTICE GRAVITATIONAL 1.0
1310-ZM-344 1310 BALL MILL LUBRICATION ROOM LATTICE GRAVITATIONAL 1.0
1310-ZM-345 1310 BALL MILL LUBRICATION ROOM LATTICE GRAVITATIONAL 1.0
1310-ZM-346 1310 BALL MILL LUBRICATION ROOM LATTICE GRAVITATIONAL 1.0
1310-ZM-347 1310 SAG MILL LUBRICATION ROOM LATTICE GRAVITATIONAL 1.0
1310-ZM-397 1310 GRINDING BUILDING AIR EXTRACTOR 1.0
1310-ZM-399 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-400 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-401 1310 BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-402 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-403 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-404 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-405 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-406 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-407 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-408 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-409 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-410 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-411 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-412 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-413 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-414 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-415 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-416 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-417 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1310-ZM-418 1310 FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1320-AG-043 1320 REGRIND CYCLONE FEED TANK AGITATOR 1.0
1320-AG-044 1320 REGRIND CYCLONE FEED TANK AGITATOR 1.0
1320-BL-050 1320 FLOTATION CELL BLOWER 1.0
1320-BL-051 1320 FLOTATION CELL BLOWER 1.0
1320-BL-052 1320 FLOTATION CELL BLOWER 1.0
1320-BL-053 1320 FLOTATION CELL BLOWER 1.0
1320-BL-054 1320 FLOTATION CELL BLOWER 1.0
1320-BL-055 1320 FLOTATION CELL BLOWER 1.0
1320-BN-036 1320 VERTICAL REGRIND MILL BALL STORAGE BIN 1.2
1320-CN-136 1320 ROUGHER FLOTATION BAY GANTRY CRANE "A" 1.2
1320-CN-137 1320 ROUGHER FLOTATION BAY GANTRY CRANE "B" 1.2
1320-CN-138 1320 SCAVENGER FLOTATION BAY GANTRY CRANE 1.2
1320-CN-139 1320 VERTICAL MILL AND COLUMN CELLS GANTRY CRANE 1.2
1320-CS-016 1320 REGRIND CYCLONE CLUSTER 1.2
1320-CS-017 1320 REGRIND CYCLONE CLUSTER 1.2
1320-CS-018 1320 REGRIND CYCLONE CLUSTER 1.2
1320-CV-038 1320 VERTICAL REGRIND MILL BALL FEED CONVEYOR No 1 1.2
1320-CV-039 1320 VERTICAL REGRIND MILL BALL FEED CONVEYOR No 2 1.2
1320-DI-014 1320 ROUGHER FEED DISTRIBUTOR 1.2
1320-DI-015 1320 SCAVENGER FEED DISTRIBUTOR 1.2
1320-DI-016 1320 ROUGHER CLEANER COLUMNS FEED DISTRIBUTOR 1.0
1320-DI-017 1320 REGRIND CYCLONE UNDERFLOW DISTRIBUTOR 1.0
1320-DI-019 1320 SCAVENGER CLEANER COLUMNS FEED DISTRIBUTOR 1.0
1320-FA-012 1320 PACKAGED UNITARY COOLING ROOFTOP FOR ELECTRICAL ROOM ER-523 1.0
1320-FA-023 1320 PACKAGED UNITARY COOLING ROOFTOP FOR ELECTRICAL ROOM ER-523 1.0
1320-FA-027 1320 FAN PRESSURIZATION FOR ELECTRICAL ROOM ER-523 1.0
1320-FA-028 1320 FAN PRESSURIZATION FOR ELECTRICAL ROOM ER-523 1.0
1320-FE-035 1320 VERTICAL REGRIND MILL ROTARY BALL FEEDER 1.0
1320-FT-400 1320 SCAVENGER FLOTATION CELL MACHINE BANK A 1.2
1320-FT-400-02 1320 SCAVENGER FLOTATION CELLS FEEDING BOX BANK A 1.2
1320-FT-401 1320 SCAVENGER FLOTATION CELL MACHINE BANK A 1.2
1320-FT-402 1320 SCAVENGER FLOTATION CELL MACHINE BANK A 1.2
1320-FT-403 1320 SCAVENGER FLOTATION CELL MACHINE BANK A 1.2
1320-FT-404 1320 SCAVENGER FLOTATION CELL MACHINE BANK A 1.2
1320-FT-405 1320 SCAVENGER FLOTATION CELL MACHINE BANK A 1.2
1320-FT-406 1320 SCAVENGER FLOTATION CELL MACHINE BANK A 1.2
1320-FT-410 1320 SCAVENGER FLOTATION CELL MACHINE BANK B 1.2

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
37 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1320-FT-410-02 1320 SCAVENGER FLOTATION CELL FEEDING BOX BANK B 1.2
1320-FT-411 1320 SCAVENGER FLOTATION CELL MACHINE BANK B 1.2
1320-FT-412 1320 SCAVENGER FLOTATION CELL MACHINE BANK B 1.2
1320-FT-413 1320 SCAVENGER FLOTATION CELL MACHINE BANK B 1.2
1320-FT-414 1320 SCAVENGER FLOTATION CELL MACHINE BANK B 1.2
1320-FT-415 1320 SCAVENGER FLOTATION CELL MACHINE BANK B 1.2
1320-FT-416 1320 SCAVENGER FLOTATION CELL MACHINE BANK B 1.2
1320-FT-440 1320 ROUGHER FLOTATION CELL BANK A 1.2
1320-FT-440-02 1320 ROUGHER FLOTATION CELL FEEDING BOX BANK A 1.2
1320-FT-441 1320 ROUGHER FLOTATION CELL BANK A 1.2
1320-FT-442 1320 ROUGHER FLOTATION CELL BANK A 1.2
1320-FT-443 1320 ROUGHER FLOTATION CELL BANK A 1.2
1320-FT-444 1320 ROUGHER FLOTATION CELL BANK A 1.2
1320-FT-445 1320 ROUGHER FLOTATION CELL BANK A 1.2
1320-FT-446 1320 ROUGHER FLOTATION CELL BANK A 1.2
1320-FT-450 1320 ROUGHER FLOTATION CELL BANK B 1.2
1320-FT-450-02 1320 ROUGHER FLOTATION CELL FEEDING BOX BANK B 1.2
1320-FT-451 1320 ROUGHER FLOTATION CELL BANK B 1.2
1320-FT-452 1320 ROUGHER FLOTATION CELL BANK B 1.2
1320-FT-453 1320 ROUGHER FLOTATION CELL BANK B 1.2
1320-FT-454 1320 ROUGHER FLOTATION CELL BANK B 1.2
1320-FT-455 1320 ROUGHER FLOTATION CELL BANK B 1.2
1320-FT-456 1320 ROUGHER FLOTATION CELL BANK B 1.2
1320-FT-460 1320 ROUGHER FLOTATION CELL BANK C 1.2
1320-FT-460-02 1320 ROUGHER FLOTATION CELL FEEDING BOX BANK C 1.2
1320-FT-461 1320 ROUGHER FLOTATION CELL BANK C 1.2
1320-FT-462 1320 ROUGHER FLOTATION CELL BANK C 1.2
1320-FT-463 1320 ROUGHER FLOTATION CELL BANK C 1.2
1320-FT-464 1320 ROUGHER FLOTATION CELL BANK C 1.2
1320-FT-465 1320 ROUGHER FLOTATION CELL BANK C 1.2
1320-FT-466 1320 ROUGHER FLOTATION CELL BANK C 1.2
1320-FT-470 1320 ROUGHER FLOTATION CELL BANK D 1.2
1320-FT-470-02 1320 ROUGHER FLOTATION CELL FEEDING BOX BANK D 1.2
1320-FT-471 1320 ROUGHER FLOTATION CELL BANK D 1.2
1320-FT-472 1320 ROUGHER FLOTATION CELL BANK D 1.2
1320-FT-473 1320 ROUGHER FLOTATION CELL BANK D 1.2
1320-FT-474 1320 ROUGHER FLOTATION CELL BANK D 1.2
1320-FT-475 1320 ROUGHER FLOTATION CELL BANK D 1.2
1320-FT-476 1320 ROUGHER FLOTATION CELL BANK D 1.2
1320-FT-480 1320 ROUGHER FLOTATION CELL BANK E 1.2
1320-FT-480-02 1320 ROUGHER FLOTATION CELL FEEDING BOX BANK E 1.2
1320-FT-481 1320 ROUGHER FLOTATION CELL BANK E 1.2
1320-FT-482 1320 ROUGHER FLOTATION CELL BANK E 1.2
1320-FT-483 1320 ROUGHER FLOTATION CELL BANK E 1.2
1320-FT-484 1320 ROUGHER FLOTATION CELL BANK E 1.2
1320-FT-485 1320 ROUGHER FLOTATION CELL BANK E 1.2
1320-FT-486 1320 ROUGHER FLOTATION CELL BANK E 1.2
1320-FT-490 1320 ROUGHER FLOTATION CELL BANK F 1.2
1320-FT-490-02 1320 ROUGHER FLOTATION CELL FEEDING BOX BANK F 1.2
1320-FT-491 1320 ROUGHER FLOTATION CELL BANK F 1.2
1320-FT-492 1320 ROUGHER FLOTATION CELL BANK F 1.2
1320-FT-493 1320 ROUGHER FLOTATION CELL BANK F 1.2
1320-FT-494 1320 ROUGHER FLOTATION CELL BANK F 1.2
1320-FT-495 1320 ROUGHER FLOTATION CELL BANK F 1.2
1320-FT-496 1320 ROUGHER FLOTATION CELL BANK F 1.2
1320-FT-500 1320 SECOND CLEANER COLUMN CELL 1.2
1320-FT-501 1320 SECOND CLEANER COLUMN CELL 1.2
1320-FT-502 1320 SECOND CLEANER COLUMN CELL 1.2
1320-FT-503 1320 SECOND CLEANER COLUMN CELL 1.2
1320-FT-504 1320 SECOND CLEANER COLUMN CELL 1.2
1320-FT-505 1320 SECOND CLEANER COLUMN CELL 1.2
1320-FT-506 1320 SECOND CLEANER COLUMN CELL 1.2
1320-FT-507 1320 SECOND CLEANER COLUMN CELL 1.2
1320-FT-508 1320 SECOND CLEANER COLUMN CELL 1.2
1320-FT-509 1320 SECOND CLEANER COLUMN CELL 1.2

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
38 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1320-FT-510 1320 SECOND CLEANER COLUMN CELL 1.2
1320-FT-511 1320 SECOND CLEANER COLUMN CELL 1.2
1320-FT-520 1320 ROUGHER FLOTATION CELL BANK G 1.2
1320-FT-520-02 1320 ROUGHER FLOTATION CELL FEEDING BOX BANK G 1.2
1320-FT-521 1320 ROUGHER FLOTATION CELL BANK G 1.2
1320-FT-522 1320 ROUGHER FLOTATION CELL BANK G 1.2
1320-FT-523 1320 ROUGHER FLOTATION CELL BANK G 1.2
1320-FT-524 1320 ROUGHER FLOTATION CELL BANK G 1.2
1320-FT-525 1320 ROUGHER FLOTATION CELL BANK G 1.2
1320-FT-526 1320 ROUGHER FLOTATION CELL BANK G 1.2
1320-FT-530 1320 SCAVENGER FLOTATION CELL MACHINE BANK C 1.2
1320-FT-530-02 1320 SCAVENGER FLOTATION CELL FEEDING BOX BANK C 1.2
1320-FT-531 1320 SCAVENGER FLOTATION CELL MACHINE BANK C 1.2
1320-FT-532 1320 SCAVENGER FLOTATION CELL MACHINE BANK C 1.2
1320-FT-533 1320 SCAVENGER FLOTATION CELL MACHINE BANK C 1.2
1320-FT-534 1320 SCAVENGER FLOTATION CELL MACHINE BANK C 1.2
1320-FT-535 1320 SCAVENGER FLOTATION CELL MACHINE BANK C 1.2
1320-FT-536 1320 SCAVENGER FLOTATION CELL MACHINE BANK C 1.2
1320-HU-134 1320 VALVE HYDRAULIC UNIT 1.0
1320-HU-135 1320 VALVE HYDRAULIC UNIT 1.0
1320-HU-136 1320 VALVE HYDRAULIC UNIT 1.0
1320-HU-137 1320 VALVE HYDRAULIC UNIT 1.0
1320-LA-055 1320 ROUGHER CONCENTRATE DISCHARGE LAUNDER BANK A 1.0
1320-LA-056 1320 ROUGHER CONCENTRATE DISCHARGE LAUNDER BANK B 1.0
1320-LA-057 1320 ROUGHER CONCENTRATE DISCHARGE LAUNDER BANK C 1.0
1320-LA-058 1320 ROUGHER CONCENTRATE DISCHARGE LAUNDER BANK D 1.0
1320-LA-059 1320 ROUGHER CONCENTRATE DISCHARGE LAUNDER BANK E 1.0
1320-LA-060 1320 ROUGHER CONCENTRATE DISCHARGE LAUNDER BANK F 1.0
1320-LA-061 1320 TAILINGS DISCHARGE LAUNDER BANKS A THROUGH F 1.0
1320-LA-062 1320 TAILINGS DISCHARGE LAUNDER BANK A 1.0
1320-LA-063 1320 TAILINGS DISCHARGE LAUNDER BANK B 1.0
1320-LA-064 1320 TAILINGS DISCHARGE LAUNDER BANK C 1.0
1320-LA-065 1320 TAILINGS DISCHARGE LAUNDER BANK D 1.0
1320-LA-066 1320 TAILINGS DISCHARGE LAUNDER BANK E 1.0
1320-LA-067 1320 TAILINGS DISCHARGE LAUNDER BANK F 1.0
1320-LA-068 1320 CONCENTRATE DISCHARGE LAUNDER BANKS A @ F 1.0
1320-LA-069 1320 SCAVENGER CONCENTRATE DISCHARGE LAUNDER BANK A 1.0
1320-LA-070 1320 SCAVENGER CONCENTRATE DISCHARGE LAUNDER BANK B 1.0
1320-LA-079 1320 SCAVENGER TAILINGS DISCHARGE LAUNDER BANK A & B 1.0
1320-LA-080 1320 ROUGHER CONCENTRATE DISCHARGE LAUNDER BANK G 1.0
1320-LA-081 1320 TAILINGS DISCHARGE LAUNDER BANK G 1.0
1320-LA-083 1320 ROUGHER CONCENTRATE DISCHARGE LAUNDER BANKS A@C & G 1.0
1320-LA-084 1320 ROUGHER CONCENTRATE DISCHARGE LAUNDER BANKS D@F 1.0
1320-LA-085 1320 SCAVENGER CONCENTRATE DISCHARGE LAUNDER BANKS A@B 1.0
1320-LA-086 1320 SCAVENGER DISCHARGE LAUNDER BANKS A@B 1.0
1320-LA-093 1320 SCAVENGER CONCENTRATE DISCHARGE LAUNDER BANK C 1.0
1320-MT-015 1320 VERTICAL REGRIND MILL 1.2
1320-MT-015-01 1320 LUBRICATION SYSTEM FOR VERTIMILL 1.0
1320-MT-015-02 1320 RECYCLE PUMP FOR VERTIMILL 1.0
1320-MT-015-03 1320 SEPARATING TANK 1.0
1320-MT-015-04 1320 SCREW TRANSPORTER CART 1.0
1320-MT-016 1320 VERTICAL REGRIND MILL 1.2
1320-MT-016-01 1320 LUBRICATION SYSTEM FOR VERTIMILL 1.0
1320-MT-016-02 1320 RECYCLE PUMP FOR VERTIMILL 1.0
1320-MT-016-03 1320 SEPARATING TANK 1.0
1320-MT-017 1320 VERTICAL REGRIND MILL 1.2
1320-MT-017-01 1320 LUBRICATION SYSTEM FOR VERTIMILL 1.0
1320-MT-017-02 1320 RECYCLE PUMP FOR VERTIMILL 1.0
1320-MT-017-03 1320 SEPARATING TANK 1.0
1320-PP-045 1320 ROUGHER CONCENTRATE SAMPLER PUMP 1.0
1320-PP-131 1320 ROUGHER CLEANER COLUMNS FEED PUMP 1.2
1320-PP-132 1320 ROUGHER CLEANER COLUMNS FEED PUMP 1.2
1320-PP-136 1320 SCAVENGER CLEANER COLUMNS FEED PUMP 1.2
1320-PP-137 1320 SCAVENGER CLEANER COLUMNS FEED PUMP 1.2
1320-PP-313 1320 COLUMN CELL RECIRCULATION PUMP 1.0

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
39 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1320-PP-314 1320 COLUMN CELL RECIRCULATION PUMP 1.0
1320-PP-317 1320 COLUMN CELL RECIRCULATION PUMP 1.0
1320-PP-318 1320 COLUMN CELL RECIRCULATION PUMP 1.0
1320-PP-319 1320 COLUMN CELL RECIRCULATION PUMP 1.0
1320-PP-320 1320 COLUMN CELL RECIRCULATION PUMP 1.0
1320-PP-321 1320 COLUMN CELL RECIRCULATION PUMP 1.0
1320-PP-322 1320 COLUMN CELL RECIRCULATION PUMP 1.0
1320-PP-323 1320 COLUMN CELL RECIRCULATION PUMP 1.0
1320-PP-324 1320 COLUMN CELL RECIRCULATION PUMP 1.0
1320-PP-325 1320 COLUMN CELL RECIRCULATION PUMP 1.0
1320-PP-326 1320 COLUMN CELL RECIRCULATION PUMP 1.0
1320-PP-350 1320 REGRIND CYCLONE FEED PUMP 1.0
1320-PP-351 1320 REGRIND CYCLONE FEED PUMP 1.0
1320-PP-352 1320 REGRIND CYCLONE FEED PUMP 1.0
1320-PP-353 1320 SCAVENGER FEED PUMP 1.0
1320-PP-354 1320 SCAVENGER FEED PUMP 1.0
1320-PP-355 1320 SCAVENGER FEED PUMP 1.0
1320-SA-301 1320 ROUGHER TAILINGS IN-STREAM PROBE ANALYZER BANK B 1.0
1320-SA-302 1320 ROUGHER TAILINGS IN-STREAM PROBE ANALYZER BANK A 1.0
1320-SA-303 1320 ROUGHER TAILINGS IN-STREAM PROBE ANALYZER BANK D 1.0
1320-SA-304 1320 ROUGHER TAILINGS IN-STREAM PROBE ANALYZER BANK C 1.0
1320-SA-305 1320 ROUGHER TAILINGS IN-STREAM PROBE ANALYZER BANK F 1.0
1320-SA-306 1320 ROUGHER TAILINGS IN-STREAM PROBE ANALYZER BANK E 1.0
1320-SA-307 1320 ROUGHER TAILINGS IN-STREAM PROBE ANALYZER BANK G 1.0
1320-SA-322 1320 ROUGHER CLEANER FEED PRIMARY SAMPLER 1.0
1320-SA-323 1320 ROUGHER CLEANER FEED PRIMARY SAMPLER 1.0
1320-SA-324 1320 ROUGHER CLEANER FEED IN-STREAM PROBE ANALYZER 1.0
1320-SA-325 1320 ROUGHER CONCENTRATE IN-STREAM PROBE ANALYZER 1.0
1320-SA-326 1320 ROUGHER TAILINGS IN-STREAM PROBE ANALYZER 1.0
1320-SA-327 1320 SCAVENGER CLEANER FEED PRIMARY SAMPLER 1.0
1320-SA-328 1320 SCAVENGER CLEANER FEED PRIMARY SAMPLER 1.0
1320-SA-329 1320 SCAVENGER CLEANER FEED IN-STREAM PROBE ANALYZER 1.0
1320-SA-330 1320 SCAVENGER CLEANER TAILINGS IN STREAM PROBE ANALYZER 1.0
1320-SA-331 1320 SCAVENGER CLEANER CONCENTRATE IN-STREAM PROBE ANALYZER 1.0
1320-SA-332 1320 SCAVENGER FEED PRIMARY SAMPLER PRESSURE PIPE 1.0
1320-SA-333 1320 SCAVENGER FEED PRIMARY SAMPLER PRESSURE PIPE 1.0
1320-SA-334 1320 SCAVENGER FEED IN-STREAM PROBE ANALYZER 1.0
1320-SA-336 1320 SECOND CLEANER CONCENTRATE PARTICLE SIZE ANALYZER 1.0
1320-SA-337 1320 REGRIND CYCLONE OVERFLOW PARTICLE SIZE ANALYZER 1.0
1320-SA-338 1320 ROUGHER CLEANER CONCENTRATE IN-STREAM PROBE ANALYZER 1.0
1320-SA-339 1320 SCAVENGER FEED PRIMARY SAMPLER PRESSURE PIPE 1.0
1320-SA-342 1320 ROUGHER CLEANER TAILINGS IN-STREAM PROBE ANALYZER 1.0
1320-SA-343 1320 SCAVENGER CLEANER TAILINGS IN-STREAM PROBE ANALYZER 1.0
1320-SL-042 1320 VERTICAL REGRIND MILL FEED BELT SCALE 1.0
1320-ST-019 1320 VERTICAL REGRIND MILLS BALL FEED DISCHARGE CHUTE 1.0
1320-ST-020 1320 VERTICAL REGRIND MILL MT-015 BALL FEED DISCHARGE CHUTE 1.0
1320-ST-021 1320 VERTICAL REGRIND MILL MT-016 BALL FEED DISCHARGE CHUTE 1.0
1320-ST-022 1320 VERTICAL REGRIND MILL MT-017 BALL FEED DISCHARGE CHUTE 1.0
1320-ST-050 1320 DIVERSION GATE BALLS VERTICAL REGRIND MILL 1.0
1320-ST-051 1320 DIVERSION GATE BALLS VERTICAL REGRIND MILL 1.0
1320-ST-052 1320 DISCHARGE DUCT ROUGHER CONCENTRATE BANKS A@C & G 1.0
1320-ST-053 1320 DISCHARGE DUCT ROUGHER CONCENTRATE BANKS D@F 1.0
1320-ST-055 1320 DISCHARGE DUCT SCAVENGER CONCENTRATE BANKS A & B 1.0
1320-ST-301 1320 ROUGHER TAILINGS SAMPLER BOX BANK B 1.0
1320-ST-302 1320 ROUGHER TAILINGS SAMPLER BOX BANK A 1.0
1320-ST-303 1320 ROUGHER TAILINGS SAMPLER BOX BANK D 1.0
1320-ST-304 1320 ROUGHER TAILINGS SAMPLER BOX BANK C 1.0
1320-ST-305 1320 ROUGHER TAILINGS SAMPLER BOX BANK F 1.0
1320-ST-306 1320 ROUGHER TAILINGS SAMPLER BOX BANK E 1.0
1320-ST-307 1320 ROUGHER TAILINGS SAMPLER BOX BANK G 1.0
1320-ST-324 1320 ROUGHER CLEANER FEED SAMPLER COLLECTION BOX 1.0
1320-ST-325 1320 ROUGHER CONCENTRATE SAMPLER BOX 1.0
1320-ST-326 1320 ROUGHER TAILINGS SAMPLER BOX 1.0
1320-ST-329 1320 SCAVENGER CLEANER FEED SAMPLER COLLECTION BOX 1.0
1320-ST-330 1320 SCAVENGER CLEANER TAILINGS SAMPLER BOX 1.0

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
40 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1320-ST-331 1320 SCAVENGER CLEANER CONCENTRATE SAMPLER BOX 1.0
1320-ST-334 1320 SCAVENGER FEED SAMPLING COLLECTION BOX 1.0
1320-ST-337 1320 CYCLONE OVERFLOW SAMPLER BOX 1.0
1320-ST-338 1320 ROUGHER CLEANER CONCENTRATE SAMPLER BOX 1.0
1320-ST-342 1320 ROUGHER CLEANER TAILINGS SAMPLER BOX 1.0
1320-ST-343 1320 SCAVENGER CLEANER TAILINGS SAMPLER BOX 1.0
1320-ST-666 1320 DISCHARGE DUCT ROUGHER CONCENTRATE BANK A 1.0
1320-ST-667 1320 DISCHARGE DUCT ROUGHER CONCENTRATE BANK B 1.0
1320-ST-668 1320 DISCHARGE DUCT ROUGHER CONCENTRATE BANK C 1.0
1320-ST-669 1320 DISCHARGE DUCT ROUGHER CONCENTRATE BANK D 1.0
1320-ST-670 1320 DISCHARGE DUCT ROUGHER CONCENTRATE BANK E 1.0
1320-ST-671 1320 DISCHARGE DUCT ROUGHER CONCENTRATE BANK F 1.0
1320-ST-672 1320 DISCHARGE DUCT SCAVENGER CONCENTRATE BANK A 1.0
1320-ST-673 1320 DISCHARGE DUCT SCAVENGER CONCENTRATE BANK B 1.0
1320-ST-686 1320 DISCHARGE DUCT ROUGHER CONCENTRATE BANK G 1.0
1320-ST-691 1320 BALL FEED CHUTE FOR MT-015 1.0
1320-ST-692 1320 OIL SPILL TRAY FOR MT-015 1.0
1320-ST-693 1320 BALL FEED CHUTE FOR MT-016 1.0
1320-ST-694 1320 OIL SPILL TRAY FOR MT-016 1.0
1320-ST-695 1320 BALL FEED CHUTE FOR MT-017 1.0
1320-ST-696 1320 OIL SPILL TRAY FOR MT-017 1.0
1320-ST-707 1320 VERTICAL REGRIND MILL BALL DISCHARGE CHUTE 1.0
1320-ST-707-01 1320 GATE HYDRAULIC UNIT 1.0
1320-ST-709 1320 REGRIND CYCLONE SAMPLING POINT BOX 1.0
1320-ST-710 1320 REGRIND CYCLONE SAMPLING POINT BOX 1.0
1320-ST-711 1320 REGRIND CYCLONE SAMPLING POINT BOX 1.0
1320-ST-752 1320 DISCHARGE DUCT SCAVENGER CONCENTRATE BANK C 1.2
1320-SU-009 1320 SCAVENGER DISCHARGE TANK BANKS A & B 1.2
1320-SU-016 1320 FLOTATION'S SUMP 1.0
1320-SU-017 1320 CONCENTRATE DISCHARGE TANK BANKS A @ F 1.2
1320-TK-040 1320 ROUGHER CLEANER COLUMN FEED TANK 1.2
1320-TK-043 1320 SCAVENGER CLEANER COLUMN FEED TANK 1.2
1320-TK-044 1320 REGRIND CYCLONE FEED TANK 1.0
1320-TK-045 1320 SCAVENGER FEED TANK 1.0
1320-VS-017 1320 BACKUO AIR ACCUMULATOR, FLOTATION AREA 1.0
1320-ZM-373 1320 HVAC FIXED LOUVERS AND RELIEF DAMPER 1.0
1320-ZM-374 1320 HVAC FIXED LOUVERS AND RELIEF DAMPER 1.0
1320-ZM-419 1320 BACKDRAFT RELIEF DAMPER 1.0
1320-ZM-420 1320 BACKDRAFT RELIEF DAMPER 1.0
1330-BN-004 1330 PEBBLE SURGE BIN 1.2
1330-BN-005 1330 PEBBLE SURGE BIN EMERGENCY 1.2
1330-BN-058 1330 SCRAP HOPPER MAGNET 1.0
1330-BN-059 1330 SCRAP HOPPER MAGNET 1.0
1330-CN-023 1330 PEBBLE CRUSHER BRIDGE CRANE 1.2
1330-CR-005 1330 PEBBLE CRUSHER 1.2
1330-CR-005-01 1330 CRUSHER HYDRAULIC UNIT 1.0
1330-CR-005-02 1330 CRUSHER LUBRICATION SYSTEM 1.0
1330-CR-005-03 1330 DUST SEAL BLOWER 1.0
1330-CR-005-04 1330 CRUSHER DRIVE SYSTEM 1.0
1330-CR-005-06 1330 CRUSHER COOLING SYSTEM 1.0
1330-CR-005-08 1330 CRUSHER SUB-BASE 1.0
1330-CR-005-21 1330 CRUSHER LUBRICATION SYSTEM PUMP 1.0
1330-CR-005-22 1330 CRUSHER LUBRICATION SYSTEM PUMP 1.0
1330-CR-005-61 1330 CRUSHER COOLING SYSTEM FAN 1.0
1330-CR-005-62 1330 CRUSHER COOLING SYSTEM FAN 1.0
1330-CR-006 1330 PEBBLE CRUSHER 1.2
1330-CR-006-01 1330 CRUSHER HYDRAULIC UNIT 1.0
1330-CR-006-02 1330 CRUSHER LUBRICATION SYSTEM 1.0
1330-CR-006-03 1330 DUST SEAL BLOWER 1.0
1330-CR-006-04 1330 CRUSHER DRIVE SYSTEM 1.0
1330-CR-006-06 1330 CRUSHER COOLING SYSTEM 1.0
1330-CR-006-08 1330 CRUSHER SUB-BASE 1.0
1330-CR-006-21 1330 CRUSHER LUBRICATION SYSTEM PUMP 1.0
1330-CR-006-22 1330 CRUSHER LUBRICATION SYSTEM PUMP 1.0
1330-CR-006-61 1330 CRUSHER COOLING SYSTEM FAN 1.0

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
41 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1330-CR-006-62 1330 CRUSHER COOLING SYSTEM FAN 1.0
1330-CV-201 1330 DISCHARGE SCREEN BELT CONVEYOR 1.0
1330-CV-202 1330 PEBBLES FEED SURGE BIN BELT CONVEYOR 1.0
1330-CV-203 1330 PEBBLES FEED SURGE BIN BELT CONVEYOR 1.0
1330-CV-206 1330 DISCHARGE PEBBLE CRUSHER BELT CONVEYOR 1.0
1330-DC-052 1330 CRUSHERS DISCHARGE DUST COLLECTOR 1.0
1330-EL-007 1330 FREIGHT ELEVATOR PEBBLE CRUSHER BUILDING 1.2
1330-FE-204 1330 DISCHARGE PEBBLE BIN BELT FEEDER 1.0
1330-FE-205 1330 DISCHARGE PEBBLE BIN BELT FEEDER 1.0
1330-FE-207 1330 DISCHARGE PEBBLE SURGE BIN EMERGENCY BELT FEEDER 1.0
1330-HU-142 1330 LANCES HYDRAULIC UNIT 1.0
1330-MA-201 1330 TRAMP IRON MAGNET 1.0
1330-MA-202 1330 TRAMP IRON MAGNET 1.0
1330-MA-204 1330 TRAMP IRON MAGNET 1.0
1330-MA-205 1330 TRAMP IRON MAGNET 1.0
1330-MA-215 1330 TRAMP IRON MAGNET 1.0
1330-SL-201 1330 OVERSIZE SCREEN BELT SCALE 1.0
1330-SL-206 1330 PEBBLE RETURN BELT SCALE 1.0
1330-ST-572 1330 CONVEYOR CV-201 FEED CHUTE 1.0
1330-ST-573 1330 CV-201 CONVEYOR SKIRTBOARD 1.0
1330-ST-574 1330 CONVEYOR CV-201 DISCHARGE CHUTE 1.0
1330-ST-575 1330 MOVILE CHUTE FEED PEBBLE SURGE BIN 1.0
1330-ST-576 1330 CV-202 CONVEYOR SKIRTBOARD 1.0
1330-ST-577 1330 CONVEYOR CV-202 DISCHARGE CHUTE 1.0
1330-ST-578 1330 CONVEYOR CV-203 DISCHARGE CHUTE 1.0
1330-ST-579 1330 CV-203 CONVEYOR SKIRTBOARD 1.0
1330-ST-580 1330 SILO DISCHARGE CHUTE TO FE-204 1.0
1330-ST-584 1330 SILO DISCHARGE CHUTE TO FE-205 1.0
1330-ST-585 1330 BIN EMERGENCY DISCHARGE CHUTE TO FE-207 1.0
1330-ST-586 1330 CONVEYOR CV-206 DISCHARGE CHUTE 1.0
1330-ST-588 1330 BELT FEEDER FE-204 DISCHARGE CHUTE 1.0
1330-ST-590 1330 BELT FEEDER FE-205 DISCHARGE CHUTE 1.0
1330-ST-591 1330 BELT FEEDER FE-207 DISCHARGE CHUTE 1.0
1330-ST-594 1330 PEBBLE CRUSHER FEED CHUTE 1.0
1330-ST-595 1330 PEBBLE CRUSHER FEED CHUTE 1.0
1330-ST-596 1330 PEBBLE CRUSHER DISCHARGE CHUTE 1.0
1330-ST-598 1330 PEBBLE CRUSHER DISCHARGE CHUTE 1.0
1330-ST-604 1330 EMERGENCY CHUTE 1.0
1330-ST-702 1330 SCRAP MAGNET BOX 1.0
1330-ST-703 1330 SCRAP MAGNET BOX 1.0
1330-ST-804 1330 LANCES STORAGE RACK - ST-804 1.2
1330-ST-805 1330 LANCES STORAGE RACK - ST-805 1.2
1330-ST-806 1330 LANCES STORAGE RACK - ST-806 1.2
1330-ZM-031 1330 SCANNER 1.0
1340-CH-120 1340 THICKENER'S MECHANISM MAINTENANCE HOIST 1.0
1340-CH-121 1340 THICKENER'S MECHANISM MAINTENANCE HOIST 1.0
1340-CH-122 1340 CLARIFIER'S MECHANISM MAINTENANCE HOIST 1.0
1340-CH-123 1340 CLARIFIER'S MECHANISM TUNNEL MAINTENANCE CAR 1.0
1340-CH-124 1340 THICKENER'S MECHANISM TUNNEL MAINTENANCE CAR 1.0
1340-CH-125 1340 THICKENER'S MECHANISM TUNNEL MAINTENANCE CAR 1.0
1340-DI-106 1340 CONCENTRATE THICKENER TANK DISTRIBUTOR 1.2
1340-PP-057 1340 CONCENTRATE THICKENER UNDERFLOW PUMP 1.2
1340-PP-058 1340 CONCENTRATE THICKENER UNDERFLOW PUMP 1.2
1340-PP-059 1340 CONCENTRATE THICKENER UNDERFLOW PUMP 1.2
1340-PP-060 1340 CONCENTRATE THICKENER UNDERFLOW PUMP 1.2
1340-PP-061 1340 CLARIFIER UNDERFLOW PUMP 1.2
1340-PP-062 1340 CLARIFIER UNDERFLOW PUMP 1.2
1340-SU-701 1340 CLARIFIER THICKENER FEED BOX 1.2
1340-TK-027 1340 CONCENTRATE THICKENER 1.2
1340-TK-028 1340 CONCENTRATE THICKENER 1.2
1340-TK-029 1340 CLARIFIER THICKENER 1.2
1340-TM-027 1340 CONCENTRATE THICKENER MECHANISM 1.2
1340-TM-028 1340 CONCENTRATE THICKENER MECHANISM 1.2
1340-TM-029 1340 CLARIFIER THICKENER MECHANISM 1.0
1350-AG-201 1350 FLOTATION EMERGENCY TANK AGITATOR 1.0

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
42 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1350-AG-202 1350 FLOTATION EMERGENCY TANK AGITATOR 1.0
1350-CH-126 1350 TAILINGS THICKENER'S MECHANISM MAINTENANCE HOIST 1.0
1350-CH-127 1350 TAILINGS THICKENER'S MECHANISM MAINTENANCE HOIST 1.0
1350-CH-128 1350 TAILINGS THICKENER'S MECHANISM MAINTENANCE HOIST 1.0
1350-CH-129 1350 TAILINGS THICKENER'S MECHANISM TUNNEL MAINTENANCE CAR 1.0
1350-CH-130 1350 TAILINGS THICKENER'S MECHANISM TUNNEL MAINTENANCE CAR 1.0
1350-CH-131 1350 TAILINGS THICKENER'S MECHANISM TUNNEL MAINTENANCE CAR 1.0
1350-DI-151 1350 TAILINGS THICKENER DISTRIBUTOR 1.2
1350-DI-152 1350 THICKENER OVERFLOW TANK DISTRIBUTOR 1.0
1350-HU-139 1350 VALVE HYDRAULIC UNIT 1.0
1350-HU-140 1350 VALVE HYDRAULIC UNIT 1.0
1350-HU-141 1350 VALVE HYDRAULIC UNIT 1.0
1350-HU-145 1350 VALVE HYDRAULIC UNIT 1.0
1350-LA-019 1350 TAILINGS COLLECTING LAUNDER 1.0
1350-LA-020 1350 TAILINGS COLLECTING LAUNDER 1.0
1350-LA-077 1350 LAUNDER OVERFLOW THICKENER TANK 1.0
1350-LA-078 1350 LAUNDER OVERFLOW THICKENER TANK 1.0
1350-LA-089 1350 TAILINGS THICKENER DISCHARGE LAUNDER 1.0
1350-LA-090 1350 TAILINGS THICKENER DISCHARGE LAUNDER 1.0
1350-LA-091 1350 TAILINGS THICKENER DISCHARGE LAUNDER 1.0
1350-PP-360 1350 TAILING THICKENERS BY-PASS PUMP 1.0
1350-PP-363 1350 RECLAIM WATER PUMP 1.0
1350-PP-364 1350 RECLAIM WATER PUMP 1.0
1350-PP-365 1350 RECLAIM WATER PUMP 1.0
1350-PP-366 1350 RECLAIM WATER PUMP 1.0
1350-PP-367 1350 RECLAIM WATER PUMP 1.0
1350-PP-368 1350 RECLAIM WATER PUMP 1.0
1350-PP-369 1350 RECLAIM WATER PUMP 1.0
1350-PP-370 1350 ANTISCALANT METERING PUMP 1.0
1350-PP-371 1350 ANTISCALANT METERING PUMP 1.0
1350-PP-391 1350 FLOTATION AREA DRAINS SUMP PUMP 1.0
1350-PP-392 1350 FLOTATION AREA DRAINS SUMP PUMP 1.0
1350-SA-335 1350 FINAL TAILING IN STREAM PROBE ANALYZER 1.0
1350-ST-101 1350 TAILINGS THICKENER DISTRIBUTOR DISCHARGE GATE 1.0
1350-ST-102 1350 TAILINGS THICKENER DISTRIBUTOR DISCHARGE GATE 1.0
1350-ST-103 1350 TAILINGS THICKENER DISTRIBUTOR DISCHARGE GATE 1.0
1350-ST-104 1350 TAILINGS THICKENER DISTRIBUTOR BY-PASS GATE 1.0
1350-ST-335 1350 FINAL TAILINGS SAMPLER BOX 1.0
1350-ST-684 1350 THICKENER OVERFLOW TANK GATE 1.0
1350-ST-685 1350 THICKENER OVERFLOW TANK GATE 1.0
1350-ST-746 1350 ORIFICE PLATE BOX 1.0
1350-ST-747 1350 ORIFICE PLATE BOX 1.0
1350-ST-748 1350 ORIFICE PLATE BOX 1.0
1350-ST-749 1350 ORIFICE PLATE BOX 1.0
1350-ST-750 1350 ORIFICE PLATE BOX 1.0
1350-ST-751 1350 ORIFICE PLATE BOX 1.0
1350-SU-018 1350 TAILINGS FINAL TANK 1.0
1350-SU-025 1350 TAILINGS THICKENER DISCHARGE SUMP 1.0
1350-SU-026 1350 TAILINGS THICKENER DISCHARGE SUMP 1.0
1350-SU-027 1350 TAILINGS THICKENER DISCHARGE SUMP 1.0
1350-SU-201 1350 FLOTATION EMERGENCY TANK 1.0
1350-SU-201-01 1350 FLOTATION EMERGENCY TANK DISTRIBUTOR 1.0
1350-SU-202 1350 FLOTATION EMERGENCY TANK 1.0
1350-TK-009 1350 ROUGHER/SCAVENGER TAILINGS COLLECTION BOX 1.0
1350-TK-014 1350 TAILINGS THICKENER 1.2
1350-TK-015 1350 TAILINGS THICKENER 1.2
1350-TK-016 1350 TAILINGS THICKENER 1.2
1350-TK-019 1350 THICKENERS OVERFLOW TANK 1.2
1350-TK-020 1350 THICKENERS OVERFLOW TANK 1.2
1350-TM-014 1350 TAILINGS THICKENER MECHANISM 1.2
1350-TM-015 1350 TAILINGS THICKENER MECHANISM 1.2
1350-TM-016 1350 TAILINGS THICKENER MECHANISM 1.2
1360-CN-122 1360 FLOCCULANT SYSTEM SERVICE CRANE 1.2
1360-CN-128 1360 XANTHATE SYSTEM SERVICE CRANE 1.2
1360-PP-375 1360 TAILINGS FLOCCULANT PROGESSIVE CAVITY PUMP 1.0

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
43 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1360-PP-376 1360 TAILINGS FLOCCULANT PROGESSIVE CAVITY PUMP 1.0
1360-PP-377 1360 TAILINGS FLOCCULANT PROGESSIVE CAVITY PUMP 1.0
1360-PP-378 1360 TAILINGS FLOCCULANT PROGESSIVE CAVITY PUMP 1.0
1360-PP-379 1360 TAILINGS FLOCCULANT PROGESSIVE CAVITY PUMP 1.0
1360-PP-380 1360 TAILINGS FLOCCULANT PROGESSIVE CAVITY PUMP 1.0
1360-PP-383 1360 PRIMARY COLLECTOR RECIRCULATION PUMP 1.0
1360-PP-384 1360 PRIMARY COLLECTOR RECIRCULATION PUMP 1.0
1360-PP-389 1360 NAHS COLLECTOR RECIRCULATION PUMP 1.0
1360-PP-390 1360 NAHS COLLECTOR RECIRCULATION PUMP 1.0
1360-PP-676 1360 CONCENTRATE FLOCCULANT METERING PUMP 1.0
1360-PP-677 1360 CONCENTRATE FLOCCULANT METERING PUMP 1.0
1360-PP-678 1360 CONCENTRATE FLOCCULANT METERING PUMP 1.0
1360-PP-679 1360 CONCENTRATE FLOCCULANT METERING PUMP 1.0
1360-PP-680 1360 CONCENTRATE FLOCCULANT METERING PUMP 1.0
1360-PP-681 1360 CONCENTRATE FLOCCULANT METERING PUMP 1.0
1360-PP-684 1360 NAHS DISCHARGE PUMP 1.0
1360-PP-685 1360 NAHS SPILLS MANAGE PUMP 1.0
1360-PP-686 1360 XANTHATE SPILLS MANAGE PUMP 1.0
1360-PP-700 1360 SPARE SPILLS MANAGE PUMP 1.0
1360-ST-738 1360 REAGENT COLLECTOR FUNNEL 1.0
1360-ST-739 1360 REAGENT COLLECTOR FUNNEL 1.0
1360-TK-079 1360 NAHS STORAGE TANK 1.2
1360-ZM-094 1360 FLOCCULANT FEED PACKAGE 1.0
1360-ZM-094-01 1360 FLOCCULANT FEED SYSTEM 1.0
1360-ZM-094-02 1360 FLOCCULANT SCREW FEEDER 1.0
1360-ZM-094-03 1360 FLOCCULANT BLOWER 1.0
1360-ZM-094-04 1360 EDUCTOR 1.0
1360-ZM-094-05 1360 MIX TANK 1.2
1360-ZM-094-06 1360 AGITATOR MIX TANK 1.2
1360-ZM-094-07 1360 FLOCCULANT TRANSFER PUMP 1.0
1360-ZM-094-08 1360 FLOCCULANT TRANSFER PUMP 1.0
1360-ZM-094-09 1360 MIXING HEAD 1.0
1360-ZM-094-10 1360 FLOCCULANT STORAGE TANK 1.2
1360-ZM-094-11 1360 FLOCCULANT STORAGE TANK AGITATOR 1.2
1360-ZM-095 1360 FLOCCULANT FEED PACKAGE 1.0
1360-ZM-095-01 1360 FLOCCULANT FEED SYSTEM 1.0
1360-ZM-095-02 1360 FLOCCULANT SCREW FEEDER 1.0
1360-ZM-095-03 1360 FLOCCULANT BLOWER 1.0
1360-ZM-095-04 1360 EDUCTOR 1.0
1360-ZM-095-05 1360 MIX TANK 1.2
1360-ZM-095-06 1360 AGITATOR MIX TANK 1.2
1360-ZM-095-07 1360 FLOCCULANT TRANSFER PUMP 1.0
1360-ZM-095-08 1360 FLOCCULANT TRANSFER PUMP 1.0
1360-ZM-095-09 1360 MIXING HEAD 1.0
1360-ZM-095-10 1360 FLOCCULANT STORAGE TANK 1.2
1360-ZM-095-11 1360 FLOCCULANT STORAGE TANK AGITATOR 1.2
1360-ZM-096 1360 TAILING FLOCCULANT EDUCTOR 1.0
1360-ZM-097 1360 TAILING FLOCCULANT EDUCTOR 1.0
1360-ZM-098 1360 TAILING FLOCCULANT EDUCTOR 1.0
1360-ZM-394 1360 EDUCTOR 1.0
1360-ZM-395 1360 EDUCTOR 1.0
1360-ZM-396 1360 EDUCTOR 1.0
1360-ZM-398 1360 XANTHATE PLANT 1.2
1360-ZM-398-01 1360 XANTHATE STORAGE TANK 1.2
1360-ZM-398-02 1360 XANTHATE MIXING TANK 1.2
1360-ZM-398-03 1360 XANTHATE PUMP 1.0
1360-ZM-398-05 1360 XANTHATE MIXING TANK AGITATOR 1.2
1360-ZM-398-06 1360 XANTHATE AREA SCRUBBER 1.0
1360-ZM-398-07 1360 SCRUBBER FAN 1.0
1360-ZM-398-08 1360 XANTHATE STORAGE TANK AGITATOR 1.2
1360-ZM-398-09 1360 SPARE REAGENT MIXING TANK 1.2
1360-ZM-398-10 1360 SPARE REAGENT STORAGE TANK 1.2
1360-ZM-398-11 1360 SPARE REAGENT STORAGE TANK AGITATOR 1.2
1360-ZM-398-12 1360 SPARE REAGENT MIXING TANK AGITATOR 1.2

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
44 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1360-ZM-398-13 1360 SPARE REAGENT PUMP 1.0
1360-ZM-421 1360 FLOCCULANT FEED PACKAGE 1.0
1360-ZP-008 1360 EMERGENCY SHOWER W/ EYE WASH 1.0
1360-ZP-009 1360 EMERGENCY SHOWER W/ EYE WASH 1.0
1360-ZP-010 1360 EMERGENCY SHOWER W/ EYE WASH 1.0
1360-ZP-011 1360 EMERGENCY SHOWER W/ EYE WASH 1.0
1360-ZP-012 1360 EMERGENCY SHOWER W/ EYE WASH 1.0
1360-ZP-013 1360 EMERGENCY SHOWER W/ EYE WASH 1.0
1370-AG-046 1370 MILK OF LIME STORAGE TANK AGITATOR GRINDING AREA 1.2
1370-AG-047 1370 MILK OF LIME STORAGE TANK AGITATOR GRINDING AREA 1.2
1370-AG-048 1370 MILK OF LIME STORAGE TANK AGITATOR GRINDING AREA 1.2
1370-AG-049 1370 MILK OF LIME STORAGE TANK AGITATOR GRINDING AREA 1.2
1370-CH-105 1370 HOIST 1.0
1370-CH-106 1370 HOIST 1.0
1370-DI-009 1370 FEED DISTRIBUTOR FLOTATION AREA 1.0
1370-DI-009-01 1370 DART VALVE 1.0
1370-DI-009-02 1370 DART VALVE 1.0
1370-PP-082 1370 MILK OF LIME CIRCULATION PUMP GRINDING AREA 1.0
1370-PP-083 1370 MILK OF LIME CIRCULATION PUMP GRINDING AREA 1.0
1370-PP-089 1370 MILK OF LIME CIRCULATION PUMP FLOTATION AREA 1.0
1370-PP-090 1370 MILK OF LIME CIRCULATION PUMP FLOTATION AREA 1.0
1370-TK-046 1370 MILK OF LIME STORAGE TANK GRINDING AREA 1.2
1370-TK-047 1370 MILK OF LIME STORAGE TANK GRINDING AREA 1.2
1370-TK-048 1370 MILK OF LIME STORAGE TANK FLOTATION AREA 1.2
1370-TK-049 1370 MILK OF LIME STORAGE TANK FLOTATION AREA 1.2
1370-ZM-121 1370 LIME PLANT 1.2
1370-ZM-121-01 1370 LIME STORAGE BIN 1.2
1370-ZM-121-02 1370 LIME STORAGE BIN VIBRATING BOTTOM 1.0
1370-ZM-121-03 1370 LIME LOADOUT AIR COMPRESSOR 1.0
1370-ZM-121-04 1370 LIME SLAKING MILL FEED CONVEYOR 1.0
1370-ZM-121-05 1370 LIME DISCHARGE BOX 1.0
1370-ZM-121-06 1370 LIME SLAKING MILL 1.0
1370-ZM-121-07 1370 OIL COOLER, SPEED REDUCER 1.0
1370-ZM-121-08 1370 LUBRICATION SYSTEM FOR SPEED REDUCER 1.0
1370-ZM-121-09 1370 FEED BALLS CHUTE 1.0
1370-ZM-121-10 1370 LIME SLAKING MILL RECIRCULATING PUMP 1.0
1370-ZM-121-11 1370 SLAKING MILL OVERFLOW SUMP 1.0
1370-ZM-121-12 1370 LIME SLAKING MILL CYCLONE FEED PUMP 1.0
1370-ZM-121-13 1370 PUMPING BOX TO CYCLONE FEED 1.0
1370-ZM-121-14 1370 CHUTE FEED LIME SLAKING MILL 1.0
1370-ZM-121-15 1370 CHUTE DISCHARGE LIME SLAKING MILL 1.0
1370-ZM-121-16 1370 ACCUMULATOR 1.0
1370-ZM-121-17 1370 LIME BIN DUST COLLECTOR 1.0
1370-ZM-121-18 1370 DUST COLLECTOR FAN 1.0
1370-ZM-121-20 1370 LIME SLAKING MILL CYCLONE 1.0
1370-ZM-121-21 1370 FEED DISTRIBUTOR GRINDING AREA 1.0
1370-ZM-121-22 1370 DART VALVE 1.0
1370-ZM-121-23 1370 DART VALVE 1.0
1370-ZP-001 1370 EMERGENCY SHOWER W/ EYE WASH 1.0
1370-ZP-002 1370 EMERGENCY SHOWER W/ EYE WASH 1.0
1370-ZP-003 1370 EMERGENCY SHOWER W/ EYE WASH 1.0
1370-ZP-004 1370 EMERGENCY SHOWER W/ EYE WASH 1.0
1370-ZP-005 1370 EMERGENCY SHOWER W/ EYE WASH 1.0
1370-ZP-006 1370 EMERGENCY SHOWER W/ EYE WASH 1.0
1370-ZP-007 1370 EMERGENCY SHOWER W/ EYE WASH 1.0
1390-CP-035 1390 AIR COMPRESSOR 1.0
1390-CP-036 1390 AIR COMPRESSOR 1.0
1390-CP-037 1390 AIR COMPRESSOR 1.0
1390-CP-038 1390 AIR COMPRESSOR 1.0
1390-CP-039 1390 AIR COMPRESSOR 1.0
1390-CP-040 1390 AIR COMPRESSOR 1.0
1390-CP-041 1390 AIR COMPRESSOR 1.0
1390-CP-042 1390 INSTRUMENTATION AIR COMPRESSOR 1.0
1390-DR-011 1390 INSTRUMENTATION AIR DRYER 1.0
1390-DR-012 1390 INSTRUMENTATION AIR DRYER 1.0

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
45 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1390-VS-019 1390 AIR ACCUMULATOR COLLUMN CELLS 1.0
1390-VS-020 1390 AIR ACCUMULATOR 1.0
1390-VS-021 1390 AIR ACCUMULATOR 1.0
1390-VS-022 1390 INSTRUMENTATION AIR ACCUMULATOR 1.0
1410-AG-033 1410 CONCENTRATE STORAGE TANK AGITATOR 1.2
1410-AG-034 1410 CONCENTRATE STORAGE TANK AGITATOR 1.2
1410-AG-035 1410 CONCENTRATE STORAGE TANK AGITATOR 1.2
1410-AG-036 1410 CONCENTRATE STORAGE TANK AGITATOR 1.2
1410-DI-107 1410 CONCENTRATE STORAGE TANK DISTRIBUTOR 1.2
1410-DI-174 1410 CHARGE PUMPS DISTRIBUTOR 1.0
1410-DI-175 1410 CHARGE PUMPS DISTRIBUTOR 1.0
1410-PP-107 1410 SUMP PUMP 1.0
1410-TK-033 1410 CONCENTRATE STORAGE TANK 1.2
1410-TK-034 1410 CONCENTRATE STORAGE TANK 1.2
1410-TK-035 1410 CONCENTRATE STORAGE TANK 1.2
1410-TK-036 1410 CONCENTRATE STORAGE TANK 1.2
1420-CN-123 1420 CONCENTRATE PUMP STATION BRIDGE CRANE 1.0
1420-FA-013 1420 PACKAGED UNITARY COOLING ROOFTOP FOR ELECTRICAL ROOM ER-532 1.0
1420-FA-016 1420 FAN PRESSURIZATION FOR ELECTRICAL ROOM ER-532 1.0
1420-FA-021 1420 PACKAGED UNITARY COOLING ROOFTOP FOR ELECTRICAL ROOM ER-532 1.0
1420-FA-022 1420 FAN PRESSURIZATION FOR ELECTRICAL ROOM ER-532 1.0
1420-FL-001 1420 CONCENTRATE FILTER 1.0
1420-FL-002 1420 CONCENTRATE FILTER 1.0
1420-FL-003 1420 CONCENTRATE FILTER 1.0
1420-FL-004 1420 CONCENTRATE FILTER 1.0
1420-PP-049 1420 CHARGE PUMP 1.0
1420-PP-050 1420 CHARGE PUMP 1.0
1420-PP-063 1420 CHARGE PUMP 1.0
1420-PP-064 1420 CHARGE PUMP 1.0
1420-PP-075 1420 CHARGE PUMP 1.0
1420-PP-076 1420 SEAL WATER PUMP 1.0
1420-PP-077 1420 SEAL WATER PUMP 1.0
1420-PP-080 1420 CHARGE PUMP 1.0
1420-PP-098 1420 SEAL WATER PUMP 1.0
1420-PP-099 1420 SEAL WATER PUMP 1.0
1420-PP-101 1420 CONCENTRATE POSITIVE DISPLACEMENT PUMP 1.2
1420-PP-102 1420 CONCENTRATE POSITIVE DISPLACEMENT PUMP 1.2
1420-PP-103 1420 CONCENTRATE POSITIVE DISPLACEMENT PUMP 1.2
1420-ZM-026 1420 HVAC FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1420-ZM-027 1420 HVAC FIXED LOUVERS AND BACKDRAFT RELIEF DAMPER 1.0
1420-ZM-028 1420 BACKDRAFT RELIEF DAMPER 1.0
1420-ZM-029 1420 BACKDRAFT RELIEF DAMPER 1.0
1610-DI-178 1610 TAILINGS COLLECTOR BOX 1.0
1620-AG-176 1620 AGITATOR SAND TANK 1.0
1620-CN-070 1620 BRIDGE CRANE CYCLONE BATTERY 1.0
1620-CS-030 1620 CYCLONE BATTERY 1.0
1620-DI-450 1620 CICLONE CHARGE BOX 1.0
1620-DI-451 1620 LAMAS BOX 1.0
1620-DI-501 1620 TAILINGS DISTRIBUTION BOX 1.0
1620-DI-502 1620 TAILINGS DISTRIBUTION BOX 1.0
1620-DI-503 1620 TAILINGS DISTRIBUTION BOX 1.0
1620-DI-504 1620 TAILINGS DISTRIBUTION BOX 1.0
1620-DI-505 1620 TRANSFER BOX N° 1 1.0
1620-DI-506 1620 TRANSFER BOX N° 2 1.0
1620-PP-450 1620 SAND DISTRIBUTION PUMP 1.0
1620-PP-459 1620 LAMAS PUMP 1.0
1620-PP-463 1620 SEAL WATER PUMP FOR LAMAS PUMP 1.0
1620-PP-464 1620 SEAL WATER PUMP FOR LAMAS PUMP 1.0
1620-PP-511 1620 SEAL WATER PUMP FOR TAILINGS DISTRIBUTION PUMP 1.0
1620-PP-512 1620 SEAL WATER PUMP FOR TAILINGS DISTRIBUTION PUMP 1.0
1620-PP-513 1620 SEAL WATER PUMP FOR TAILINGS DISTRIBUTION PUMP 1.0
1620-PP-514 1620 SEAL WATER PUMP FOR TAILINGS DISTRIBUTION PUMP 1.0
1620-PP-515 1620 TAILINGS DISTRIBUTION PUMP 1.0
1620-PP-516 1620 TAILINGS DISTRIBUTION PUMP 1.0
1620-PP-517 1620 TAILINGS DISTRIBUTION PUMP 1.0

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
46 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1620-PP-518 1620 TAILINGS DISTRIBUTION PUMP 1.0
1620-PP-519 1620 TAILINGS DISTRIBUTION PUMP 1.0
1620-PP-520 1620 TAILINGS DISTRIBUTION PUMP 1.0
1620-PP-521 1620 TAILINGS PUMP TRANSFER 1.0
1620-PP-522 1620 TAILINGS PUMP TRANSFER 1.0
1620-PP-531 1620 SEAL WATER PUMP FOR TAILINGS PUMP TRANSFER 1.0
1620-PP-532 1620 SEAL WATER PUMP FOR TAILINGS PUMP TRANSFER 1.0
1620-PP-533 1620 SEAL WATER PUMP FOR TAILINGS PUMP TRANSFER 1.0
1620-PP-534 1620 SEAL WATER PUMP FOR TAILINGS PUMP TRANSFER 1.0
1620-TK-181 1620 SEAL WATER TANK FOR TAILINGS DISTRIBUTION PUMP 1.0
1620-TK-182 1620 SEAL WATER TANK FOR TAILINGS TRANSFER PUMP 1.0
1620-TK-184 1620 SEAL WATER TANK FOR LAMAS PUMP 1.0
1630-CN-090 1630 PORTAL CRANE PUMPS DRAIN MAINTENANCE 1.0
1630-PD-500 1630 FILTRATIONS POND 1.0
1630-PP-541 1630 VERTICAL PUMP DRAIN RECOVERY 1.0
1630-PP-542 1630 VERTICAL PUMP DRAIN RECOVERY 1.0
1630-PP-550 1630 SUBMERSIBLE PUMP DRAIN POND 1.0
1630-SU-541 1630 SUMP DRAIN AND FILTRATIONS RECUPERATION 1.0
1630-TK-180 1630 WATER TANK DRAINS AND FILTRATIONS 1.0
1720-CZ-004 1720 COOLING TOWER 1.0
1720-CZ-005 1720 COOLING TOWER 1.0
1720-CZ-006 1720 COOLING TOWER 1.0
1720-DI-177 1720 DISTRIBUIDOS AGUA RECUPERADA 1.0
1720-DI-177-01 1720 DART VALVE 1.0
1720-DI-177-02 1720 DART VALVE 1.0
1720-DI-177-03 1720 DART VALVE 1.0
1720-DI-177-04 1720 DART VALVE 1.0
1720-DI-177-05 1720 DART VALVE 1.0
1720-DI-177-06 1720 DART VALVE 1.0
1720-DI-177-07 1720 DART VALVE 1.0
1720-DI-177-08 1720 DART VALVE 1.0
1720-HX-014 1720 HEAT EXCHANGER 1.0
1720-HX-015 1720 HEAT EXCHANGER 1.0
1720-HX-016 1720 HEAT EXCHANGER 1.0
1720-LA-092 1720 DRAIN COLLECTOR LAUNDER 1.0
1720-PP-211 1720 R. O. PLANT FEED PUMP 1.0
1720-PP-212 1720 R. O. PLANT FEED PUMP 1.0
1720-PP-239 1720 COOLING TOWER PUMP 1.0
1720-PP-240 1720 COOLING TOWER PUMP 1.0
1720-PP-241 1720 COOLING TOWER PUMP 1.0
1720-PP-244 1720 COOLING EQUIPMENT PUMP 1.0
1720-PP-245 1720 COOLING EQUIPMENT PUMP 1.0
1720-PP-246 1720 FIRE WATER PUMP (ELECTRICAL) 1.0
1720-PP-247 1720 FIRE WATER PUMP (DIESEL) 1.0
1720-PP-248 1720 FIRE WATER JOCKEY PUMP 1.0
1720-PP-249 1720 COOLING EQUIPMENT PUMP 1.0
1720-PP-682 1720 SERVICE PUMP R.O. PLANT 1.0
1720-PP-683 1720 SERVICE PUMP R.O. PLANT 1.0
1720-SU-015 1720 COOLING TOWER SUMP 1.0
1720-SU-204 1720 DRAIN COLLECTOR BOX 1.0
1720-TE-002 1720 OSMOSIS REVERSE PLANT 1.2
1720-TE-002-01 1720 MULTIMEDIA FILTER 1.0
1720-TE-002-02 1720 RO UNIT 1.0
1720-TE-002-03 1720 CLORATION SYSTEM 1.2
1720-TE-002-04 1720 ADDITION OF ACID SYSTEM 1.2
1720-TE-002-05 1720 ADDITION OF ANTI FOULING SYSTEM 1.2
1720-TE-002-06 1720 DESCARBONATOR 1.0
1720-TE-002-07 1720 DISCHARGE PUMPS 1.0
1720-TE-002-08 1720 CLEANER SYSTEM RO 1.0
1720-TE-002-09 1720 REAGENT TRANSFER PUMP 1.0
1720-TE-002-10 1720 REAGENT TRANSFER PUMP 1.0
1720-TE-002-11 1720 REAGENT TRANSFER PUMP 1.0
1720-TE-002-12 1720 REAGENT TRANSFER PUMP 1.0
1720-TK-251 1720 FRESH WATER TANK 1.2
1720-TK-252 1720 POTABLE WATER TANK 1.2

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
47 of 48
DesignCriteria for Civil-Structural
25713-220-3DR-S15-00001-00B

Component Facility
Number Code Description Import ID
1720-TK-253 1720 WARM WATER TANK 1.2
1720-TK-254 1720 COLD WATER TANK 1.2
1720-TK-255 1720 WATER POND 1.2
1720-TK-256 1720 WATER POND 1.2
1730-SU-205 1730 SEWAGE SPILLS PARAPET 1.2
1730-TE-003 1730 SEWAGE TREATMENT PLANT 1.2
3300-PD-005 3300 DESALINATED WATER RECEIVOR 1.2
5300-CN-135 5300 PUMP STATION N°5 BRIDGE CRANE 1.2
5300-PD-004 5300 PUMP STATION N°5 EMERGENCY POND 1.0
5300-PP-500 5300 BOOSTER PUMP 400x400 POND PUMP STATION TO NEW FRESH WATER POND 1.2
5300-PP-501 5300 BOOSTER PUMP 400x400 POND PUMP STATION TO NEW FRESH WATER POND 1.2
5300-PP-502 5300 BOOSTER PUMP 400x400 POND PUMP STATION TO NEW FRESH WATER POND 1.2
5300-PP-503 5300 DESALINATED WATER PUMP, STATION N°5 1.2
5300-PP-503-01 5300 LUBE UNIT SYSTEM PUMP 1.0
5300-PP-504 5300 DESALINATED WATER PUMP, STATION N°5 1.2
5300-PP-504-01 5300 LUBE UNIT SYSTEM PUMP 1.0
5300-PP-505 5300 DESALINATED WATER PUMP, STATION N°5, STAND BY 1.2
5300-PP-505-01 5300 LUBE UNIT SYSTEM PUMP 1.0
5300-PP-506 5300 COOLING WATER PUMP LUBRICATION SYSTEM 1.0
5300-TE-006 5300 R.O. PLANT 1.0
5300-TE-007 5300 SEWAGE TREATMENT PLANT 1.0
5300-TK-262 5300 PUMP STATION N°5 DESALINATED WATER TANK 1.2
5300-TK-263 5300 OGP1 TO ESCONDIDA NORTE FRESH WATER STORAGE TANK 1.2

Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in stobhpOGP1 of Infoworks for current revisions.
Bechtel Confidential © Bechtel 2011. Contains confidential and/or information proprietary to Bechtel and its affiliated companies which
shall not be used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights
reserved. Use of this deliverable is subject to restrictions set forth in the contract
48 of 48

You might also like