You are on page 1of 1

1700 FOUNDATION BOLT

M-18 X 500 MM

75
300
8 NOS. 20Ø 8 NOS. 20Ø
G.L. G.L.

1500
8Ø @ 200C/C 8Ø @ 200C/C

850

850
150 150

800 800

250

250
100

100
10Ø @
1000 200C/C (both ways) 1000 10Ø @
200C/C (both ways)

100 thick PCC 1:4:8 100 thick PCC 1:4:8

SECTION A-A

130 1570 130

800
200
800
130

1. All dimensions are in millimeter.


2. This drawing is not to scale. Only written dimensions shall
500 be followed.
1700

1830

1000 1000 3. This drawing shall be read in conjunction with the other
structural drawing. If doubt stop the work and consult our
office.
4. Concrete shall be of grade M-20. Nominal Mix 1:1.5:3
800
130

800

(1cement : 1.5 Coarse Sand : 3 Graded stone aggregate of


nominal size 20mm) confirming to IS456:2000. The
characteristic strength at 28 days is 20 N/Sq.mm.
1700
5.Steel shall be high strength deformed bars confirming to
IS1786:1985 Grade Fe415.
FOUNDATION PLAN 6. Reinforcement shall be bent and positioned in
accordance to the procedure specifiedin IS2502:1963.
7. Clear cover to the reinforcement shall be as follows.
a. Footing -50 mm
b. Slab & Walls - 25 mm on liquid retaining side
c. Beams - 25 mm
d. Column - 40 mm
8. Lap length shall be 50Ø.
9. Chairs of approved type shall be used.
10. 100 mm thick PCC of 1:4:8 shall be provided under the raft.
11. Levels are in Meter.
12. The unit shall be laid over naturally consolidated firm
ground.
13. Safe bearing capacity of soil is 100 KN/SQ. M.