You are on page 1of 10

j m a t e r r e s t e c h n o l .

2 0 2 0;9(3):4968–4977

Available online at www.sciencedirect.com

www.jmrt.com.br

Original Article

Influence of design durability on concrete columns


fire performance

Fabrício Longhi Bolina a , Augusto Masiero Gil b , Bruno Fernandes c ,


Guilherme Gunther Hennemann a , Jordana Gonçalves a , Bernardo Fonseca Tutikian a,∗
a University of Vale do Rio dos Sinos, São Leopoldo, Rio Grande do Sul, Brazil
b Michigan State University, Michigan, United States
c Université de Pau et des Pays de l’Adour, France

a r t i c l e i n f o a b s t r a c t

Article history: Reinforced concrete structures must be designed to meet minimum durability requirements
Received 28 January 2020 throughout service life and, as well as in case of a fire, to fulfill fire resistance demands to
Accepted 4 March 2020 guarantee user’s safety. This study experimentally evaluated the behavior of column proto-
Available online 30 March 2020 types built of different concrete durability design parameters when exposed to fire, confined
by a masonry wall. The evaluation consisted of 16 precast columns of 25 × 25 × 300 cm
Keywords: divided into 4 groups of different concrete mix design. The elements were tested in a
Fire safety standardized vertical furnace for 240 min, exposed to the heating curve from ISO 834. The
Concrete structures results showed that the concrete durability parameters influenced the spalling degree and
Fire resistance fire resistance performance of the columns. Nevertheless, the concrete cover thickness and
Structural durability the diameter of the longitudinal reinforcing steel bars presented greater influence in fire
resistance than concrete mix design.
© 2020 The Authors. Published by Elsevier B.V. This is an open access article under the
CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).

maximum water-cement ratio, as well as a minimum com-


1. Introduction pressive strength and cement consumption.
Regarding fire safety design criteria, standards such as ACI
The durability criteria of the main international structural o
216-R [7], CEB Bulletin n 208 [8], BS 8110-2 [9], AS 1530-1 [10],
design standards, such as ACI 318 [1], AS-3600 [2], BS 8500-
NZS 3101 [11], IS 456 [5] and NBR 15200 [12] are based on
1 [3], EN 206-1 [4], IS 456 [5] and NBR 6118 [6], are based
fixed structural verification methods. In some of these meth-
on the relationship between the environmental aggression,
ods, design parameters usually refer to a minimum concrete
the concrete specifications and the concrete cover thickness.
cover thickness and dimensions of the elements. However,
For each type of aggressive environment, it is specified a
these methods do not admit constitutive concrete mix design
minimum concrete cover thickness for reinforcing bars, a
in the analysis, such as compressive strength, cement con-
sumption, water-cement ratio (w/c). Therefore, a detailed fire
analysis should be considered as an alternative to the pre-

Corresponding author. scriptive method [13].
E-mail: bftutikian@unisinos.br (B.F. Tutikian).
https://doi.org/10.1016/j.jmrt.2020.03.015
2238-7854/© 2020 The Authors. Published by Elsevier B.V. This is an open access article under the CC BY-NC-ND license (http://
creativecommons.org/licenses/by-nc-nd/4.0/).
j m a t e r r e s t e c h n o l . 2 0 2 0;9(3):4968–4977 4969

Moreover, the main international structural design stan- are directly related to each other [26]. Dwaikat and Kodur [27]
dards [5,7–12], especially the simplified methods of analysis, highlight that the fire resistance of ultra-high-performance
do not completely relate the durability and fire resistance cri- concrete beams is lower than of regular concrete beams.
teria. The fire safety structural design standards are based, The authors also indicate that ultra-high-performance con-
usually, on a concrete cover thickness necessary for protect crete beams also present a greater degree of spalling and the
the steel bars temperature. Differently from durability, the w/c increase in the concrete performance increases the probability
ratio and the concrete strength are not considered in the fire of explosive spalling [28].
resistance analysis. If, on the one hand, concretes of reduced Nevertheless, other authors indicate an opposite behav-
w/c ratios tend to increase the durability, on the other hand, ior, in which the performance reduces the incidence of such
researches show that when subjected to high temperatures, mechanism. This would be associated with material’s tensile
concretes could produce the explosive spalling phenomenon strength, which balances or exceeds the effect of low w/c ratio.
[14]. Nevertheless, an opposite behavior was verified [15] and, It was highlighted in the study by Ali [29], which presented a
thus, further investigation is necessary. comparative study on the occurrence of spalling in ultra-high
performance and regular concrete columns. In such study,
a direct relationship between the material strength and the
2. Relevance of this research spalling occurrence was not identified, and, in some cases,
the spalling was more severe in the regular concrete columns.
The durability parameters specified in technical standards of Overall, a significant number of experimental programs
reinforced concrete, as cover thickness, cement consumption, evaluating durability parameters can be found in the liter-
water-cement ratio and compressive strength, affect not only ature. However, most part of them are isolated and do not
the behavior of concrete at ambient temperature, but also infer show a direct relationship between such parameters and the
in the behavior of concrete and reinforced concrete elements behavior under fire conditions. Therefore, this study aimed to
exposed to high temperatures [16,17]. Among the processes evaluate the design durability parameters influence on the fire
that involve the behavior of column prototypes, it is possible resistance of reinforced concrete columns subjected to high
to verify that the increase in the environmental aggressive- temperatures.
ness class produced greater resistance to compression of this
material, an increase in the spalling and the degradation of
concrete structures. 3. Experimental investigation
The build-up of resistance of concrete and reduction in the
water/cement ratio, caused a highlight durability and low per- In order to analyze the influence of durability design param-
meability, also control aggressive agents in the interior of the eters of concrete elements in fire conditions, 16 reinforced
concrete [18]. concrete columns prototypes were produced. The specimens
Under these circumstances at elevated temperatures, the had dimensions of 25 × 25 × 300 cm and were built of concretes
disintegration of hydrated cement products, rupture of bonds with different strengths, cement consumptions and w/c ratios.
in the microstructure of cement paste and the extent of reduc- For each durability parameter, four columns with the same
tion be contingent on moisture loss [19]. Despite the beneficial concrete mix design were built having only one variable, which
effect on durability, the greater thickness of concrete cover can was the concrete cover thickness. Table 1 presents the overall
intensify the mechanism. An inverse relationship between information about the specimens tested.
durability and fire resistance is not considered by the pre- Concrete mixtures were determined by the mix design
scribed standards of the project in these conditions [20]. method proposed by Tutikian and Helene [30]. The dry mortar
Regarding the influence of the concrete cover thickness, ratio was fixed in 52%. The w/c ratio and cement consumption
Guo and Shi [21] verified that a cover increment of 10–30 mm were defined according to the durability requirements. Table 2
at beam’s maximum moment zone increase its fire resistance. presents the proportioning of concrete mixtures.
However, such influence reduces when the cover increment is The column’s fabrication procedure was performed in an
greater than 20 mm. In terms of concrete spalling, Kyu and automated concrete batcher at a precast plant. Column’s
Hoon [22] verified an increase in the degree of spalling with structural details is indicated in Fig. 1.
the increase of concrete cover thickness in a study involving In the laboratory, the tests of high temperature were con-
reinforced concrete columns. Furthermore, Dwaikat [23] stud- ducted in a standardized vertical test furnace and followed
ied the behavior of beams and verified that the cover thickness the temperature curve from ISO 834 [31]. The temperature
increment reduces the temperature in the reinforcement steel progress in the reinforcement steel bars was analyzed both
bars and, thus, reduces the element deflection. on the exposed concrete surface and in different points and
Regarding cement consumption, Ergün et al. [24] verified layers of the cross section of the columns.
the residual mechanical behavior of concrete specimens with The columns were tested in pairs, resulting in 8 tests. The
different cement consumptions (250 and 350 kg/m3 ) and found location of thermocouples followed the guidelines from JIS
that, despite affecting the behavior at ambient temperature, A1304 [32]. The installation of thermocouples in the column P1
this parameter does not influence the residual compressive of each concrete mixture was performed according to Fig. 2a.
strength of concretes exposed to high temperatures. The type Besides the alignment of the thermocouples fixed into the
of aggregate is another variable influence [25]. reinforcement steel bars (alignment A and B), the element
Lastly, there is a relevant amount of studies that evaluate also received thermocouples to measure the progress of the
the compressive strength and the water-cement ratio, which temperatures in the interior of the cross section (alignment
4970 j m a t e r r e s t e c h n o l . 2 0 2 0;9(3):4968–4977

Table 1 – Overall information about the specimens tested.


Specimen MRa EAC CT w/c Ratio CC (kg/m3 ) Concrete Class

T1P1 25
T1P2 30
1 I (Weak) 0.65 260 ≥C20
T1P3 40
T1P4 50
T2P1 25
T2P2 30
2 II (Moderate) 0.60 280 ≥C25
T2P3 40
T2P4 50
T3P1 25
T3P2 30
3 III (Strong) 0.55 320 ≥C30
T3P3 40
T3P4 50
T4P1 25
T4P2 30
4 IV (Very Strong) 0.45 360 ≥C40
T4P3 40
T4P4 50

a
MR: Mixing Ratio; EAC: Environmental Aggression Class; CT: Cover Thickness (mm); CC: Cement Consumption (kg/m3 ).

Table 2 – Concrete mixtures proportioning.


MRa Constituent (kg/m3 ) fc,28 (MPa)

Cement CS NS CA (e = 9,5 mm) CA (e = 19 mm) Water

1 260 312 578 321 750 169 47.9


2 280 308 572 321 749 168 61.9
3 320 292 543 320 745 176 40.2
4 360 280 519 322 751 162 75.6

a
MR: Mixing Ratio; Cement: CP V ARI; CS: Crushed sand; NS: Natural sand; CA: Coarse aggregate.

Fig. 1 – Overall structural detailing of columns P1, P2, P3 and P4.

D and E) in every 5 cm, starting from the surface. Further- the vertical furnace is illustrated in Fig. 3. A floor plan of the
more, a thermocouple was installed in the concrete cover layer system, highlighting the column lines, is shown in Fig. 4. Fig. 5
(alignment C). The other columns of equal mixing ratio (P2, P3 illustrates one of the specimens coupled with the furnace.
and P4) received a thermocouple in the concrete cover (align-
ment C) and two alignments to measure the temperature in
the reinforcing steel bars, (alignments A and B), according to
4. Experimental results and discussion
Fig. 2b.
The testing system consisted of two columns confined in
a masonry wall in order to expose 45% of the column cross
4.1. Pathological manifestations during the tests
section to high temperatures, because it is a usual situation
The explosive noises were preceded and classified by low-
in most of residential buildings. The coupling of the wall and
and medium-intensity noise. The duration of such manifes-
j m a t e r r e s t e c h n o l . 2 0 2 0;9(3):4968–4977 4971

Fig. 2 – Location of the thermocouples in the columns (a) P1 and (b) P2, P3 and P4.

Fig. 3 – Perspective of the system coupling with the vertical furnace.

Fig. 4 – Detailing (floor plan) of the system coupled with the vertical furnace.

tations did not last longer than 35 min of testing, as shown The total amount of noises described in Fig. 6 is representa-
in Fig. 6. The main manifestations occurred between 5 and tive for each pair of columns taken from the total amount
15 min and were accompanied by the release of water and of noises that had low, moderate and high intensities. It
vapor through the surface not exposed to high temperatures, is noticed the trend of more concrete cover layer, more
what accentuates the thermo-hydrualical spalling hypothesis. noises.
4972 j m a t e r r e s t e c h n o l . 2 0 2 0;9(3):4968–4977

as a result of differential thermal tensions on the corners.


The cases in which the detachment of the superficial layers
occurred, the indication of internal tension became more evi-
dent. In the cross sections without the occurrence of spalling,
the cracks generated by the thermo-mechanical tensions may
have created a relief point for the internal pore pressure, which
reduced the magnitude and left insufficient energy for the ten-
sions to detach the concrete cover layer. In almost all cases,
reinforcing steel bars were not directly exposed to high tem-
peratures. A smaller degree of spalling predominated, which is
limited to the cover region without exposing directly the rein-
forcing bars. The cases in which such exposure was observed,
only up to half the perimeter of the reinforcing bars was
directly exposed to high temperatures. The whole perimeter
of the bars was exposed in none of the cases tested.

4.3. Degree of spalling

A greater trend of spalling was identified as a result of the


increment of concrete cover thickness, as seen by Morita et al.
[20] and Majorana et al. [33]. Fig. 8 demonstrates, through the
curves of “spalling degree versus concrete cover”, the ten-
Fig. 5 – Columns T4P1 and T4P2 coupled with the vertical
dency of an increment cross section loss as the cover thickness
furnace.
increases, regardless of concrete mixture. The concrete mix-
ture, on the other hand, influenced the magnitude of such
losses. Most of spalling occurred on the corners and with
4.2. Pathological manifestations after the tests greater intensity in the larger diameter reinforcing bar.
Furthermore, the frequency of spalling occurrence was
The aspect of the 16 columns after the tests is presented in overall predicted by a curve in which critical compressive
Fig. 7. strengths are shown according to the respective concrete
The spalling occurred in different intensities and in all cover thickness. Fig. 9 presents the curves of “spalling degree
columns, except P1 of Concrete III, which predominantly pre- versus compressive strength”. It was also observed from the
sented spalling on the corners. In some cases, the cracks on graph that there is a tendency of increasing spalling as the
the corners of the columns occurred with higher intensity. compressive strength increases up to 60 MPa, from where such
However, without causing the detachment of the concrete tendency reverses and the degree of spalling starts to reduce.
cover layer from the cross section. Such cracks occurred The column T1-P3 presented an anomalous behavior when

Fig. 6 – Frequency of sound manifestations registered.


j m a t e r r e s t e c h n o l . 2 0 2 0;9(3):4968–4977 4973

Fig. 8 – Tendency Curves: degree of spalling versus concrete


cover thickness.

Fig. 9 – “Spalling degree versus compressive strength”


curve.

compared to the curve generated by the columns of different


mixing ratios.
This smaller degree of spalling in concretes of strengths
lower than 60 MPa is explained because such concretes are
more permeable, which diminishes the pore pressures caused
by the process of water evaporation in the interior of the con-
crete. On the other hand, the smaller degree of spalling for
strengths higher than 60 MPa is explained by Ali et al. [34] and
Tutikian et al. [35], where the authors confirmed that concretes
of high values of compressive strength also possess signifi-
cant values of tensile strength and, thus, are more capable
of absorbing the tensions that cause spalling. Therefore, it is
possible to state that, for the conditions studied, the spalling
phenomenon occurs in a greater degree in concrete columns
with strength around 60 MPa.

4.4. Temperature distribution in concrete

From the temperature values measured in the cross sections of


the columns, heat maps were elaborated, and the intermedi-
ate values were calculated through interpolation algorithms.
The interpolation method used was Polynomial Regression for
Trend Surface Analysis. Fig. 10 presents the isotherms from
concrete mixture 2.
The temperature distribution in the cross sections shows
Fig. 7 – Frequency of sound manifestations registered.
a low thermal conductivity of concrete, which insulate the
reinforcing steel bars. After 30 min of testing, the core of the
columns at ambient temperature was identified. The tem-
perature gradient between the column surface and the layer
4974 j m a t e r r e s t e c h n o l . 2 0 2 0;9(3):4968–4977

Fig. 10 – Isotherms of columns from mixing ratio 2.

Fig. 11 – Temperature distribution curves in the cross section of the columns.

of 25 mm reached 700 ◦ C, which justifies the spalling of con- The growth of vapor pressure in the cross section, com-
crete caused by differential thermal movements of the layers. ing from thermo-hydraulic mechanism, combines with the
The thermo-mechanical mechanism may generate cracks that internal stress state of the element, which produces a weak-
induce, together with the pore pressures from vapor, the con- ening of the section by the formation of cracks, coming from
crete spalling [36]. the thermo-mechanical mechanism, are ideal conditions for
j m a t e r r e s t e c h n o l . 2 0 2 0;9(3):4968–4977 4975

Fig. 12 – Temperature distribution curves in the cross section of the columns.

spalling [37] which occurs when the tensile stress is exceeded


Table 3 – Concrete Cover Thickness at the critical
[38]. temperature of 500 ◦ C.
Fig. 11 presents the temperature distribution diagrams
Time (min) Concrete thickness (mm)
in the interior of the cross section of the columns, which
were generated from (a) mixture I, (b) mixture II, (c) mix- Concrete number
ture III and (d) mixture IV. It is noted that, in general,
o I II III IV
the temperature evolution is similar to FIB Bulletin n 46
[39]. 30 08 09 10 11
The non-linear distribution in the first instants is related 60 14 23 16 19
90 19 31 22 28
to the amount of energy consumed by the heat produced dur-
120 48 42 30 40
ing the process, as well as by the transformation of hydrated
150 58 54 39 49
compounds in the paste, and by the evaporation of the water 180 67 67 56 56
contained in the concrete. The segment in the tempera- 240 90 90 96 68
ture distribution that presents a linear aspect indicated the
heat exchange without transforming the hydrated compounds
4.5. Temperature distribution in the reinforcing steel
(sensible heat).
bars
In Table 3, the concrete thickness that acts at tempera-
ture 500 ◦ C, which is defined by fib Bulletin n 38 [40] as being
o
The temperature in the longitudinal reinforcement steel bars
the critical temperature in concrete, is detailed. The spalling
of the columns and on the surface of the columns produced
degree influence is noticed after 30 min, when the thermal
from (a) mixture I, (b) mixture II, (c) mixture III and (d) mixture
insulation of concrete starts to decrease and the columns from
IV are presented in Fig. 12. It is noticed that the medium tem-
concrete II, most affected by spalling, starts to increase tem-
perature in reinforcement bars with larger diameter (16 mm)
perature over the cover thickness.
were lower than with smaller diameter (10 mm), as observed
by Kodur et al. [41].
4976 j m a t e r r e s t e c h n o l . 2 0 2 0;9(3):4968–4977

The spalling did not indicate an active influence on the


temperature of the main reinforcement bars during the ini-
Acknowledgments
tial instants. After 90 min of testing, the influence of such
phenomenon in the reinforcement bars was more noticeable. The authors wish to express their gratitude and sincere appre-
The columns built from concrete III were the least affected by ciation to the authority of itt Performance, Technological
the spalling mechanism and the temperatures measured were Institute in Performance and Civil Construction from Unisinos
the lowest, especially in those specimens of thinner concrete University, for financing this research work.
covers. It demonstrates the negative influence of spalling in
reinforcement bars temperature.
Furthermore, the greater the cover thickness, the lower the references
temperature in the reinforcing bars and the later the tem-
perature of 500 ◦ C was reached, which is defined by technical
standards as the critical temperature in the main reinforcing [1] ACI 318. Building code requirements for structural concrete
bars. However, it was also observed that the temperature in and commentary. Farmington Hills, MI, USA: American
Concrete Institute; 2014.
the reinforcing bars, for equal duration of exposure to fire, was
[2] AS 3600. Concrete structures. Canberra, AS, Australia:
generally greater than the temperature of the concrete cover
Standards Association of Australia; 2009.
thickness. This fact indicated that some crack might have cre- [3] BS 8500. Concrete: complementary British Standard to BS EN
ated a path and facilitated the entrance of hot gases into the 206 - method of specifying and guidance for the specifier.
interior of the cross section, which subjected a segment of London, BSI, UK: British Standards Institution; 2015.
reinforcing bars to be in touch with heat. [4] EN 206-1. Concrete - specification, performance, production
and conformity. Brussels, CEN, Belgium: European
Committee for Standardization; 2015.
[5] IS 456. Plain and reinforced concrete. New Delphi, IS, India:
5. Conclusions Indian Standard; 2000.
[6] ABNT 6118. Projeto de Estruturas de Concreto -
Procedimento. Rio de Janeiro, RJ, Brazil: Associação Brasileira
By evaluating the prototypes of precast concrete columns built de Normas Técnicas; 2014.
with the materials and conditions described, it was possible [7] ACI 216. Guide for determining the fire endurance of
to conclude that the increase concrete durability criteria pro- concrete elements: concrete international. Farmington Hills,
moted, until determined compressive strength, an increase in MI, USA: American Concrete Institute; 1989.
the degree of spalling and loss of cross section of the elements. [8] CEB Bulletin d’Information n◦ 208. Fire design of concrete
The magnitude of section reduction in the elements did not structures. Lausanne, CEB, Switzerland: Comité
Euro-International Du Béton; 1991.
influence the temperature in the main reinforcing steel bars
[9] BS 8110-2. Structural use of concrete - code of practice for
until 90 min of exposure. special circumstances. London, BSI, UK: British Standards
Moreover, there was a tendency in the concrete spalling Institution; 1985.
not to expose the main reinforcement bars directly to high [10] AS 1530-1. Methods for fire test to building materials,
temperatures and protect the bars for a longer period due to components and structures. Canberra, AS, Australia:
the residual cover thickness around the bars and to the lower Standards Association of Australia; 1994.
[11] NZS 3101. Concrete structures standard, part 1 - the design
thermal conductivity of concrete. In addition, the influence of
of concrete structures. Wellington, NZS, New Zeland: New
the spalling degree on the temperature in the reinforcement
Zeland Standard; 1995.
steel bars was more noticeable after 120 min of testing. Until [12] ABNT 15200. Projeto de estruturas de concreto em situação
90 min of testing, the temperature difference between rein- de incêndio. Rio de Janeiro, RJ, Brazil: Associação Brasileira
forcing bars in the elements of different concrete mixtures de Normas Técnicas; 2012.
and different degrees of spalling was not significant, given the [13] Kodur VKR, Dwaikat MMS. Design equation for predicting
thermal protection that the residual cover thickness provided. fire resistance of reinforced concrete beams. Eng Struct
2011;33(2):602–14,
The results demonstrated an influence of the diameters
http://dx.doi.org/10.1016/j.engstruct.2010.11.019.
of reinforcing steel bars on concrete spalling. It was verified [14] Kodur V. Properties of concrete at elevated temperatures.
that the reinforcing bars with a diameter of 16 mm generated ISRN Civ Eng 2014;2014:1–15,
greater cross section losses in the columns than bars with a http://dx.doi.org/10.1155/2014/468510.
diameter of 10 mm. Furthermore, the duration of column’s fire [15] Robert F, Colina H, Debicki G. A durabilidade do concreto
performance of different mixing ratios and equal cross section mediante ao fogo. In: Durabilidade do Concreto. 1st ed. São
and disposition of reinforcing steel bars changed. Neverthe- Paulo: IBRACON; 2014. p. 509–58.
[16] Ju Y, Tian K, Liu H, Reinhardt HW, Wang L. Experimental
less, the average temperatures in the reinforcing bars obtained
investigation of the effect of silica fume on the thermal
a greater variation with an alteration in the concrete cover spalling of reactive powder concrete. Constr Build Mater
thickness and diameter of bars rather than in the concrete 2017;155:571–83,
mixture. http://dx.doi.org/10.1016/j.conbuildmat.2017.08.086.
[17] Shah AH, Sharma UK. Fire resistance and spalling
performance of confined concrete columns. Constr Build
Mater 2017;156:161–74,
Conflicts of interest http://dx.doi.org/10.1016/j.conbuildmat.2017.08.167.
[18] Gjørv OE. Durability design of structures in severe
The authors declare no conflicts of interest. environments. New York: Taylor & Francis; 2009.
j m a t e r r e s t e c h n o l . 2 0 2 0;9(3):4968–4977 4977

[19] Kodur VKR, Garlock M, Iwankiw N. Structures in fire: [31] ISO 834-1. Fire-resistance tests: elements of building
state-of-the-art, research and training needs. Fire Technol construction - part 1: general requirements. Geneve,
2012;48(4):825–39, Switzerland: International Organization for Standardization;
http://dx.doi.org/10.1007/s10694-011-0247-4. 1999.
[20] Morita T, Nishida A, Yarnazaki N, Schneider U, Diederichs U. [32] JIS A1304. Method of fire resistance test for strucutral parts of
An experimental study on spalling of high strength concrete buildings. Tokyo, Japan: Japanese Standard Association; 1994.
elements under fire attack. Fire Saf Sci 2000;6:855–66, [33] Majorana CE, Salomoni VA, Mazzucco G, Khoury GA. An
http://dx.doi.org/10.3801/IAFSS.FSS.6-855. approach for modelling concrete spalling in finite strains.
[21] Guo Z, Shi X. Experiment and calculation of reinforced Math Comput Simul 2010;80(8):1694–712,
concrete at elevated temperatures. Elsevier; 2011, 2011. http://dx.doi.org/10.1016/j.matcom.2009.05.011.
[22] Kyu PC, Hoon LS. Fire resistance of ultra high strength [34] Ali FA, O’Connor D, Abu-Tair A. Explosive spalling of
concrete columns with cover depth. In: Proceedings of high-strength concrete columns in fire. Mag Concr Res
International Conference ACF/VCA, 1002-1007. Viet Nam: 2001;53(3):197–204,
Institute for Building Materials; 2017. http://dx.doi.org/10.1680/macr.2001.53.3.197.
[23] Dwaikat MB. Flexural response of reinforced concrete beams [35] Tutikian BF, Isaia GC, Helene P. Concreto de Alto e Ultra-Alto
exposed to fire. Doctoral dissertation. Michigan State Desempenho. Concreto. Ensino, Pesquisa e Realizações, 1.
University; 2009. São Paulo: IBRACON; 2011. p. 1283–325.
[24] Ergün A, Kürklü G, Serhat BM, Mansour MY. The effect of [36] Kodur VKR, Dwaikat MMS. Effect of high temperature creep
cement dosage on mechanical properties of concrete on the fire response of restrained steel beams. Mater Struct
exposed to high temperatures. Fire Saf J 2013;55:160–7, 2010;43(10):1327–41,
http://dx.doi.org/10.1016/j.firesaf.2012.10.016. http://dx.doi.org/10.1617/s11527-010-9583-y.
[25] Mohd Ali AZ, Sanjayan J, Guerrieri M. Specimens size, [37] Wang G, Barber D, Johnson P, Hui MC. Fire safety provisions
aggregate size, and aggregate type effect on spalling of for aged concrete building structures. Procedia Eng
concrete in fire. Fire Mater 2017;42(1):59–68, 2013;62:629–38,
http://dx.doi.org/10.1002/fam.2457. http://dx.doi.org/10.1016/j.proeng.2013.08.108.
[26] Mehta PK, Monteiro PJM. Concreto: microestrutura, [38] Van Der Heijden GHA, Pel L, Adan OCG. Fire spalling of
propriedades e materiais. São Paulo: IBRACON; 2014. concrete, as studied by NMR. Cem Concr Res
[27] Dwaikat mB, Kodur VKR. Fire induced spalling in high 2012;42(2):265–71,
strength concrete beams. Fire Technol 2010;46(1):251–74, http://dx.doi.org/10.1016/j.cemconres.2011.09.014.
http://dx.doi.org/10.1007/s10694-009-0088-6. [39] FIB Bulletin n◦ 46. Fire design of concrete structures -
[28] Hertz KD. Limits of spalling of fire-exposed concrete. Fire Saf structural behavior and assessment. Lausanne, Switzerland:
J 2013;38(2):103–16, Fédération Internationale Du Béton; 2008.
http://dx.doi.org/10.1016/S0379-7112(02)00051-6. [40] FIB Bulletin n◦ 38. Fire design of concrete structures -
[29] Ali F. Is high strength concrete more susceptible to explosive materials, structures and modelling. Lausanne, Switzerland:
spalling than normal strength concrete in fire? Fire Mater Fédération Internationale Du Béton; 2007.
2002;26(3):127–30, http://dx.doi.org/10.1002/fam.791. [41] Kodur VKR, Yu B, Dwaikat MMS. A simplified approach for
[30] Tutikian BF, Helene P. Dosagem dos Concretos de Cimento predicting temperature in reinforced concrete members
Portland Concreto. Ensino, Pesquisa e Realizações, 1. São exposed to standard fire. Fire Saf J 2013;56:39–51,
Paulo: IBRACON; 2011. p. 439–71. http://dx.doi.org/10.1016/j.firesaf.2012.12.004.

You might also like