Professional Documents
Culture Documents
Arc Suppression Coil or Petersen Coil - Electrical4U PDF
Arc Suppression Coil or Petersen Coil - Electrical4U PDF
Ads by
Stop seeing this ad Why this ad?
SPONSORED SEARCHES
In underground high voltage and medium voltage cable network, there is always petersen coil is used for
a capacitance between conductor and earth in each phase. Because of that there is
explain arc suppression coil earthing
always a capacitive current from phase to earth. In each phase the capacitive
arc suspension coil
current leads the corresponding phase voltage by 900 as shown in figure – 2.
how does an arc suppression coil work
Now suppose there is an earth fault at yellow phase of the system. Ideally, the
voltage of yellow phase that is yellow phase to ground voltage becomes zero.
Thus, null point of the system is shifted at the tip of the yellow phase vector, as
shown in the figure-3, below. As a result, the voltage in healthy phases (red and
blue) becomes &sqrt;3 times of the original.
Ads by
Stop seeing this ad Why this ad?
Naturally, the corresponding capacitive current in each healthy phase (red and
blue) becomes &sqrt;3 of the original as shown in figure-4, below.
The vector sum that is resultant of these two capacitive current now will be 3I,
where I is taken as rated capacitive current per phase in the balanced system.
That means, at healthy balanced condition of the system, IR = IY =
IB = I.
The capacitive component of the fault current is high in the underground cabling
system. When earth fault occurs, the magnitude of this capacitive current
through the faulty path becomes 3 times more than rated phase to earth
capacitive current of healthy phase. This causes significant shifting of zero
crossing of current away from zero crossing of voltage in the system. Due to
presence of this high capacitive current in the earth fault path there will be a
series of re-striking at fault location. This may lead unwanted over voltage in the
system.
The inductance of the Petersen Coil is selected or adjusted at such value which
causes the inductive current which can exactly neutralize the capacitive current.
For that let us consider capacitance between conductor and earth in each phase of
a system, is C farad. Then the capacitive leakage current or charging current in
each phase will be
So, the capacitive current through the faulty path during single phase to earth
fault is
After fault, the star point will have phase voltage as the null point is shifted to
fault point. So the voltage appears across the inductor is Vph. Hence, the
inductive current through the coil is
Now, for cancellation capacitive current of value 3I, IL must have same
magnitude but 180o electrically apart. Therefore,
When, design or configuration (in length and/or cross section and/or thickness
and quality in insulation) of the system changes the inductance of the coil is to be
adjusted accordingly. That is why often Petersen coil is provided with tap
changing arrangement.
Ads by
Stop seeing this ad
About Electrical4U
...
Related Articles
Name *
Email *
Post Comment
We are a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a
means for us to earn fees by linking to Amazon.com and affiliated sites. Full disclaimer here.
© 2020 Electrical4U