UTION NETWORKS
Renato Cespedes G . , Senior Member, IEEE
Systems Control - Division of Power Automation. Cra. 4 No.69-45
Bogota, Colombia
Authorized licensed use limited to: Renato Cespedes. Downloaded on October 13, 2009 at 16:41 from IEEE Xplore. Restrictions apply.
392
Connectivity
branches nodes
1 -> 0
2 -> 1
3 -> 2
4 -> 3
5 -> 4
- 6 6 -> 1
7 -> 6
8 -> 6
8 9 -> 8
ft
FIGURE 1
Authorized licensed use limited to: Renato Cespedes. Downloaded on October 13, 2009 at 16:41 from IEEE Xplore. Restrictions apply.
393
-
(Source) 9 <- 8 2) Assume a voltage magnitude for each node
for the initial load estimation and
calculation of loads dependent on the voltage
111. RADIAL LOARJ?LQK magnitude.
3) Calculate the equivalent for each node
summing all loads of the network fed through
The solution proposed for the load flow the node, including losses. This is the
problem is to solve for every branch the "upstream" iteration, form end nodes to source
following basic equation (see details in nodes.
appendix A):
4) Starting from the source(s) node(s) and
Source Side Load Side using equation (3), calculate the load voltage
(Vr) for all loads. This is the "downstream"
vs Vr iteration, from source nodes to end nodes.
I I
I -> -I
I
I R + jX I
I
I
I 5) With the new voltages recalculate the
node s node r losses. If the total losses variation with
-
I
Authorized licensed use limited to: Renato Cespedes. Downloaded on October 13, 2009 at 16:41 from IEEE Xplore. Restrictions apply.
394
-
The last column in the previaua table also
presents the voltage magnitude results for
case No. described below.
The following table summarizes the convergency - Connect or disconnect capacitors modifying
found for these cases: the reactive load of the feeder.
Case No.1 Case No.2 For the first type of control it is necessary
Iter. delta P delta Q delta P delta Q to know the source voltage that is required in
1 0.298269 0.283743 0.329253 0.313220 case that one or more node voltage magnitudes
2 0.086390 0.082021 0.055621 0.052996 or out of limits. The required source node
3 0.000232 0.000220 0.014802 0.014094 shall maintain all voltages within limits.
4 0.004037 0.003844 The algorithm proposed for the constrained
5 0.001104 0.001051 load flow is based on the following:
6 0.000302 0.000287
a. All network loads have net lagging power
The convergence of case No.1 compares well factor, that is, they may include capacitors
with the same test run with the method but which compensate the reactive load to
presented in 141 which takes 6 iterations for maximum a power factor equal to 1.0.
solving the same case. However the solution by
the cbupled Newthon Raphson method is found to b. The lowest voltage magnitude, under the