You are on page 1of 10

Accelerat ing t he world's research.

Local Voltage-Stability Index Using


Tellegen's Theorem
Ivo Smon

IEEE Transactions on Power Systems

Cite this paper Downloaded from Academia.edu 

Get the citation in MLA, APA, or Chicago styles

Related papers Download a PDF Pack of t he best relat ed papers 

An adapt ive t hree-bus power syst em equivalent for est imat ing volt age st abilit y margin from …
Navin Bhat t

Est eban Tobon EPSR Feb2015


Juan M Ramirez

Índices Para Det ect ar en T iempo Real Problemas De Est abilidad De Volt aje
Mario A Rios
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 21, NO. 3, AUGUST 2006 1267

Local Voltage-Stability Index


Using Tellegen’s Theorem
Ivan Šmon, Student Member, IEEE, Gregor Verbič, Member, IEEE, and Ferdinand Gubina, Senior Member, IEEE

Abstract—In the paper, the Tellegen’s theorem and adjoint net- this reason, control-actions, time-range, quasi-steady-state
works are used to derive a new, local voltage-stability index. The time-domain simulations are used [3] to simplify matters. The
new approach makes it possible to determine the Thevenin’s pa- results of such studies can also be used for screening purposes
rameters in a different way than adaptive curve-fitting techniques,
from two consecutive phasor measurements. to identify critical cases that require a more detailed or dynamic
The new index was rigorously tested on different test systems. analysis [4].
The results were obtained on a static two-bus test system and on Most methods are based on executing a large number of
the dynamic Belgian–French 32-bus test system that includes full power flows using conventional models and the P-V or Q-V
dynamic models of all power-system components crucial to the curves at selected buses [5], [6]. Sensitivity methods based on
voltage instability analysis. The results show advantages of the
proposed index: it is simple, computationally very fast, and easy linearization around an operating point (the solved power-flow
to implement in the wide-area monitoring and control center or case) are usually repeated at several points along the P-V
locally in a numerical relay. or Q-V curves. Together with modal analysis [7], all these
Index Terms—Adjoint networks, local phasors, Tellegen’s the- methods use the system’s Jacobian matrix. To avoid uncertainty
orem, Thevenin’s equivalent, voltage-stability index. of the load-flow convergence, the continuation power flow [8]
allows tracing of the solution path passing through the loading
margin; this is the most widely accepted index for determining
I. INTRODUCTION the distance of the power system state to the voltage collapse.
Methods to assess the voltage stability of a power system, such
OWER systems are forced to operate ever closer to their as bifurcations, direct methods, energy functions, etc., can be
P load limits because of the demands of deregulated elec-
tricity markets. As a result, several blackouts have occurred due
found in the literature [2].
The main idea behind local methods is that the local phasors
to voltage instability. This means that voltage stability has be- contain enough information to directly detect the voltage-
come a matter of serious concern for system operators and is a stability margin using their measurements. This concept is
subject of a lot of investigation due to its importance in terms attractive, since real-time measurements of the voltage and
of the system security and power quality. Significant efforts are current phasors at the system buses are already available from
still being directed toward definitions, classifications, new con- the phasor measurement units (PMUs) installed in many power
cepts, practices, and tools for solving the voltage-stability and systems [9]. In addition to the benefits of small computational
security-analysis problems [1], [2]. effort and simplicity, local methods also give a very good
The voltage-instability problem is characterized by voltage insight into the voltage-collapse process and can easily be used
uncontrollability at certain locations in a power network after for online system monitoring.
a disturbance. The problem occurs more frequently in stressed The local method proposed by Strmčnik and Gubina [10] is
networks with reduced stability margins and/or reduced re- based on the power-system decomposition on reactive-power
active-power reserves. The voltage instability is basically a radial transmission paths modeled as two-bus equivalents.
dynamic phenomenon with rather slow dynamics and a time In addition to proximity to the voltage collapse, the method
domain ranging from a few seconds to some minutes or more. also considers exhaustion of the generator’s reactive-power
Although the voltage instability is a complex problem, it is very reserves. However, two indicators mean that the determination
important that system operators use quick, simple, and correct of the problem is not straightforward. Another weakness of
methods to calculate the distance to the worst case: the voltage this method is a complex identification of critical buses in
collapse. the system and the fact that the electric distance of the reac-
Many system-oriented approaches and long-term voltage-sta- tive-power source from the affected load bus is not considered
bility methods are based on static models because of the high when calculating the generator’s reactive-power reserve.
dimensionality and complexity of stability problems. For Verbič and Gubina [11] proposed a local method based on the
fact that, in vicinity of the voltage collapse, the entire increase
Manuscript received April 27, 2005; revised January 17, 2006. This work was
in the apparent power loading at the sending end of a line is due
supported by the Ministry of Higher Education, Science, and Technology of the to the supply of transmission losses. The main shortfall of this
Republic of Slovenia. Paper no. TPWRS-00254-2005. method lies in additional checking if the line is loaded below its
The authors are with the Laboratory of Power Systems and High Voltage, natural loading.
Faculty of Electrical Engineering, University of Ljubljana, SI-1000 Ljubljana,
Slovenia (e-mail: ivo.smon@fe.uni-lj.si). Vu et al. [12] proposed a local method based on the power-
Digital Object Identifier 10.1109/TPWRS.2006.876702 transfer impedance-matching principle. The measured data are
0885-8950/$20.00 © 2006 IEEE

Authorized licensed use limited to: UNIVERSITY OF SYDNEY. Downloaded on August 09,2010 at 01:09:49 UTC from IEEE Xplore. Restrictions apply.
1268 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 21, NO. 3, AUGUST 2006

used to obtain the Thevenin’s equivalent of the system, as seen and buses of the adjoint network. The incremented network is a
from the load bus, and the apparent impedance of the load. The base-case network subject to the set of the following.
voltage collapse occurs when these two impedances are equal. 1) Power disturbances: The power corresponding to a
The locally measured data and concepts of the Thevenin’s given bus is changed by . The set of power distur-
equivalent of the system are also used in [13] and [14], where bances is then
instead of the “impedance margin,” the authors express the prox-
imity to collapse in terms of the power margin. Julian et al. [13]
even show that adding the effects of the system dynamics means (3)
that the Thevenin’s concept can be used for the voltage-sta-
where is the index set of the buses where the disturbance
bility determination, including generator-excitation systems and
occurred.
voltage-frequency-dependent loads. References [13] and [15]
2) Network disturbances: The power system network is mod-
also report on feasibility studies relating to the development and
ified. The set of network disturbances is represented by the
implementation of these kinds of methods into voltage security
changes in the system-admittance matrix .
monitoring and control tools and techniques for large realistic
The only condition for validity of (2) is that the base-case net-
systems.
work and adjoint network are topologically identical. The
Milosević and Begović [16] combine the methods proposed
adjoint network is an artificial network, and since it is physically
in [10] and [12] for determining the voltage stability for mixed
decoupled from the base-case network, it remains unchanged
loads and propose a new index to control exhaustion of the
after disturbances in the system.
generator’s reactive-power reserves. All local voltage-stability
The concept of adjoint networks has been applied to online
methods [12]–[16] track the Thevenin’s parameters using pa-
voltage security assessment and the straightforward calculation
rameter-identification recursive algorithms.
of post-contingency voltages, sensitivities, and direct calcula-
In this paper, we propose a new approach to local voltage sta-
tion of the security indexes [18][19]–[20].
bility methods. Tellegen’s theorem and adjoint networks have
Derivations that follow are aimed at modeling an appropriate
been applied to many different areas; in this paper, we will
adjoint network, which will help in computing the system re-
show how they can be applied to solve the local voltage-stability
sponse due to disturbances anywhere in the system.
problem. The new approach makes it possible to simplify deter-
Let and be portioned into three groups of sub-
mination of the Thevenin’s parameters, which are calculated in
vectors indexed by the following:
a different way than adaptive curve-fitting techniques [12]–[16],
1) S set, corresponding to the slack bus;
from two consecutive phasor measurements.
2) P set, corresponding to all the remaining buses;
II. THEORETICAL BACKGROUND 3) B set, corresponding to all the network branches.
Using the above decomposition, (2) can be rewritten as
A. Tellegen’s Theorem and Adjoint Networks
Among circuit-theory theorems, the Tellegen’s theorem is
(4)
unusual in that it depends solely on the Kirchhoff’s laws and
topology of the network. The theorem therefore applies to all The slack buses in adjoint networks are modeled as short-cir-
electrical networks that obey Kirchhoff’s laws, whether they cuit lines or constant-voltage sources with the voltage .
are linear or nonlinear, time invariant or time variant, reciprocal The slack bus or infinite bus is assumed as a source of invari-
or nonreciprocal, and hysteretic or nonhysteretic; the excitation able frequency and voltage; thus, . That means that a
is arbitrary, and the initial conditions are also immaterial. The reference bus in (4) has no contribution
basic form of the Tellegen’s theorem [17] states the following
relationship between the complex voltages and complex cur-
(5)
rents flowing across all network elements:
We can argue that if we have only a slack bus and loads in the
system and that, by eliminating the slack bus, there is no gen-
(1)
erator in the system. However, we must keep in mind that if
The most interesting feature of (1) is that it is still valid, even we want to observe the voltage sensitivities on any element in
though the voltages and currents relate to two different networks the system, we must add an independent current generator in
of the same topology. This brings us to an expression better parallel to it. As an illustration, a simple example of a resistant
known as the difference form of Tellegen’s theorem [18] circuit and an exact adjoint network modeling [21] is shown in
Fig. 1. An independent current source must be added in par-
allel to the resistance .
(2) The final result for the normalized sensitivity of the
voltage on resistance using Tellegen’s theorem and an
where and represent the changes in the complex volt- adjoint network is
ages and currents corresponding to all the branches and buses
of the incremented network, and and represent the com-
plex currents and voltages corresponding to all the branches (6)

Authorized licensed use limited to: UNIVERSITY OF SYDNEY. Downloaded on August 09,2010 at 01:09:49 UTC from IEEE Xplore. Restrictions apply.
ŠMON et al.: LOCAL VOLTAGE-STABILITY INDEX USING TELLEGEN’S THEOREM 1269

Fig. 1. Simple resistant circuit and its exact adjoint network.

Similarly, by observing the current sensitivities, we add an


independent voltage source in parallel with the observed ele-
ment. We must also have in mind that accurate models of loads
and P-V buses in an adjoint network are voltage-controlled cur-
rent sources and current-controlled voltage sources, respectively
[18], [20]. In further derivations, we will need only basic equa-
tions; therefore, we will not use exact modeling anymore.
Equation (5) is further developed to obtain the voltage sensi- Fig. 2. General representation of load bus k in a power system, the corre-
tivities of system elements to power and network disturbances ^.
sponding network N, and its adjoint network N
[18], [20]. Network disturbances, , only have an influence
on the part of (5) associated with the branches
. On the other hand, the power disturbances affect only The receiving and sending currents for the power system as
the bus equations . The topology of the ad- shown in Fig. 2(b) are
joint network remains unchanged after network disturbances in
the system; thus, , and consequently
(11)

(7) Equation (11) can be rewritten as follows:

Considering (4), (5), and (7), the equation that follows is


(12)

(8) For a given power , the phasor equation (12) permits at


most two voltage solutions . Maximum power transfer occurs
Since the complex conjugation is a linear Kirchhoff operator, when these solutions become equal
(8) can be expressed as follows [22]:

(13)
(9)
Equation (13), which is the basis for the local voltage-stability
or method used in [10], leads us to an already-known result from
the circuit theory

(10)
(14)
Equations (9) and (10) are basic formulas for derivation of the
new local voltage-stability index. These equations will be ap- When the magnitude of the load impedance becomes equal to
plied on the Thevenin’s equivalent and its adjoint network to the magnitude of the Thevenin’s impedance, the system reaches
obtain the Thevenin’s parameters directly from two consecutive the maximum deliverable power [5]. Extensive field measure-
measurements or two respective states directly, without any re- ments reported by [23] have shown that normally, at least a part
cursive-parameter identification. of the load has constant power characteristics, and the max-
imum deliverable power then becomes a loadability limit. Past
B. Thevenin’s Equivalent this limit, there is a loss of equilibrium, and voltage collapse
Consider the bus having a complex load will occur [5]. Equation (14) therefore also denotes the stability
and complex impedance connected to the rest of limit.
the power system, as shown in Fig. 2(a). The rest of the power
system, treated as a Thevenin’s equivalent in Fig. 2(b), may C. Adjoint Thevenin’s Equivalent
consist of any number of generators, transmission lines, trans- The adjoint Thevenin’s network has the same topology as
formers with ULTCs, and loads. The Thevenin’s parameters are the base network , as shown in Fig. 2(c). Equations (11) –(14)
the Thevenin’s voltage and Thevenin’s impedance . can also be rewritten with a hat (^), which denotes the adjoint

Authorized licensed use limited to: UNIVERSITY OF SYDNEY. Downloaded on August 09,2010 at 01:09:49 UTC from IEEE Xplore. Restrictions apply.
1270 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 21, NO. 3, AUGUST 2006

network variables. According to (9), the difference form of the Equation (22) is indeed a conjugated (21). To eliminate the con-
Tellegen’s theorem is equal to jugate values, the absolute value of the Thevenin’s impedance
is defined as follows:

(15)
(23)
where and represent the complex voltage and current
increments for the bus with respect to their base-case values Note that and can only be identified if the system’s
and . The increments are determined after the base-case operating point changes. Hence, it is evident that the Thevenin’s
network in Fig. 2(b) is subjected to the set of disturbances in the parameters are not constant values and can be directly deter-
system. and represent the complex current and voltage mined at every new changed situation in the system. The situa-
corresponding to the bus of the adjoint network. tion where the system’s operating point does not change is not
When we have real online measurements, and are critical for the voltage stability and should be disregarded.
the voltage and current differences between the two consecutive In the case of normal loading, the condition
measurement samples from a PMU at the bus .
While the adjoint network is topologically identical to the
(24)
base-case network, the characteristics of the elements in each
of them can be arbitrary. The load impedance of the adjoint holds. At the onset of voltage instability, the difference between
network is defined as the ratio of the voltage and current these impedances approaches zero, and at the voltage collapse,
phasors at the bus both impedances have the same value

(16)
(25)
Note that the load impedance (16) refers to the base-case net- III. VOLTAGE-STABILITY INDEX
work and is calculated at the moment before the network has
As noted in the introduction, local methods based on tracking
been subjected to the power disturbances
the Thevenin’s parameters [12]–[16] use recursive parameter-
identification algorithms to determine them.
(17) Our newly proposed method identifies the Thevenin’s
impedance directly by calculating the voltage and current
Substituting into (15) and taking into consideration (11) can increments (23) after the base-case network is subjected to a
derive the adjoint Thevenin’s impedance set of disturbances in the system. On the other hand, the load
impedance can also be determined simply from the ratio of the
voltage and current (17). Considering (24) and (25), a simple
(18) normalized impedance-stability index (ISI) for determining the
voltage-stability margin can be defined as
Equation (18) could be rewritten as follows:

ISI (26)
(19)
Substituting the impedances with voltages and currents (25), the
Considering (13), the maximum power transfer in the adjoint ISI can also be written as
Thevenin’s network occurs when
ISI (27)
(20)
In prevailing operating conditions, condition (24) holds. This
condition can also be written as
Comparing (19) and (20), the Thevenin’s impedance at the
voltage-collapse point is simply
(28)
(21) or
This result is of fundamental importance. The Thevenin’s
impedance can be easily calculated as the ratio between (29)
and . Using (10) and (11), we could also derive
Therefore, under normal loading, the ISI takes values around 1.
At the voltage-collapse point ( ), the ISI diminishes
(22) to 0.

Authorized licensed use limited to: UNIVERSITY OF SYDNEY. Downloaded on August 09,2010 at 01:09:49 UTC from IEEE Xplore. Restrictions apply.
ŠMON et al.: LOCAL VOLTAGE-STABILITY INDEX USING TELLEGEN’S THEOREM 1271

Fig. 3. Load (Z
^ ) and Thevenin’s impedance (Z^ ) of the two-bus test system. Fig. 4. Local voltage-stability index, ISI, based on the Tellegen’s theorem of
the two-bus test system.

A careful reader may observe that the ISI is actually a gener-


alization of the criterion named SDC, proposed in [11].

IV. EXAMPLES
The derived formulas and proposed index was tested on a
simple static two-bus test system using continuation power flow
(CPF) [24] and on the dynamic Belgian–French 32-bus meshed
test system. In the latter case, full dynamic models of the system
components crucial to the long-term voltage stability phenom-
enon were used.

A. Two-Bus Test System


The two-bus test system consists of the generator that sup-
plies local load bus over the branch . The assumed pa-
rameters of this system are p.u.
p.u., and MVA. The CPF result Fig. 5. Belgian–French 32-bus test system.
shows that the maximum deliverable power is 487.5 MW.
The Thevenin’s and load impedance are calculated using (17)
and (23), respectively. The results are plotted in Fig. 3. in the EUROSTAG. More details on the system modeling, sce-
It can be seen from Fig. 3 that the Thevenin’s impedance has nario, and simulation results can be found in [26].
a constant value of 0.05 p.u. for all load levels and is basically The system represents a simplified 400-kV and 150-kV
equal to the line impedance . It is also evident Belgian–French system from the early 1980s. The external
that, under normal loading, the load impedance is much greater system is modeled by means of three infinite buses. Two impor-
than the Thevenin’s impedance. At the voltage-collapse, these tant power stations, N1 and N10, produce most of the power.
impedances are equal, which confirms that (25) holds true. The global load of the system is mainly located at the subtrans-
The newly proposed local voltage-stability index based on the
mission level, downstream the 150/70-kV ULTC transformers.
Tellegen’s theorem for load bus is plotted in Fig. 4. During the
The loads connected to buses N201-N207 consist of a mix of
voltage-collapse, the ISI approaches 0.
induction motors, constant impedance loads, and compensation
capacitors. Buses N203 and N205 are located in the “southern”
B. Belgian–French 32-Bus Test System part of the system and the others in the “northern” part.
The Belgian–French 32-bus test system displayed in Fig. 5 This 32-bus meshed system undergoes a 2-h load pickup
was first used in [25] and [26] to demonstrate the mechanisms of 30% followed by tripping of the north international tie line
leading to the voltage-collapse. The same system was later used N16-N3 at 5000 s. The system transiently recovers from this
in [2] as a benchmark for comparison of the voltage stability in- “large” contingency. At the time 7400 s, unit M2 trips for un-
dexes proposed so far. Time-domain simulation was performed known reasons. Because of this trip and action of the automatic

Authorized licensed use limited to: UNIVERSITY OF SYDNEY. Downloaded on August 09,2010 at 01:09:49 UTC from IEEE Xplore. Restrictions apply.
1272 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 21, NO. 3, AUGUST 2006

Fig. 7. Belgian–French 32-bus test system, load and Thevenin’s impedance as


Fig. 6. Belgian–French 32-bus test system, voltage at bus N204.
seen from bus N204, I1 = 0 015
: p.u.

tap-changers, the rotor current limit of the unit M1 is reached.


The limiter is ill tuned and reduces drastically the excitation,
provoking the loss of synchronism of the unit M1 about 2 min
after M2 tripping. After this second unit tripping, the voltage
on the terminals of the other units is progressively reduced
because of further tap-changes and rotor current limiter actions.
The remaining generating units successively trip by under the
voltage protection or by loss of synchronism, leading to the
final blackout of the system, as depicted in Fig. 6.
It can be observed in Fig. 6 that the time profile of the
voltage magnitude is not a good way of detecting the prox-
imity to collapse, since it remains very much unaffected by
system contingencies.
As we stated before, the equivalent Thevenin’s impedance
can only be identified if the system’s operating point changes,
since the division with 0 is not allowed. The new Thevenin’s
impedance is calculated if the load current difference between
Fig. 8. Belgian–French 32-bus test system, Thevenin’s voltage as seen from
two operating points, , is greater than the predefined bus N204, I1 = 0 015
: p.u.
threshold. The threshold magnitude defines sensitivity of the
ISI to different changes in the system. The threshold
used here was experimentally set to 0.015 p.u. Choosing the over the calculation window. In case of any corrective actions
appropriate threshold will be further discussed in Section V. applied to the systems, the average value of load impedance sig-
The load impedance and Thevenin’s impedance, which is nificant increases, and every calculated Thevenin’s impedance
reflecting the network structure changes, load changes, tap must be accepted. In our case, no corrective action has been ap-
changer action, and rotor current limiter action, are calculated plied; therefore, the average load impedance has not been calcu-
using (17) and (23) at every integration step, which varies from lated. In the real environment, the above procedure will be used
0.001 to 35s. The results for the bus N204 are plotted in Fig. 7. if analyzing the fast system dynamic only. The PMUs use con-
The integration step is reduced to very small values during stant sample rates, and more tests on real systems are required to
the fast dynamics in the system, excited by discrete changes determine the length of the impedance calculation window that
of the voltage set point, tap position, and tripping of the line. should be used. The PMUs’ sample rates are further discussed
These transients are already reflected in the shape of the load in Section V.
impedance. At the Thevenin’s impedance oscillations, its Once knowing the Thevenin’s impedance, the Thevenin’s
highest value is considered, and its new calculated value is voltage is simultaneously calculated using (11). The result for
accepted if it is higher than the previous one, which means that the bus N204 is shown in Fig. 8.
only the worst case is tracked. The ISI changes versus time for buses N204 and N205 are
To consider any corrective actions applied to the system, it is plotted in Fig. 9. ULTCs, voltage support devices limits, and
necessary to observe the average value of the load impedance loss of the line N16-N3 produce sharp changes of the ISI. In all

Authorized licensed use limited to: UNIVERSITY OF SYDNEY. Downloaded on August 09,2010 at 01:09:49 UTC from IEEE Xplore. Restrictions apply.
ŠMON et al.: LOCAL VOLTAGE-STABILITY INDEX USING TELLEGEN’S THEOREM 1273

Fig. 10. Belgian–French 32-bus test system, bus N204, the ISI changes versus
Fig. 9. Belgian–French 32-bus test system, buses N204 and N205,
1
time for transient system response at 5000 s, I = 0 015
: p.u.
new local voltage-stability index, ISI, based on the Tellegen’s theorem,
1 I = 0 015
: p.u.
to 0.65 or higher, depending on the desired tolerance level, in
order to make additional corrective and/or coordinated actions
cases, the index was normalized with respect to the initial values in critical areas possible before the system collapses.
of the load and Thevenin’s impedances.
Observe in Fig. 9 that the bus N205 located in the “southern” V. PRACTICAL APPLICABILITY
part of the system is not severely affected by tripping of the north The proposed index can be applied in at least two different
international tie-line N16-N3 at 5000 s. The sharp changes at ways: as a part of wide-area monitoring and control (WAMC)
times 1500, 5214, 5277, 5499, and 6100 s are due to the op- system (center) [27], where coordinated system-wide control
eration of transformer ULTCs located in the “southern” part or action can be undertaken, or locally in a numerical relay, where
very close “northern” part of the system. At 7400 s when unit actions can be taken in real time without sending any data to the
M2 trips, the load has already exceeded the maximum deliver- control center.
able power of the system without units N16 and M2 [2]. The The proposed index requires voltage and current phasors pro-
stability boundary is crossed as indicated by ISI = 0, and the vided by the PMUs to evaluate the system’s voltage stability.
system collapse progresses rapidly after that point. Just before When calculating them in real time, it is important to consider
the voltage-collapse, the ISI is still relatively high due to reac- several issues, such as noise, redundancy, bad data detection,
tive power support from the “southern” generators, and this bus phasor sample rate, accuracy of the representation of included
is considered as not being critical. The shapes of the ISIs for information, out-of-band rejection, and measurement delay. The
both “southern” buses N203 and N205 are very similar. last four data requirements are actually the main considerations
On the contrary, tripping of the line N16-N3 strongly affects in PMUs’ designing problems [28]. Redundancy aspects and
bad data detection algorithms are well discussed in [27] and
the “northern” part of the system, as shown in Fig. 9, where
[29], respectively.
the ISI for the bus N204 indicates a reduction of the voltage-
The phasor measurement process in a PMU can be broken
collapse margin. The ISI is reduced to 0.2, which reveals that
into two subprocesses. The first is sampling the voltage and cur-
the bus N204 is a part of the critical “northern” area, which is
rent waveforms, and the second is the phasor calculation. The
also demonstrated in [2]. The smaller sharp changes are again
waveform-sampling rate must be high enough to make a good
due to the transformer ULTCs action. reproduction of the waveform. It requires analog antialiasing
The voltage-instability problem is characterized by the filtering before sampling. The Nyquist criterion limits the in-
voltage uncontrollability at certain locations in a power system. formation bandwidth to half the sample rate, and additional fil-
Sharp reductions in the ISI indicate a reduction of collapse tering may be required. Current PMUs use waveform sampling
margin. Hence, the corrective actions, such a blocking of at maximum 2880 samples/s. Phasor calculation sample rates
the tap changers, triggering of voltage increase signals at the of 10 samples/s are adequate for real-time operator monitoring
selected nearest generators or at compensating devices, and and response and for a fast dynamic response; 20 samples/s is
load-shedding activation at the affected buses can be directly the minimum data rate that should be used.
associated with the sharp index changes. When corrective In our test case, the waveform and phasor sample rates were
actions should be applied, an ISI threshold can be defined the same and varied from 0.03 to 1000 samples/s rate. The
heuristically based on the historical data, on offline stability, on system transient recovery of the north international tie-line
contingency studies, and on operator’s experience. The results N16-N3 tripping at 5000 s reflects in the ISI time response, as
in Fig. 9 suggest that the ISI threshold should be set at least shown in Fig. 10, which is actually an enlarged part of Fig. 9.

Authorized licensed use limited to: UNIVERSITY OF SYDNEY. Downloaded on August 09,2010 at 01:09:49 UTC from IEEE Xplore. Restrictions apply.
1274 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 21, NO. 3, AUGUST 2006

REFERENCES
[1] IEEE/CIGRE, Joint Task Force on Stability Terms and Definitions,
“Definition and classification of power system stability,” IEEE Trans.
Power Syst., vol. 19, no. 3, pp. 1387–1401, Aug. 2004.
[2] Voltage stability assessment: Concepts, practices and tools, ISBN
0780378695, 2002, IEEE/PES, Power System Stability Subcommittee
C. Cañizares (Editor/Coordinator).
[3] T.Van Cutsem and C. Vournas, Voltage Stability of Electric Power Sys-
tems. Norwell, MA: Kluwer, 1998.
[4] G. K. Morison, B. Gao, and P. Kundur, “Voltage stability analysis using
static and dynamic approaches,” IEEE Trans. Power Syst., vol. 8, no.
3, pp. 1159–1171, Aug. 1993.
[5] C. W. Taylor, Power System Voltage Stability. New York: McGraw-
Hill, 1994.
[6] P. Kundur, Power System Stability and Control. New York: McGraw-
Hill, 1994.
[7] B. Gao, G. K. Morison, and P. Kundur, “Voltage stability evaluation
using modal analysis,” IEEE Trans. Power Syst., vol. 7, no. 4, pp.
1529–1542, Nov. 1992.
[8] V. Ajjarapu and C. Christy, “The continuation power flow: A tool for
steady state voltage analysis,” IEEE Trans. Power Syst., vol. 7, no. 1,
pp. 416–423, Feb. 1992.
[9] A. G. Phadke, “Synchronized phasor measurements in power systems,”
IEEE Comput. Appl. Power, vol. 6, no. 3, pp. 10–15, Apr. 1993.
Fig. 11. Belgian–French 32-bus test system, bus N204, the ISI changes versus
1
time for different white noise SNRs, I = 0 015
: p.u.
[10] F. Gubina and B. Strḿčnik, “A simple approach to voltage stability
assessment in radial networks,” IEEE Trans. Power Syst., vol. 12, no.
3, pp. 1121–1128, Aug. 1997.
[11] G. Verbič and F. Gubina, “A new concept of voltage-collapse protec-
tion based on local phasors,” IEEE Trans. Power Del., vol. 19, no. 2,
The relative small changes of the ISI at 5036 and 5040 s are pp. 576–581, Apr. 2004.
due to the ULTCs’ operations. [12] K. Vu, M. M. Begovič, D. Novosel, and M. M. Saha, “Use of local mea-
surements to estimate voltage-stability margin,” IEEE Trans. Power
To make the simulation more realistic, white noise with a Syst., vol. 14, no. 3, pp. 1029–1035, Aug. 1999.
signal-to-noise ratio (SNR) of 75 and 55 dB, respectively, was [13] D. E. Julian, R. P. Schulz, K. T. Vu, W. H. Quaintance, N. B. Bhatt,
and D. Novosel, “Quantifying proximity to voltage collapse using the
added to the phasor measurements before calculating the ISI. voltage instability predictor (VIP),” in Proc. IEEE Power Eng. Soc.
The results for different SNR ratios are plotted in Fig. 11. Ob- Summer Meeting, Seattle, WA, Jul. 2000, vol. 2, pp. 931–936.
[14] M. H. Haque, “On-line monitoring of maximum permissible loading of
serve in Fig. 11 that voltage collapse is properly determined for a power system within voltage stability limits,” Proc. Inst. Elect. Eng.,
SNR of 75 dB or more. When the white noise with SNR of 80 dB Gen., Transm., Distrib., vol. 150, no. 1, pp. 107–112, Jan. 2003.
is added, the ISI does not differ from the base case without noise. [15] W. H. Quaintance, K. Uhlen, D. E. Julian, J. O. Gjerde, K. T. Vu,
and L. K. Vormedal, “Raising energy transfer in corridors constrained
If the SNR is less then 70 dB, then results are not adequate. by voltage instability-Statnett case,” in Proc. IEEE Power Eng. Soc.
As discussed before, the magnitude of the threshold Summer Meeting, Seattle, WA, Jul. 2000, vol. 4, pp. 16–20.
[16] B Milosevič and M. Begovič, “Voltage-stability protection and con-
defines sensitivity of the ISI to different changes in the system. trol using a wide-area network of phasor measurements,” IEEE Trans.
The problem of not choosing the appropriate threshold is Power Syst., vol. 18, no. 1, pp. 121–127, Feb. 2003.
[17] B. D. H. Tellegen, “A general network theorem, with applications,”
actually very similar to the problem of adding white noise of Philips Res. Rep., vol. 7, pp. 259–269, 1952.
SNR less than 75 dB. If the threshold value is chosen [18] L. A. F. M. Ferreira, “A network-based approach to power system secu-
less than 0.015, the ISI is more sensitive to smaller changes in rity assessment and control,” Ph.D. dissertation, Georgia Inst. Technol.,
Atlanta, GA, 1986.
the system, and the algorithm gets more conservative. General- [19] A. S. Debs, Modern Power System Control and Operation. Norwell,
ization of the threshold to be used on any system would MA: Kluwer, 1988.
[20] F. Gubina, R. Golob, and A. S. Debs, “Fast contingency evaluation by
require more tests on different test systems and real systems means of the improved adjoint network method,” Int. J. Elect. Power
taking into account the above discussed issues of real-time Energy Syst., vol. 18, no. 6, pp. 377–383, 1996.
[21] S. W. Director and R. A. Rohrer, “The generalized adjoint network and
phasor measurements. network sensitivities,” IEEE Trans. Circuit Theory, vol. CT-16, no. 3,
pp. 318–323, Aug. 1969.
[22] P. Penfield Jr, R. Spence, and S. Duinker, “A generalized form of Tel-
VI. CONCLUSION legen’s Theorem,” IEEE Trans. Circuit Theory, vol. CT-17, no. 3, pp.
302–305, Aug. 1970.
In this paper, a new solution to the problem of voltage sta- [23] D. Karlsson and D. J. Hill, “Modeling and identification of nonlinear
bility is presented. The Tellegen’s theorem makes it possible dynamic loads in power systems,” IEEE Trans. Power Syst., vol. 9, no.
to simplify the determination of the Thevenin’s parameters and 1, pp. 157–163, Feb. 1994.
[24] F. Milano, Power System Analysis Toolbox (PSAT), 2005. [Online].
enables derivation of the new index. It requires the voltage and Available: http://www.power.uwaterloo.ca/̃fmilano/.
current phasors measurements only, to evaluate the system’s [25] N. D. Hatziargyriou and T. Van Cutsem, Eds., “Indices predicting
voltage collapse including dynamic phenomena,” Dec. 1994, CIGRE
voltage stability at a bus, which makes it very appealing for Task Force 38-02-11.
PMU-based online monitoring and protection schemes. [26] CIGRE Task Force 38-02-08, M. Stubbe (Convener), “Long Term Dy-
The advantage of the proposed method based on two consec- namics Phase II,” Mar. 1995.
[27] M. Zima, M. Larsson, P. Korba, C. Rehtanz, and G. Andersson, “De-
utive phasor measurements over alternative approaches is the sign aspect for wide-area monitoring and control systems,” Proc. IEEE,
one-step calculation procedure. It can also be used in systems vol. 93, no. 5, pp. 980–996, May 2005.
[28] J. A. de la O Serna and K. E. Martin, “Improving phasor measurements
where the fast dynamics are not neglected but needs a careful under power system oscillations,” IEEE Trans. Power Syst., vol. 18, no.
procedure to suppress oscillations of the estimated Thevenin’s 1, pp. 160–166, Feb. 2003.
[29] K. Holbert, G. T. Heydt, and H. Ni, “Use of satellite technologies for
parameters and considering any corrective action applied to the power system measurements, command, and control,” Proc. IEEE, vol.
system. 93, no. 5, pp. 947–955, May 2005.

Authorized licensed use limited to: UNIVERSITY OF SYDNEY. Downloaded on August 09,2010 at 01:09:49 UTC from IEEE Xplore. Restrictions apply.
ŠMON et al.: LOCAL VOLTAGE-STABILITY INDEX USING TELLEGEN’S THEOREM 1275

Ivan Šmon (S’02) was born in Jesenice, Slovenia, Waterloo, ON, Canada, as a NATO-NSERC Postdoctoral Fellow. His research
in 1976. He received the Diploma Engineer degree activities are power system operation, dynamics, and control.
in electrical engineering from the University of
Ljubljana, Ljubljana, Slovenia, in 2001.
After graduation, he was with the “Elektro
Gorenjska” Distribution Company for one year. He Ferdinand Gubina (SM’73) was born in Slovenia
is currently a Research Assistant with the Faculty in 1939. He received Diploma Engineer, M.Sc., and
of Electrical Engineering, University of Ljubljana. Dr.Sc. degrees from the University of Ljubljana,
His research interests lie in the area of power-system Ljubljana, Slovenia, in 1963, 1969, and 1972,
stability. respectively.
In 1970, he joined Ohio State University,
Columbus, for a year, as a Teaching and Research
Associate. Since 1988, he has been a Full Professor
Gregor Verbič (M’98) received the Electrical at the University of Ljubljana. His main interests lie
Engineer diploma and the M.S. and Ph.D. degrees in the area of electric-power system operation and
in electrical engineering from the University of control.
Ljubljana, Ljubljana, Slovenia, in 1995, 2000, and Dr. Gubina served in the CIGRE SC-39, SC-38, SC-4, and in CIGRE Ad-
2003, respectively. ministrative Council and Technical Committee. He is a Distinguished Member
He joined Korona Power Engineering in 1995, of CIGRE Paris.
where he worked for three years. He is now a
Teaching Assistant with the Faculty of Electrical
Engineering, University of Ljubljana, and he also
is currently with the Electrical and Computer
Engineering Department, University of Waterloo,

Authorized licensed use limited to: UNIVERSITY OF SYDNEY. Downloaded on August 09,2010 at 01:09:49 UTC from IEEE Xplore. Restrictions apply.

You might also like