Professional Documents
Culture Documents
Abstract— This paper describes methods used to analyze interaction between an active source a corresponding
power system transients. Overvoltage analysis techniques are the active and reactive power demand at the
evaluated. The complete system, including power cables and fundamental frequency by the reactance sub transient.
power generation is simulated using the ATP version of the • Power factor correction (PFC) capacitance should be
Electromagnetic Transient Program (EMTP) in addition with
estimated as accurately as possible and allocated at the
several experimental cases. A new method to power quality
analysis, and detection of switching of the reclose rele and cable corresponding voltage level [1].
voltage reflections using wavelets, is proposed. Comparisons • Other elements, such as, inductors, filters and
between the power cable models are included. Experimental generators should be represented according to their
results of adverse effects in a power generation distributed along concentrated parameter equivalent such a R,L;C series
the feeder and power cables from transmission lines are shown. circuit.
• The representation should be detailed a long of the
Keywords—Wavelets; ATP-EMTP; Reclose; Power cable; distribution line. Simpler equivalents, either for the
Transients.
transmission and distribution systems don´t should be
used.
I. INTRODUCTION • For distribution system studies all the elements may be
The major difficulty in calculating transient voltages assumed to be uncoupled three-phase branches with no
and currents throughout a distribution system is the need for an mutual, but allowing unbalanced parameters per
adequate equivalent to represent the distribution generation (DG) phase.[1]
system, line transmission and transformer machine from A distribution system is detailed as a block diagram in
consumers' loads fed radially from each busbar. the figure 1. The distribution circuit configuration depends on
It is to see that the use of equivalents circuit without a the particular load requirements. In general, a considerable
comprehensive check on the effect of all impedances actually number of loads are located so close together and supplied from
present can lead to inaccurate estimation of transient over the main distribution point, that they can be considered from a
voltages and currents in the transmission system. On the other circuit breaker due the energy benchmarking to produce the
hand, it is not practicable to obtain and represent all the system transient. For the majority of Distributed Generation installation,
details. whether supplying a small factory, domestic/commercial
A detailed analysis of distribution systems, loads and consumers, or a large plant, a simple radial system is used. A
other system elements is carried out, models discussed and a typical modern distribution network is shown in Figure 2.
simple but more realistic approach adopted It consists basically
of representing the dominant characteristics of the network using
alternative configurations and models. Also simpler equivalents
for extended networks are suggested [1].
The basic assumptions used in this paper are as follows:
• Distribution lines and cables (say, 33 – 13.2kV, for
example) should be represented by an equivalent pi
using the Bergeron approach [2]. For short lines, it is
not possible to estimate the total capacitance at each
voltage level due the big error in the transient Fig. 1. Block diagram of the power distribution system
estimation.
• Transformers between distribution voltage levels
should be represented by a no-linear saturation II. CABLE MODELING
inductance. The transient behavior of cables has been documented in
• The rotating machines can be represented by the detail in many textbooks and papers [2]-[4], [8]. ATP includes
1. E.A. Cano Plata is Full Professor at the Universidad Nacional de routines to compute parameters and to simulate cable transients
Colombia, Manizales, 170003 Colombia (e-mail: [13]. Series impedance and shunt susceptance matrices are
eacanopl@unal.edu.co). computed from cable parameter routines, using multiport
2. H.Tacca is Full Professor at Universidad de Buenos Aires Paseo theory. Boundary conditions like cables transposition or earth
colón 850 1er piso CABA(e-mail: htacca@fi.uba.ar).
3. F. Bertolotti, JTP at the Universidad de Buenos Aires Paseo colón
850 1er piso CABA(e-mail: fbertol@fi.uba.ar).
2
setting can be included. Finally, two options for transient III. EVALUATION OF MITIGATION METHODS
simulation are possible lumped parameter models (cascade π There are many mitigation techniques which might be
circuits) or distributed parameters models.
employed to solve different problems in the system, however
consider the power cables overvoltage’s can occur at the
terminals of the load. In this work, behavior of two solutions
methods [14] when the power cable is considered were
explored:
1) A capacitor in parallel with the load, at the circuit
breaker terminals. It works as a passive low pass filter.
2) A line RLC filter at the cable connection. It works as
low pass filter in the output of the feeder.
The major disadvantages of passive filtering are: they are
expensive, they require extra mounting space, and they
introduce extra losses in the system. And they are designed at
frequency to be filtered (depends on the load at the feeder ).
Fig. 2. Tipical distribution system whit distributed generation (DG)
The system under test for the simulation are composed of
Cascade π-sections computed at a given frequency [4] are an AC source and four loads are connected at different times,
computationally fast. Although this model does not include the capacitor bank and the RLC filter are connected to the
frequency dependent parameters, a frequency dependent loads in order to correct different problems. In Fig. 3 voltage
behavior is achieved by the cascade connections. at load terminals is shown. The simulation does not include a
However, lumped circuits are not a good representation of power cable. The effect of the transient recovery voltage
distributed parameter effects. For example, when travel waves action without switching transient can be seen. Voltages,
or switching transients on a long power cable appears. If the including cables of 500 and 1000 meters are shown in fig. 4
particular problem includes high frequencies, a great number of and 5. Sharp peaks from cable and load interaction are very
π circuits must be used. Numerical error can appear due to big important.
differences of the π parameters respect to the network.
A. Output Line Capacitors
3 Output line capacitor is a low-cost method of conditioning
the feeder output voltage. It reduces the harmonics injected to
the load, and therefore it will reduce the dv/dt seen at the load
terminals. Lumped capacitor joined to load inductance
introduces oscillations and a voltage overshooting. They are of
2
lower frequencies than pulses. They increase first peak voltage
Voltage in pu
12 B. RLC filter
[kV]
10 This filter uses output inductors, shunt capacitors and
8
damping resistors (when necessary) to form a conventional
low-pass filter. High-frequency harmonic currents are short-
6
circuit. Lower-frequency fundamental current pass to the
4 motor.
2
The result is a near sinusoidal wave being applied to the
load in terms of both, voltage and current. It can be seen in
-0,2
15 16 17 18
(file CASO2_Systema_PC_500m.pl4; x-var t) v:1A
19 20 [ms] 21 Fig. 8.
It is important to remark that:
Fig. 5. Simulation with 500 meters of power cable 1) No transient overvoltage appear at the terminal of the
load (see curve A in Fig.9).It is a new transient, the
12 magnetizing current it is referred at the inductor´s load
[kV]
10 that is showed in curve B in the Fig. 9
8
-0,2
15 16 17 18 19 20
(file CASO3_System_PC_1000m.pl4; x-var t) v:X0014A [ms] 21
20
[kV]
15
Fig. 9. Magnetizing current inrush (curve B) and voltage (curve A) from an
10 inductor
-0,2
15 16 17
(file caso5_system_pc_1000m_rlc.pl4; x-var t) v:X0011A
18 19 20 [ms] 21
The figures 11 and 12 show the wave shapes of voltages at V. POWER QUALITY ANALYSIS TECHNIQUE
load terminal without power cables.
A. Multiresolution Analysis
In multiresolution signal decomposition (MSD), wavelet
functions and scaling functions are used as building blocks to
decompose and construct the signal at different resolutions
levels [20]. The wavelet function will generate the detail
version of the decomposed signal and the scaling function will
generate the approximated version of the decomposed signal.
This mathematically can be presented as:
f ( t ) = c jo, k φ ( t − k ) +
k k k
j −1
(
d j ,k 2 j 2ψ 2 j t − k ) (1)
Where, Cjok is the “jo” level scaling coefficient and djk is the
wavelet coefficient at scale “j”. φ(t) and ψ(t) are the scaling
Fig. 11. Transient voltage at hidroelectric machine terminals without function and wavelet function respectively and k is the
considering power cable
translation coefficient.
Figures 11 and 12 show the wave shapes of voltages at load The translated function and scaled version of the wavelet,
terminals with power cables. The long power cable was ψ(2jt-k), (both used in MSD) will give a time-frequency
simulated by series connection of model 1 and model 2. picture of the decomposed signal.
Multiresolution signal decomposition is used to obtain two
important capabilities: The first one is the time localization
capability for any transient phenomena, which will be noticed
by the presence of large coefficients at the time of disturbance.
The second capability is the signal energy partition in different
frequency bands, which gives some idea of the frequency
content of the distorted signal.
B. Wavelet Transforms of the Signals it and vt
The power signals may be represented by the
multiresolution analysis as follows: If it the current of the
system and vt the voltage of the system represent square-
integral density functions (it, vt ε L2), they can be represented
as
it = c jo, k ,t φ jo, k ( t ) + d j , k ,tψ j , k ( t ) (2)
Fig. 12. Voltage at load terminals without consider power cable k j ≥ j0 k
where
Reflection wave’s detected using model 1 for the long
power cable simulation are depicted in figure 13. c jo, k ,t = it , φ jo, k and d j , k ,t = it ,ψ j , k (3)
vt = c ' jo, k ,t φ jo, k ( t ) + d ' j , k ,t ψ j , k ( t ) (4)
k j ≥ j0 k
transient produced by the capacitor switching in the first levels The measurements given the technique pqAT at each point
of the MSD analysis. At the transient produced near 10 ms in of connection is shown in the Fig 15 for real power and in the
the four levels, it can be produced a change at the polarity. Fig 16 for reactive power.
Caso 11:Descomposi
Decomposition ción de la energy
of the actual energía real Epmeasured
medida en la Subestaci
in the ón substation As it can be seen, in the reactive power there is a change in
2000 the polarity in the capacitor, therefore it could be needed an
Nivel 1
Level 1
0
-2000 x 104 scheme considering bi-directional flows; this reaction could be
10 0.05 0.1 0.15 0.2 0.25 0.3 misunderstood as a fault.
0 Nivel 2
Level 2 5
x 10 Real Power
-1 x 104 20
50 0.05 0.1 0.15 0.2 0.25 0.3 Load B
Capacitor
0
4
Nivel 3
Level 3 Load C
-5 x 10 15 Source
10 0.05 0.1 0.15 0.2 0.25 0.3 Load D
0 Load A
-1 Nivel 4
Level 4
-2
-3
10
1500 0 0.05 0.1 0.15 0.2 0.25 0.3
1000
Watts
500
0 Nivel 5
Level 5
-500 5
x 10 0.05 0.1 0.15 0.2 0.25 0.3
5
Time [seconds]
RDD _ p =
Pmean 4
(8)
VAR
Qstd
RDD _ q = 2
Qmean
0
Pmean = active power
Pmean = reactive power
-2
4000
Real Power of coefficients (the noise/signal curve), allows the right
Not cable present. physical characterization of the kind of reflection wave in the
π model
2000 K.C. Lee model
overvoltage problem.
0 Given the results of section V, there can be seen an
-2000
important need to study and characterize the power quality
phenomena of bidirectional flows and how can affect the
Watt
[19] C. Mucas "Assessment of Electric Power Quality: Indices for [22] L.Cristaldi and A. Ferrero “A digital method for the identification of the
Identifying Disturbing Loads". European Transaction on Power source of distortion in electric power systems”. IEEE Trans. on
Systems, ETEP Vol. 8, pp. 287 – 292, July/August 1998 Instrumentation and Measure, vol .44, pp. 183-189 Feb. 1994
[20] IEEE Working Group on nosinusoidal situations: Practical definitions [23] G. Strang and T. Nguyen, Wavelets and Filter Banks Wellesley:
for powers in systems with nonsinusoidal waveforms and unbalanced Wellesley-Cambridge Press, 1996,p.269.
loads: a discussion. IEEE Trans. on Power Delivery, vol. 11, pp. 30-34, [24] A.M. Gaouda, M.M.A. Salama, M.R. Sultan and A.Y. Chikhani “Power
January 1996. quality detection and classification using wavelet-multiresolution signal
[21] L.S. Czarnecki “Orthogonal decomposition of the currents in a 3-phase decomposition” IEEE Trans. on Power Delivery, vol. 14, pp. 1469-
nonlinear asymmetrical circuit with a nonsinusoidal voltage source.” 1476, October 1999.
IEEE Trans. on Instrumentation and Measurement, vol. 39, pp. 340-344
April. 1990