You are on page 1of 1

2.09.

2019

General Specifications
Transformer type Oil immersed, Hermetically Sealed With Corrugated Wall
Installation Outdoor
Applicable standarts IEC 60076-1
Rated power kVA 6000
High voltage V 34500
High voltage tappings (Off-load) % ± 2 x 2,5
Low voltage (at no load) V 690
High voltage insulation level (U m / U AC / U LI) kV 36 / 70 / 170
Low voltage insulation level (U m / U AC / U LI) kV 1,1 / 3 / --
Frequency Hz 60
Vector group Dyn5
Number of phases 3
Max. ambient temperature ºC 50
Max. temperature rise (winding / oil) ºC 55 / 50
Max. altitude above sea level m 1000
Permissible short circuit duration s 3
Cooling KNAN
Guaranteed Values
Impedance voltage(75ºC) ±10 % tolerance % 8
No load losses +0 % tolerance W 4400
Load losses(75ºC) +0 % tolerance W 40500
This document is the property of ELTAŞ A.Ş. And may not be used and copied without permission.

Total losses (75 oC) +0 % tolerance W 44900

Structural Specifications
High voltage winding conductor material Al
Low voltage winding conductor material Al
Oil type Midel 7131
Paint finish & colour C3 & RAL 7033
Dimensions and Weight
Length with terminal box / without terminal box mm 3070 / 2920
Width mm 1750
Height mm 2220
Total weight kg 13000
Weight of active part kg 6920
Weight of oil kg 2930

Connection Terminals
High voltage Plug-in Bushings 36kV 400A x 3
Low voltage Busbar Bushing 5000 A x 4

Accessories
Off-load tap changer Terminal box
Overpressure relay (Qualitrol 148) Rating plate
Oil level detection (Qualitrol 049) Earth screen between HV&LV winding
Thermometer Earthing terminals
PT 100 Drain valve 1"
Lifting lugs
* All weights and dimensions are given approximately.

ELTAŞ TRANSFORMATÖR SANAYİ VE TİCARET ANONİM ŞİRKETİ


Atatürk Organize Sanayi Bölgesi 10046 Sokak No.4 35620 B. Çiğli - İZMİR - TURKEY
Tel:+90(232)3981500(Pbx). Fax :+90(232)3767764 e-mail : info@eltas.com.tr http: www.eltas.com.tr

SRÇ28-F02 Yayım Tarihi: 06.04.2011 Revizyon No: 00 Revizyon Tarihi: - Sayfa1/1