You are on page 1of 1

28.09.

2023

General Specifications
Transformer type Oil immersed, Hermetically sealed
Installation Outdoor
Applicable standarts IEC 60076
Rated power KNAN kVA 200
High voltage V 11000
High voltage tappings (no load) kV + 2 x 2,5 % , - 2 x 2,5 %
Low voltage (no load) V 400
High voltage insulation level (U m / U AC / U LI) kV 12 / 28 / 75
Low voltage insulation level (U m / U AC / U LI) kV 1,1 / 3 / --
Frequency Hz 50
Vector group Dyn11
Number of phases 3
Max. ambient temperature ºC 40
Max. temperature rise (winding / oil) ºC 65 / 60
Max. altitude above sea level m 1700
Permissible short circuit duration s 3
Terminal box Ingress protection IP67
Guaranteed Values
Impedance voltage(75ºC) ±10 % tolerance % 4,5
No load losses ±15 % tolerance W 570
Load losses(75ºC) ±15 % tolerance W 3850

Structural Specifications
High voltage winding conductor material Cu
Low voltage winding conductor material Cu
Oil type Natural Ester Transformer Oil
Paint corrosion level C5M - 260 μm

Dimensions and Weight


Length / Width / Height mm 1100 / 940 / 1250
Total weight kg 780
Weight of active part kg 436
Weight of oil kg 155

Connection Terminals
High voltage Plug-in Bushings 24 kV 250 A x 3 (Interface Type A)
Low voltage Porcelain Bushings 1 kV 630 A x 4

Accessories
Oil filling & drain valves Hermetical Protection Relay (DMCR-PT100)
Off - circuit tap changer Thermometer with two contacts
Lifting lugs HV/LV cable boxes
Pressure relief valve Bidirectional rollers
Earthing terminal Junction box
Rating plate MV lock
Jacking pad
* All weights and dimensions are given approximately.
SAMİ TRAFO MAK. İMALAT İNŞ.TİC. LTD. ŞTİ.
Adana Hacı Sabancı O.S.B. Anafartalar Cad. No:11 ADANA / TURKEY