TRANSFORMER INDUSTRY
MALATYA / TURKEY

TRANSFORMER TECHNICAL SCHEDULE


CUSTOMER : BID NO:

STANDARDS IN FORCE : IEC 60076


TYPE : Box Type / Conservator Wtihout Expansion Tank
NUMBER OF PHASE : 3
FREQUENCY : 60 Hz
RATED POWER : 500 kVA
RATED VOLTAGES : 34,5 / 0,48 kV
VOLTAGE REGULATION RANGE : ± 2 x 2,5 % ( Off load HV Side )
VECTOR GROUP : Dyn11
TYPE OF COOLING : ONAN
OVERLOAD : According to IEC 354
OVER VOLTAGE : 5%
IMPEDANCE VOLTAGE (at C.M.R. 75ºC) : 4,0 ± 10 %
SHORT-CIRCUIT WITHSTAND DURATION : 2 s
POWER FREQUENCY VOLTAGE LEVEL ( HV / LV ): 70 kV / 3 kV
IMPULSE VOLTAGE LEVEL ( BIL ) ( HV / LV ) : 170 kV / -
LOAD LOSSES (at C.M.R. 75ºC) : 9000 W
NO-LOAD LOSSES (at normal voltage) : 1600 W
MAXIMUM AMBIENT TEMPERATURE : 45 °C
WINDINGS TEMPERATURE RISE : 60 °C
OIL TEMPERATURE RISE : 55 °C
CONDUCTOR MATERIAL : ELECTROLYTIC ALUMINIUM
Total Weight : 1840 kg
WEIGHT * Oil Weight : 350 kg
Weight Of Active Parts : 1025 kg
Length : 1710 mm
DIMENSIONS * Width : 1290 mm
Height : 1350 mm
ACCESSORIES SUPPLIED WITH TRANSFORMER : Rating Plate, Oil level indicator ,
Thermometer with alarm&trip contacts,
Off load tap changer, Dehydrating breather,
HV&LV Side cable box,
Earthing Terminals,
Oil filling plug, Oil drain valve,
Lifting Lugs, Wheels.

*APPROXIMATE VALUES Form 037