SPECIFICATION NO: ZG/PECL/PP&DRP/E&I‐SPEC‐020, Revision 0 
Date of release: 18.12.2019 
 
 
SPECIFICATIONS OF 1250 KVA EMERGENCY DIESEL GENERATOR SET 
 
 
DIESEL ENGINE OF PRIME DUTY: 
 
Diesel engine at 1500 RPM under NTP conditions, water cooled, four stroke, 16 cylinder, 
electric start, turbocharged & after cooled model, conforming to ISO:3046, BS: 5514 with 
capacity of 10% over loading for one hour in twelve hours duration having the following 
technical specification :‐ 
 
AIR INTAKE SYSTEM 
™ Air intake manifold. 
™ Dry type air cleaner with restriction indicator. 
™ Vacuum indicator. 
 
EXHAUST SYSTEM 
™ Turbocharger. 
™ S.S Flexible connection. 
™ Pulse tuned Exhaust manifold. 
™ Residential silencer. 
 
COOLANT SYSTEM 
™ Engine water pump. 
™ Radiator. 
™ Coolant additive concentrate. 
™ By pass thermostat. 
 
LUBRICATING SYSTEM 
™ Oil pan. 
™ Full flow lube oil filter. 
™ Lube oil by‐pass filter. 
™ Plate type lube oil cooler. 
 
FUEL SYSTEM 
™ Pressure Time (PT) Fuel System. 
™ Step Time Control (STC) injector. 
™ 24V DC solenoid coil. 
™ Replaceable fuel filters (spin on type). 
 
STARTING SYSTEM 
™ 24V DC electric starter. 
™ 24V DC battery charging alternator. 
 

CLIENT‐ M/S ZEN GLOBAL DMCC (UAE)  Page 1 
 
 
 
 
DG SET CONTROLLER 
 
 
Microprocessor‐based generator set monitoring, metering, and control system. The control 
provides an operator interface to the Generator set. Digital voltage regulation, digital governing, 
and generator set protective functions. 
 
  ™ Run/ Off / Auto switch
CONTROL  ™ Emergency stop 
™ Manual Run / Stop Control switch 
™ Idle / Run mode control
  ™ Starting Battery Voltage
  ™ Lube Oil Temperature & Pressure 
™ Engine Coolant Temperature 
METERING  ENGINE  ™ Coolant Pressure 
™ Engine Rpm. 
™ Operating Hours. 
™ Number of Starts.
™ Current
  ™ Voltage 
ELECTRICAL 
™ Frequency 
™ KW 
™ KWH 
™ Pf 
™ KVA
  ™ Over Speed Shutdown
  ™ Low Lube Oil Pressure Warning /Shutdown 
™ High Coolant Temperature Warning / 
  Shutdown 
PROTECTION / WARNING ENGINE 
™ Low Coolant Temperature Warning 
™ Low Coolant Level Warning/ Shut Down 
™ Low And High Battery Voltage Warning 
™ Weak Battery Warning 
™ Over Crank Shutdown 
™ Fail To Crank Shutdown 
™ Magnetic Pickup Failure Shut Down 
  ™ Over Current
ALTERNATOR  ™ High Voltage 
™ Low Voltage 
™ Under / Over Frequency 
™ Reverse Power Protection (KVA & KVAr) 
™ Phase Sequence

CLIENT‐ M/S ZEN GLOBAL DMCC (UAE)  Page 2 
 

  ™ Digital AVR
  ™ Amp Sentry Protection 
™ Sensor Failure Indication 
SPECIAL FEATURE  ™ Programmable Idle Speed Control 
™ Compatibility to Remote Monitoring. 
™ Smart Starting 
™ Suitability for Synchronization with other DG/STG 

 
 
 
 
Page 2 of 7 

CLIENT‐ M/S ZEN GLOBAL DMCC (UAE)  Page 3 
 
 
 
ALTERNATOR: 
 
Synchronous alternator of 1250 KVA rating, suitable for 1500 RPM generating 415 volts  at  0.8 
p.f.(lag)  50  Hz,  3  phase,  4‐wire  system.  The  alternator  shall  be  Brushless  type,  separately 
excited  (through  PMG)  &  self‐regulated  through  an  AVR.  The  alternator  will  be  suitable  for 
tropical climate and shall generally confirm to IS: 4722. The salient features of the alternator 
are: ‐ 
 
™ ±0.5% voltage regulation in static conditions. 
™ IP: 23 protections with class ‘H’ insulation & temperature limited to class 'H' insulation 
limited. 
™ Permanent lubricated sealed bearing. 
™ Permissible overload of 10% for one hour in 12 hours of operation. 
 
BASE FRAME: 
 
Engine and alternator are mounted through AVM pads, on a common channel iron fabricated 
Base Frame. 
 
FUEL TANK: 
 
Fuel  tank  of  990  ltr  capacity  fabricated  from  sheet  metal  complete  with  drain  valve,  air  vent 
and inlet and outlet connection. The fuel tank shall be floor mounted type placed outside the 
acoustic enclosure. 
 
BATTERY: 
 

Reputed brand maintenance free batteries of capacity 12V, 160AH (4 No’s). 
 
SITE METEROLOGICAL DATAS: 
 
Minimum  average  temperature  in  a  year:  +21  Degree  Celsius 
Maximum average temperature in  a year: +45  Degree Celsius  Site 
Altitude (Mean Sea Level ‐ MSL): 570 meters 
 
 
 
 
 
 
 
 
 
 
 
 
 

CLIENT‐ M/S ZEN GLOBAL DMCC (UAE)  Page 4 
 
 
 
 
 
TECHNICAL SPECIFICATIONS OF ACOUSTIC ENCLOSURE 
 
 
™ Silent DG Set container shall be of modular construction with the provision to 
assemble and dismantle easily at site. 
 
™ The enclosure is fabricated out of CRCA sheet. 
 
™ The sheet metal components are hot dipped in NINE TANKS pretreated before 
powder coating. 
 
™ Enclosure is powder coated (inside as well outside) with a special pure polyester based 
powder. All Nuts and, bolt/external hardware are made from stainless steel. 
 
™ The doors are gasketed with high quality EPDM gaskets to avoid leakage of sound. 
 
™ The door handles are lockable type. 
 
™ Sound proofing of enclosure is done with high quality rock wool/mineral wool 
confirming to IS 8183. 
 
™ The rock wool is further covered with fiber glass cloth and perforated powder coated 
MS sheet. 
 
™ Specially designed attenuators are provided to control sound at air entry to the 
container and exit from the container. 
 
™ Adequate ventilation is provided to meet air requirement for combustion and heat 
removal. 
 
™ As per CPCB norms with acoustic enclosure the noise insertion loss shall be 25 dBA at one 
meter in under free field condition for 1250 KVA DG set. 
 
 
 
 

CLIENT‐ M/S ZEN GLOBAL DMCC (UAE)  Page 5 
 
 
 
 
 
 
 

Scope of Supply 
 
Sr. No.  Description Quantity
1.  1250 KVA DG Set comprising Coupled to 1250 kVA, 415 V  04 Set.
Alternator mounted on a  common base frame, Cooling type‐
RADIATOR COOLED. 
2.  Batteries & Leads  04 Set.
3.  AVM Pads  04 Set.
4.  Residential Silencer.  04 Set.
5.  Fuel tank of 990 liters (2mm thick) ‐ outside enclosure 04 Set.
6.  Acoustic Enclosure suitable for 1x1250 KVA DG set 04 Set.
7.  AMF Panel  04 Set.
 
Special Notes: ‐ 
 
All starting aids and fuel tanks shall be separate for each DG set with all interconnecting fuel 
pipelines and cablings. 
 
System Configuration:‐ 

DG sets are connected to AMF Panel with one number outgoing Breaker to connect DG power 
in Main PCC Panel 
 
 
 
 
 
 
 
 
 
 
Page 6 of 7 

CLIENT‐ M/S ZEN GLOBAL DMCC (UAE)  Page 6 
 
 
 
Drawing, Documentations and other requirements:‐ 
 
1) Type of Inspection by Client  & Pre‐Shipment Inspection by Third Party 
2) QAP, G.A. & Foundation drawings with load data 
3) Electrical Circuit Diagram 
4) Bills of Material and Make of Material 
5) Inspection / test reports: 01 Set of hard copy. 
a. Test Certificate of diesel engine. 
b. Test certificate of Alternator. 
c. Test Certificate of D.G. Set. 
6) Operation & Maintenance Manual : 01 Set 