PROTECTION AND CONTROL OF
BHAKRA POWER HOUSES
1.PROTECTION:
HELPS IN SAFE RUNNING /WORKING OF VARIOUS EQUIPMENT
NAMELY TURBINE ,GENERATOR,TRANSFORMER,SWITHCHYARD
BAY EQUIPMENT,AUXILIARY EQUIPMENT WITHIN SPECIFIED
PARAMETERS.
ISOLATE FAULTY EQUIPMENT IF ABNORMAL CONDITION ARISES.
2.CONTROL:
CONTROLLED STARTING,STOPPING AND RUNNING OF
EQUIPMENT.
IN CASE OF GENERATING UNITS,ACTIVE AND REACTIVE
POWER CONTROL ACCORDING TO GRID FREQUENCY AND
VOLTAGE.
PROTECTION CLASSIFICATION
OF BHAKRA POWER HOUSES
UNIT
PROTECTION
HYDRO
ELECTRICAL
MECHANICAL
GOVERNING EXCITATION
SYSTEM SYSTEM
CT , CVT/PT
D.C. SUPPLY
CIRCUIT BREAKER
RELAY
COMMUNICATION
CONTROL WIRING
TEMPERATURE/PRESSURE GAUGES
FLOW RELAYS
SPEED RELAYS
STAGES OF PROTECTION:
• ALARM ONLY
• TRIPPING OF GENERATOR BREAKER
• TRIPPING OF GENERATOR BREAKER AND FIELD
BREAKER,MACHINE RUNNING MECHANICALLY AT
100% SPEED-PARTIAL SHUT DOWN
• AS ABOVE AND CLOSING OF GUIDE
VANES,MACHINE COMING TO DEAD STOP-
COMPLETE SHUT DOWN
• AS ABOVE WITH OPERATION OF EMERGENCY
SLIDE VALVE
• AS ABOVE WITH PENSTOCK GATE DROPPING
1 GENERATOR
DIFFERENTIAL PROTECTION:
• TO RESPOND QUICKLY TO A PHASE FAULT WITH
DAMAGING HEAVY CURRENT.
• HIGH SPEED DIFFERENTIAL PROTECTION IS APPLIED
TO GENERATORS RATED IN EXCESS OF 1 MVA.
• FOR LARGE GENERATING UNITS, FAST FAULT
CLEARANCE WILL ALSO MAINTAIN STABILITY OF MAIN
POWER SYSTEM.
• RESULTS IN TRIPPING OF MACHINE BREAKER,FIELD
BREAKER,EXCITATION GOING IN INVERSION
MODE,TRIPPING OF UAT,TURBINE
SHUTDOWN,CARBON DIOXDE RELEASE IN BARREL.
NO WATER FLOW-ALARM
INTER TURN
STATOR E /F
REF REF
HV LV
400/1 1200/1
X X X X
X X
Z1
Z3 Z2
X X X X
X X
A B C D
BUS FAULT
BUS BAR PROTECTION
BUS-1
BUS-2
BUS BAR PROTECTION
ZONE-1
BUS BAR PROTECTION
ZONE-1
ZONE-2
PROTECTION SYSTEM
Generator T/F Protection
protection 220 KV LINE
220 KV LINKAGE
BUS TO GRID
LBB
132KV
BUS 132/11
KV T/F
Line protection
132 KV D/C
TR. LINE
11KV
Bus Bar BUS
Protn.
Generation Evacuation
1.RUN AWAY PROTECTION:
• FIRST STAGE:
• SECOND STAGE: