Professional Documents
Culture Documents
Agenda
Over fluxing protection -24
Loss of excitation – 40
inadvertent
overfluxing rotor electrical faults loss of excitation
energisation
difference in expansion
rotor distortion between rotating and parts excessive vibration
stationary
Double
Stator armature
Negative frequency
MMF due to
sequence Relative speed = currents
neg.sequence Additional heat
component in a 2Ns induced in rotor
currents rotates
generator core and
at –Ns (rpm)
winding
Protection settings
• The rate of heat generation = I22R
Setting: Causes:
• Over fluxing normally can be caused by over speed of the turbine or
• Per unit voltage divided by per unit frequency commonly called
over excitation during Off-line condition
Volts/Hertz is a measurable quantity that is proportional to flux in
• Load rejection or AVR mal-functioning during On-line condition.
the generator or step-up transformer cores.
• Moderate over fluxing (105-110%) increases core loss resulting in
increase of core temperatures due to hysterics & eddy currents loss.
• Long term operation at elevated temperatures can shorten the life
of the stator insulation.
• Severe over fluxing can breakdown inter-laminar insulation followed
by rapid local core melting.
Reverse Power Protection of Generator
If the turbine i.e. prime mover fails the Generator / Alternator connected to the system will continue to
operate as synchronous Motor drawing active power from the system.
The consequences of generator motoring and the level of power drawn from the power system
will be dependent on the type of prime mover as under this condition prime mover acts as a load for
synchronous Motor.
For steam turbines, the motoring power is around 0.5-3 % of rated power of Generator.
LOSS OF FIELD OR EXCITATION PROTECTION
• Steam MW
• Field MVar
Grid loss
Effects
• The machine operated at lower higher speeds causes severe over fluxing in the
generator-transformer.
• The abnormal under frequency on the machine may be due to improper speed
control adjustment or disoperation of the speed controller.
Voltage restrained overcurrent relay
The purpose of the relay is to allow the To accomplish this, the relay pickup must be to
generator to operate, and to provide backup the left of the generator armature steady state
fault protection for the generator and cable. current.
Above knee of
generator
Set above downstream feeder
51 Time Dial decrement curve relays.
with constant
excitation
Above knee of
generator decrement Set above downstream feeder
51 Time Dial
curve with constant relays.
excitation
200% of AC decrement
CB INST Set below cable damage curve.
curve
• The maximum sustained close-up phase fault current (neglecting AVR action) is 145A, so that a setting chosen to be
significantly below this value will suffice.
• A value of 87.5A (60% of the close-up sustained phase fault current) is therefore chosen, and hence K = 0.6.
Voltage Controlled Overcurrent Protection
• The operating time of the downstream protection for a three-phase fault current of 850A is 0.682s,
so the voltage controlled relay element should have a minimum operating time of 1.09s (0.4s grading
margin used). TMS is :
Stator Earth Fault Protection
• The maximum earth fault current, is 200A.
• Protection for 95% of the winding can be provided if the relay is set to detect a primary earth fault current of 16.4A
• This equates to a CT secondary current of 0.033A. The nearest relay setting is 0.04A, providing protection for 90% of the
winding.
• At an earth fault current of 200A, the downstream protection has an operation time of 0.73s.
• The generator earth fault protection must therefore have an operation time of not less than 1.13s.
• TMS is :
Reverse Power Protection