Professional Documents
Culture Documents
Transmission Line
Protection
Directional Overcurrent
Elements
Traditional Approach Exercise
Exercise 1
13.8 kV
N.O.
18 kV
138 kV
= Radial
13.8 kV
12 kV
Exercise 1:
Assuming all circuit breakers of the system shown in the figure have overcurrent
relays associated with them, indicate which relays must be directional.
Note: All tie circuit breakers are normally closed except where indicated.
Exercise 2
13.8 kV
G1 T1 p
18 kV
138 kV
L1
Fault
13.8 kV
12 kV
A fault occurs on the 138 kV system as indicated above. The primary current and
voltages measured by the relays at “p” are indicated in the Table on the next page.
a. Indicate which directional elements will operate and which will not, if the
phase relays are voltage-polarized directional overcurrent relays with a 900
connection and a MTA=45o leading for the phase relays, and MTA=60o
leading. The ground relay has Ires and – Vres with MTA=60° lagging, as
indicated previously. Do this analytically and graphically. Assume the
relays’ operation is defined just by sign of the operating torques and that the
minimum operating torque is zero.
b. Determine the operation time of each overcurrent element. Refer to the relay
data on the next page.
Va Vb Vc
Magnitude Angle Magnitude Angle Magnitude Angle
kV Degrees kV Degrees kV Degrees
54.9 -2 74.5 -113 75.6 113
0o 0o
90o 90o
0o 0o
3. Identify, in each diagram, the operation zone of the relay using the voltage as the
reference. Determine if the relay operates or not.
b Tb=
c Tc=
Ground TG=
Determine the sign of each torque with the following formulas. Assume k=k’=1.