X20 module • Bus modules • BM11

2.4 BM11

2.4.1 General information

The BM11 bus module serves as the basis for all 24 VDC X20 I/O modules. The internal I/O
supply is interconnected.

• Bus module for 24 VDC I/O modules


• The internal I/O supply is interconnected

2.4.2 Order data

Model number Short description Figure


Bus module
X20BM11 X20 bus module, 24 V coded, internal I/O supply is
interconnected

X20 module
Table 22: BM11 - Order data Chapter 4

2.4.3 Technical data

Product ID BM11
Short description
Bus module Bus module for 24 VDC I/O modules, the internal I/O supply is interconnected
General information
Power consumption
Bus 0.13 W
I/O internal -
Certification CE, C-UL-US, GOST-R

Table 23: BM11 - Technical data

X20 System User's Manual V 2.10 157


X20 module • Bus modules • BM11

Product ID BM11
Operating conditions
Operating temperature
Horizontal installation 0°C to +55°C
Vertical installation 0°C to +50°C
Relative humidity 5 to 95%, non-condensing
Mounting orientation Horizontal or vertical
Installation at altitudes above sea level
0 - 2000 m No derating
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Protection type IP20
Storage and transport conditions
Temperature -25°C to +70°C
Relative humidity 5 to 95%, non-condensing
Mechanical characteristics
Spacing 12.5 +0.2 mm

Table 23: BM11 - Technical data (cont.)

2.4.4 Potential control

+24 VDC +24 VDC


GND GND

Figure 61: BM11 - Potential control