Permeate Pumps P-35-1 to 10 10 5,425 USgpm 21.0 ft 80.0% 94.0% 97.0% 20.70 hr 6,087 kW.hr 2,221,785 kW.hr
Backpulse Pumps P-88A/B 1 6,117 USgpm 16.7 ft 80.0% 94.0% 97.0% 3.20 hr 85 kW.hr 30,861 kW.hr
Drain/Recirculation Pumps P-97A/B (for all trains) 1 1,150 USgpm 15.4 ft 75.0% 94.0% 97.0% 18.18 hr 89 kW.hr 32,408 kW.hr
Membrane Aeration Blowers B-85A/B 1 371 scfm 4.3 psig 55.0% 94.0% 97.0% 9.58 hr 89 kW.hr 32,667 kW.hr
Air Compressors AC-91A/B 1 24.00 hr 360 kW.hr 131,400 kW.hr
Vacuum Pumps P-92A/B 1 5.00 hr 66 kW.hr 23,908 kW.hr
Controls & Instrumentation 1 24 kW.hr 8,760 kW.hr
Miscellaneous 1 24 kW.hr 8,760 kW.hr
Daily Estimated Power Consumption 6,823 kW.hr
Annual Estimated Power Consumption 2,490,548 kW.hr
27.29 kWh/ML