Industry Interfaces
Release 1.4
Type 11201, 41201
61201, 61202
64201, 66201
66203, 80201
81201, 81202
84201, 86201
W&T 86203, 88205
W&T Industry Interfaces
70
W&T Industry Interfaces
Index
72
W&T Industry Interfaces
Function
The interface converts one data line in each direction and pro-
vides electrical isolation between the RS232 side and the 20mA
side. The interface is build in a small plastic housing designed
for top hat rail mounting according to DIN EN 50022-35.
Power supply
Both ports of the device are isolated from each other and from
the power supply with a dielectric strength of 1000 volts. The
signals are isolated by means of high-speed opto-couplers; en-
ergy is supplied to the driver and receiver elements by means
of an isolated DC/DC converter. All signal lines are protected
against electrostatic discharge of up to 15kV according to IEC
801-2, level 4.
Connectors
The two ports of the interface use DB9 male connectors. The
connector pin assignments are shown in the table below:
Display elements
The interface includes two LEDs, with green for indicating the
correct supply voltage and red for verifying data transmission
in both directions.
Applications
74
W&T Industry Interfaces
3 2 1
TxD DIn Data Out 20mA RxD +
2
20mA device
2 3 DOut Data Out+ RxD -
RxD
3
84201
5 Data Out -
passive
5 GND
GND 4
Data Out GND
PC
7 6
RTS Data In 20mA TxD +
8 7
CTS Data In+ TxD -
6 8
DSR Data In -
9
4 Data In GND
DTR
3 2 1
TxD DIn Data Out 20mA
2
20mA device
2 3 DOut Data Out+ RxD +
RxD
3
84201
active
4
Data Out GND
PC
7 6
RTS Data In 20mA
8 7
CTS Data In+ TxD +
6 8
DSR Data In - TxD -
9
4 Data In GND
DTR
3 2 1
TxD DIn Data Out 20mA
active / passive
RxD +
2
20mA device
7 6
RTS Data In 20mA
8 7
CTS Data In+ TxD +
6 8
DSR Data In - TxD -
9
4 Data In GND
DTR
Technical Data
76
W&T Industry Interfaces
Function
The interfaces convert one data line and one handshaking line
in each direction and provide electrical isolation between the
RS232 side and the RS422/RS485 side. The interfaces are build
in a small plastic housing designed for top hat rail mounting
according to DIN EN 50022-35.
Power supply
Both ports of the devices are isolated from each other and from
the power supply with a dielectric strength of 1000 volts. The
signals are isolated by means of high-speed opto-couplers; en-
ergy is supplied to the driver and receiver elements by means
of an isolated DC/DC converter. All signal lines are protected
against electrostatic discharge of up to 15kV according to IEC
801-2, level 4.
Connectors
The two ports of the interfaces use DB9 male connectors. The
connector pin assignments are shown in the table below:
The interfaces include two LEDs, with green for indicating the
correct supply voltage and red for verifying data transmission
in both directions.
78
W&T Industry Interfaces
Operating mode
The interfaces can be set for five operating modes by DIP switch
setting on the RS422/RS485 interface module. The selectable
operating modes are briefly described here:
RS422, RS485, 4-wire bus master OFF OFF OFF ON OFF OFF
Termination
+5V
For all RS485 operating modes it is essential
that the bus system be terminated with a ter-
mination network which assures a defined Data In B
SW6
rest state in the high-impedance phases of
bus operation. The bus system can be con- Data In A
SW7
nected to a termination network by closing
switches #6 and #7 on the interface module.
80
W&T Industry Interfaces
Applications
3 2 DOut A 1
TxD DIn RxD A (-)
DOut B 6
2 3 RxD B (+)
RxD DOut 2
DIn A TxD A (-)
86201
RS422
device
8 4 7
CTS HOut DIn B
PC
TxD B (+)
6 HOut A 3
DSR GND CTS A (-)
5 5 HOut B 8
GND HIn CTS B (+)
HIn A 4
4 8 RTS A (-)
DTR 9
HIn B RTS B (+)
RS485
device
TxD DIn 6
DOut B RxD B (+)
2 3
RxD DOut DIn A 2 TxD A (-)
5 5 7
GND GND DIn B TxD B (+)
PC
7
RTS
8 RxD A (-)
RS485
device
CTS
6 RxD B (+)
DSR
TxD A (-)
4
DTR TxD B (+)
3 2 DOut A 1
TxD DIn Bus A (-)
DOut B 6
2 3 Bus B (+)
RxD DOut 2
DIn A
5 5
86201
7
RTS
RS485
device
8 Bus A (-)
CTS
6 Bus B (+)
DSR
4 8
DTR HIn
3 2 DOut A 1
Bus A (-)
86201
TxD DIn
DOut B 6
2 3 Bus B (+)
RxD DOut 2
DIn A
5 5 7
GND GND DIn B
PC
7
RTS
RS485
device
8 Bus A (-)
CTS
6 Bus B (+)
DSR
4
DTR
Technical Data
82
W&T Industry Interfaces
Function
The interface converts one data line in each direction and pro-
vides electrical isolation between the 20mA side and the
RS422/RS485 side. The interface is build in a small plastic hou-
sing designed for top hat rail mounting according to DIN EN
50022-35.
Power supply
Both ports of the device are isolated from each other and from
the power supply with a dielectric strength of 1000 volts. The
signals are isolated by means of high-speed opto-couplers; en-
ergy is supplied to the driver and receiver elements by means
of an isolated DC/DC converter. All signal lines are protected
against electrostatic discharge of up to 15kV according to IEC
801-2, level 4.
Conenctors
The two ports of the interface use DB9 male connectors. The
connector pin assignments are shown in the table below:
Display elements
The interface includes two LEDs, with green for indicating the
correct supply voltage and red for verifying data transmission
in both directions.
Operating modes
20mA interface
The interface can be used as an active or passive 20mA com-
ponent. In the active mode, the interface supplies the current
required by the respective 20mA loop, while in the passive
mode the loop current must be supplied by the connected de-
vice. The operating mode can be selected for both loops sepa-
rately.
84
W&T Industry Interfaces
RS422/RS485 interface
The interface can be set for three operating modes by DIP
switch setting on the RS422/RS485 interface module. The sel-
ectable operating modes are briefly described here:
Termination
For all RS485 operating modes it is essential that the bus sy-
stem be terminated with a termination network which assures a
defined rest state in the high-impedance phases of bus opera-
tion.
+5V
Data In B
SW6
Data In A
SW7
86
W&T Industry Interfaces
Applications
1 1
RxD- Data Out A Data Out 20mA RxD +
2
RS422 device
20mA device
RxD+ Data Out B
3
64201
2 Data Out -
passive
TxD- Data In A 4
Data Out GND
7 6
TxD+ Data In B Data In 20mA TxD +
7
Data In+ TxD -
8
Data In -
9
Data In GND
1 1
RxD- Data Out A Data Out 20mA
RS422 device
6 2
RxD+ Data Out B Data Out+ RxD +
20mA device
3
64201
active
Data Out GND
7 6
TxD+ Data In B Data In 20mA
7
Data In+ TxD +
8
Data In - TxD -
9
Data In GND
1 1
RxD- Data Out A Data Out 20mA RxD +
2
RS422 device
active / passive
2 Data Out -
TxD- Data In A 4
Data Out GND
7 6
TxD+ Data In B Data In 20mA
7
Data In+ TxD +
8
Data In - TxD -
9
Data In GND
1 1
Bus- Data Out A Data Out 20mA RxD +
2
RS485 device
6
active/passive
2 Data Out -
Data In A 4
Data Out GND
7 6
Data In B Data In 20mA
7
Data In+ TxD +
8
Data In - TxD -
9
Data In GND
Technical Data
88
W&T Industry Interfaces
Function
Power supply
Both ports of the device are isolated from each other and from
the power supply with a dielectric strength of 1000 volts. The
signals are isolated by means of high-speed opto-couplers; en-
ergy is supplied to the driver and receiver elements by means
of an isolated DC/DC converter. All signal lines are protected
against electrostatic discharge of up to 15kV according to IEC
801-2, level 4.
Connectors
The DTE port of the isolator uses a 9-pin male SUB-D connec-
tor, while the DCE port uses an 9-pin female SUB-D connector.
The connector pin assignments are shown in the table below:
90
W&T Industry Interfaces
Display elements
The isolator includes two LEDs, with green for indicating the
correct supply voltage and red for verifying data transmission
in both directions.
Applications
modem
88205
RI 9 9 RI RI 9 22 RI
PC
Technical Data
92
W&T Industry Interfaces
Function
In RS422 mode the isolator supports one data and one hand-
shaking line in each direction. In RS485 mode the isolator sup-
ports 2-wire and 4-wire bus systems. The repeater is build in a
small plastic housing designed for top hat rail mounting accor-
ding to DIN EN 50022-35.
Power supply
Both ports of the device are isolated from each other and from
the power supply with a dielectric strength of 1000 volts. The
signals are isolated by means of high-speed opto-couplers; en-
ergy is supplied to the driver and receiver elements by means
of an isolated DC/DC converter. All signal lines are protected
against electrostatic discharge of up to 15kV according to IEC
801-2, level 4.
Connectors
The two ports of the device use DB9 male connectors. The con-
nector pin assignments are shown in the table below:
Pin# Function
1 data out A (-)
2 data in A (-)
3 handshake out A (-)
4 handshake in A (-)
5 signal GND
6 data out B (+)
7 data in B (+)
8 handshake out B (+)
9 handshake in B (+)
Display elements
The isolator includes two LEDs, with green for indicating the
correct supply voltage and red for verifying data transmission
in both directions.
Operating mode
The isolator can be set for three operating modes by DIP switch
setting on the RS422/RS485 interface module. The selectable
operating modes are briefly described here:
RS422
One data channel and one handshake channel in each direc-
tion are available. The RS422/RS485 receivers and transmitters
are always active in this operating mode.
94
W&T Industry Interfaces
Termination
For all RS485 operating modes it is essential that the bus sy-
stem be terminated with a termination network which assures a
defined rest state in the high-impedance phases of bus opera-
tion.
+5V
Data In B
SW6
Data In A
SW7
Applications
1 1 RxD A (-)
RxD A (-) Data Out A (-) Data Out A (-)
6 6 RxD B (+)
RxD B (+) Data Out B (+) Data Out B (+)
2 2
device 2
TxD A (-)
device 1
RS422
RS422
7 7 TxD B (+)
TxD B (+) Data In B (+) Data In B (+)
3 3 CTS A (-)
CTS A (-) Hs Out A Hs Out A
8 8 CTS B (+)
CTS B (+) Hs Out B (+) Hs Out B (+)
4 4 RTS A (-)
RTS A (-) Hs In A (-) Hs In A (-)
9 9 RTS B (+)
RTS B (+) Hs In B (+) Hs In B (+)
1 1
Bus A (-) Data Out A (-) Data Out A (-) Bus A (-)
6 6
Bus B (+) Data Out B (+) Data Out B (+) Bus B (+)
2 2
Data In A (-) Data In A (-)
66201
7 7
Data In B (+) Data In B (+)
3 3
Hs Out A Hs Out A
8 8
Hs Out B (+) Hs Out B (+)
RS485
RS485
device
device
4 4
Bus A (-) Hs In A (-) Hs In A (-) Bus A (-)
9 9
Bus B (+) Hs In B (+) Hs In B (+) Bus B (+)
96
W&T Industry Interfaces
Technical Data
98
W&T Industry Interfaces
Function
Power supply
Both ports of the device are isolated from each other and from
the power supply with a dielectric strength of 1000 volts. The
signals are isolated by means of high-speed opto-couplers; en-
ergy is supplied to the driver and receiver elements by means
of an isolated DC/DC converter. All signal lines are protected
against electrostatic discharge of up to 15kV according to IEC
801-2, level 4.
Connections
The two ports of the device use DB9 female connectors. The
connector pin assignments are shown in the table below:
Pin# Function
1 Shield
2 n.c.
3 RxD/TxD-P
4 CNTR-P
5 DGND
6 VP
7 n.c.
8 RxD/TxD-N
9 CNTR-N
Display elements
The isolator includes two LEDs, with green for indicating the
correct supply voltage and red for verifying data transmission
in both directions.
Termination
100
W&T Industry Interfaces
Technical Data
102
W&T Industry Interfaces
Function
Power supply
The RS232 port of the device is isolated from the power supply
with a dielectric strength of 1000 volts. The signals are isola-
ted by means of high-speed opto-couplers; energy is supplied
to the driver and receiver elements by means of an isolated DC/
DC converter. All signal lines are protected against electrosta-
tic discharge of up to 15kV according to IEC 801-2, level 4.
Connections
Pin# Function
2 data in
3 data out
4 active level
5 signal GND
7 active level
Display elements
The interface includes two LEDs, with green for indicating the
correct supply voltage and red for verifying data transmission
in both directions.
Assembly
104
W&T Industry Interfaces
At the same time insert the separated end of the fiber optic
duplex line into the fiber optic coupling female.
Releasing the locking levers locks the fiber optics into the
coupling.
To release, pull the two locking levers on the top of the cou-
pling towards the module, and pull the fiber optic cable out
of the female.
The arrows on the top side of the coupling clearly show the
location of the emitter and receiver lines.
Applications
2 3 DOut
RxD
5 5 GND
GND
PC
7
RTS
8
CTS
6
DSR
4
DTR
2 3 DOut
RxD
5 5 GND
GND
PC
7
RTS
8
CTS
6
DSR
4
DTR
Technical Data
106
W&T Industry Interfaces
Function
The Interface supports one data line and one handshake line in
each direction and transmits data over a distance of max. 50
meters. The transmission medium is standard duplex plastic fi-
ber optic cable, which is inexpensive and extremely easy to
work with and install. The use of fiber optics as a transmission
medium ensures perfect galvanic isolation between the con-
nected devices and clean transmission even in noise-prone en-
vironments. The interface is build in a small plastic housing de-
signed for top hat rail mounting according to DIN EN 50022-
35.
Power supply
The RS232 port of the device is isolated from the power supply
with a dielectric strength of 1000 volts. The signals are isola-
ted by means of high-speed opto-couplers; energy is supplied
to the driver and receiver elements by means of an isolated DC/
DC converter. All signal lines are protected against electrosta-
tic discharge of up to 15kV according to IEC 801-2, level 4.
Connections
Pin# Function
2 data in
3 data out
4 active level
5 signal GND
7 handshake out
8 handshake in
Display elements
The interface includes two LEDs, with green for indicating the
correct supply voltage and red for verifying data transmission
in both directions.
Assembly
108
W&T Industry Interfaces
At the same time insert the separated end of the fiber optic
duplex line into the fiber optic coupling female.
Releasing the locking levers locks the fiber optics into the
coupling.
To release, pull the two locking levers on the top of the cou-
pling towards the module, and pull the fiber optic cable out
of the female.
The arrows on the top side of the coupling clearly show the
location of the emitter and receiver lines.
Applications
RS232 POF
3 2 Receive fiber
TxD DIn
2 3 Transmit fiber
81202
RxD DOut
5 5
GND GND
PC
7 8 HIn
RTS
8 7 HOut
CTS
6
DSR
4
DTR
RS232 POF
3 2 Receive fiber
TxD DIn
2 3 Transmit fiber
81202
RxD DOut
5 5
GND GND
PC
7 8 HIn
RTS
8 7 HOut
CTS
6
DSR
4
DTR
Technical Data
110
W&T Industry Interfaces
Function
Power supply
Connections
Pin# Function
1 data out A (-)
2 data in A (-)
5 signal GND
6 data out B (+)
7 data in B ( +)
Display elements
The interface includes two LEDs, with green for indicating the
correct supply voltage and red for verifying data transmission
in both directions.
Assembly
112
W&T Industry Interfaces
The arrows on the top side of the coupling clearly show the
location of the emitter and receiver lines.
Operating Mode
Termination
For all RS485 operating modes it is essential that the bus sy-
stem be terminated with a termination network which assures a
defined rest state in the high-impedance phases of bus opera-
tion. The bus system can be connected to a termination net-
work by closing switches #6 and #7 on the interface module:
+5V
Data In B
SW6
Data In A
SW7
114
W&T Industry Interfaces
Applications
61201
RS422
device
DOut B 6
RxD B (+)
DIn A 2 TxD A (-)
DIn B 7 TxD B (+)
RS485
device
DOut B 6
RxD B (+)
DIn A 2 TxD A (-)
DIn B 7 TxD B (+)
RxD A (-)
RS485
device
RxD B (+)
TxD A (-)
TxD B (+)
DOut A 1
Transmit fiber Bus A (-)
61201
DOut B 6
Bus B (+)
DIn A 2
DIn B 7
RS485
device
Bus A (-)
Bus B (+)
Technical Data
116
W&T Industry Interfaces
Function
Power supply
The Profibus port of the device is isolated from the power sup-
ply with a dielectric strength of 1000 volts. The signals are
isolated by means of high-speed opto-couplers; energy is sup-
plied to the driver and receiver elements by means of an isola-
ted DC/DC converter. All signal lines are protected against elec-
trostatic discharge of up to 15kV according to IEC 801-2,
level 4.
Connections
Pin# Function
1 Shield
2 n.c.
3 RxD/TxD-P
4 CNTR-P
5 DGND
6 VP
7 n.c.
8 RxD/TxD-N
9 CNTR-N
Display elements
The interface includes two LEDs, with green for indicating the
correct supply voltage and red for verifying data transmission
in both directions.
Assembly
118
W&T Industry Interfaces
The arrows on the top side of the coupling clearly show the
location of the emitter and receiver lines.
Termination
Technical Data
120
W&T Industry Interfaces
Function
Power supply
The 20mA port of the device is isolated from the power supply
with a dielectric strength of 1000 volts. The signals are isola-
ted by means of high-speed opto-couplers; energy is supplied
to the driver and receiver elements by means of an isolated DC/
DC converter. All signal lines are protected against electrosta-
tic discharge of up to 15kV according to IEC 801-2, level 4.
Connections
Pin# Function
1 data out 20mA
2 data out +
3 data out -
4 data out GND
5 n.c.
6 data in 20mA
7 data in +
8 data in -
9 data in GND
Display elements
The interface includes two LEDs, with green for indicating the
correct supply voltage and red for verifying data transmission
in both directions.
Assembly
122
W&T Industry Interfaces
The arrows on the top side of the coupling clearly show the
location of the emitter and receiver lines.
Applications
1
Data Out 20mA RxD +
20mA device
Receive fiber Data Out+
2
RxD -
3
41201
Transmit fiber
passive
Data Out -
4
Data Out GND
6
Data In 20mA TxD +
7
Data In+ TxD -
8
Data In -
9
Data In GND
1
Data Out 20mA
Receive fiber 2
20mA device
4
Data Out GND
6
Data In 20mA
7
Data In+ TxD +
8
Data In - TxD -
9
Data In GND
1
Data Out 20mA RxD +
active/passive
Receive fiber 2
20mA device
124
W&T Industry Interfaces
Technical Data
126
W&T Industry Interfaces
The W&T Fiber Optic Repeater Model 11201 allows two com-
ponents with plastic fiber optic interfaces to be connected over
a distance of more than 100 meters.
Function
Power supply
Connections
Display elements
The repeater includes two LEDs, with green for indicating the
correct supply voltage and red for verifying data transmission
in both directions.
Assembly
The arrows on the top side of the coupling clearly show the
location of the emitter and receiver lines.
128
W&T Industry Interfaces
Applications
RS232 POF
3 2
81201
TxD DIn
8120
2 3 DOut
RxD
5 5 GND
GND
PC
7
RTS
m
ax
8
.1
CTS
00
6
DSR
m
4
DTR
POF
repeater
#11201
m
00
.1
RS232 POF
ax
m
3 2
81201
TxD DIn
2 3 DOut
RxD
5 5 GND
GND
PC
7
RTS
8
CTS
6
DSR
4
DTR
Technical Data
130
W&T Industry Interfaces
Function
The RS232 Line Driver Set modules are build in a small plastic
housing designed for top hat rail mounting according to DIN
EN 50022-35.
Power supply
The interfaces of the line driver set use build-in switching regu-
lators for power supply and has a wide input voltage range from
12V to 24V. The operating voltage can be supplied by the
enclosed AC adaptor or by any other AC or DC voltage in the
permissible range. The interfaces have a build-in reverse volta-
ge protection. The power can be supplied by screwed contacts.
Both ports of the device are isolated from each other and from
the power supply with a dielectric strength of 1000 volts. The
signals are isolated by means of high-speed opto-couplers; en-
ergy is supplied to the driver and receiver elements by means
of an isolated DC/DC converter. All signal lines are protected
against electrostatic discharge of up to 15kV according to IEC
801-2, level 4.
Connectors
The two ports of the W&T line driver module 80201 use DB9
male connectors. The connector pin assignments are shown in
the table below:
Display elements
The interface includes two LEDs, with green for indicating the
correct supply voltage and red for verifying data transmission
in both directions.
132
W&T Industry Interfaces
Interconnecting cable
Applications
3 1 2 DIn A
TxD
2
DIn
DOut A DIn 2 2
TxD
DOut B 6 7 DIn B
2 3 DOut 3 3
Plotter
80201
8
CTS
4
HOut DIn B 7 6 DOut B HOut 4 5
CTS
PC
6 3 4 6
DSR HOut A HIn A DSR
5 8 9
GND
5
GND HOut B HIn B GND 5 7
GND
HIn A 4 3 HOut A
4
DTR
8
HIn 9 8 HIn 8 20
DTR
HIn B HOut B
7
80201
7 6 4 7
RTS DIn B DOut B RTS
8 8
PC
PC
Technical Data
134
W&T Industry Interfaces
EC Declarartion of conformity
136