Professional Documents
Culture Documents
A New System To Solve The Problems of Positioning The Air-Termination Components
A New System To Solve The Problems of Positioning The Air-Termination Components
ICLP 2010
A NEW SYSTEM TO SOLVE THE PROBLEMS OF POSITIONING
THE AIR-TERMINATION COMPONENTS
Prof. Tibor Horvath
1021 - 1
2.1.1. Problems of the standardized method Fig. 1 and Fig. 2 illustrate structures of unreal sizes.
This definition eliminates the existing contradiction that The radius of the rolling sphere is 20 m at least but it may
the sphere is “rolling around and on top of the structure” be 60 m too. On Fig. 1, the building of two stages is hardly
while “it should touch only the ground and/or the air- higher than 20 m or just than 60 m. The lateral surfaces
termination system”. Annex A and Annex E contain now exposed to side flash determine the scale of Fig. 2. The
such examples that clearly demonstrate the mis- radius of sphere is 60 m. Therefore; the higher structure is
understanding the application of the rolling sphere about 240 m and the lower about 195 m high in the
method. Typical cases are: structures without any air- background. The width of the total group is more that 420
termination system as shown in Fig.1 (IEC E.21). Its aim m, and the air-termination rod is 60 m high. Neglecting
would be to show, which parts need to be protected on a these irrational assumptions, both figures represent a
structure! Considering the third view (failing in the contrast to the definition of the rolling sphere method,
standard), the rolling sphere method demonstrates only the because there is no air-termination on Fig. 1 and only a
evident result that the roof is exposed to lightning strike. rod on Fig. 2. Therefore, the sphere contacts the structures
almost everywhere, though it is strictly excluded by
definition of the rolling sphere method. At the same time,
they represent only evident statements.
1021 - 2
occurring mistake that the rolling sphere is similar to the Fig. 5 and Fig. 6 show the sphere that continuously
protection angle only a circular arc should be used instead contacts the ground while it is rolling around a rod or
of a straight line. Fig. 4 demonstrates the difference along horizontal conductors. In these cases, the center of
between the applications of the rolling sphere method. sphere is always in the height equal to its radius. The
distance of the center is the radius of the horizontal cross
section of the sphere in the height of the air-termination
components. This can be calculated by:
rh = h 2r h) (1)
1021 - 3
of the structure to be protected is farther removed
from the air-termination than distance d depending on
the Class of LPS. This method can be applied if the
roof is made of insulating material and contains no
metal component inside 0,6 m below its surface.
The size of the mesh can be determined using the
rolling sphere method, with supposition that the surface to
be protected is sunk down with 1% of the sphere radius
below the physical surface of the roof as shown by Fig. 10.
In this case the mesh method will harmonize with the
rolling sphere method and result in distances of Table 2.
Table 2. The limited distance from the mesh sides
Figure 9. Rolling the sphere along two parallel lines. Class of LPS I II III IV
Fig. 9 shows the sphere that continuously contacts two Distance d from 3m 4m 6,5 m 8,5 m
parallel conductors in two points. The center moves air-termination
always in the plane of symmetry; therefore, equation (2)
can be reduced to two unknown coordinates. As illustrated in Fig. 11, the sizes of quadratic meshes
The numbers mean in Fig. 5 – Fig. 9 as follows: are defined as before. In another case, a circle may not be
put into the mesh, whose radius is distance d.. The shape
1 The rolling sphere 4 Rolling way
of a mesh can be any polygon also with curved sides.
2 Air-termination conductors 5 Rolling direction
3 Air-termination rods
When the center has been determined, the contours of
the protected volume can be estimated in several planes. A
comparison shows whether the structure to be protected
fits into the protected volume or protrudes out of it.
Figure 10. Applying the rolling sphere method to construct the mesh width.
1021 - 4
Using the standardized diagram, Table 3 indicates the
2.3. The protection angle method extension of protected area on the ground around air-
termination masts of several heights. These data
2.3.1. Problem with the standardized method demonstrate that the standardized procedure always results
IEC 62305-3 and EN 62305-3 standards contain a in the smallest protected area in the case of the highest air-
diagram below Table 2 that is reproduced here as Fig. 11. termination mast. Such values could not be accepted as
rational results!
The standardized diagram gives protection angles in the
range 70° – 79°, when H is less than 2 m. According to a
Note: H is the height of air-termination above the
reference plain of the area to be protected. Although, the
definition of reference plain is failing, the standard often
takes it identical with the flat roof independent from its
height above the ground. This is in contradiction to the
long time experience of high voltage lines, which resulted
in about 20° degree above 40 m and 15° above 50 m.
Observed lightning strokes also demonstrated in Malaysia
Figure. 11. The protection angle plotted against the height, that large protection angles are irrational [4]. The ESE
according to IEC 62305-3 standard. argumentation abuses such protection angles for promising
the extreme large protection effects.
Although, it is not declared, this is based upon a Because of the contradictions and the irrational values
completely baseless idea. According to this idea, the of the standardized protection angle method, its complete
protective effects of the protection angle and the rolling emission came also into question. However, it can be
sphere should be equivalent, if areas A1 and A2 balance properly applied in special cases.
each other as shown in Fig. 12.
2.3.2. Special application of the protection angle
The protection angle method is an additional manner,
which can be applied anywhere except of the lateral
surfaces of tall structures, which should be protected
against side flashes.
1021 - 5
The special application of the protection angle method for this case. In case a) this plane is shifted along a straight
would be defined as follows: line. In case b) the plane turns to perpendicular while
Applying this method, the positioning of the air- moves along the curved air-termination conductor.
termination system is adequate if all part of the In another typical case, the plane of the generatrix is
structure is below a surface generated by straight line rotated around a vertical axis. Fig. 15 shows two typical
of angle related to vertical. examples for such rotation. In case a) the tip of a vertical
air-termination rod determines the axis of rotation. In case
The horizontal width of the protected area should be b) this axis is at a corner of horizontal air-termination
limited to b depending on the Class of LPS. conductor. The green marked upper part is a conical
surface whose bevel angle is equal to the protection angle.
The protection angle can be assumed on the base of
The green marked upper part is a cylindrical surface
the long time experience related to transmission lines.
whose radius is equal to the limited horizontal extension of
Considering LPS Class IV the radius of sphere is 60 m,
the protected area.
and the relating protection angle is = 15° (see 2.3.1). The
height of air-termination could be lower in the case of
Classes I – III; however these should represent increased
requirement of safety. Therefore, taking a greater
protection angle would not be rational decision. The best
solution would be generally using = 15°.
This method would be usually applied on tall structures,
where side flashes also occur. In this region, the protection
angle would produce extended protected volume; therefore
a limitation is necessary. When the width of the protected
space is limited to the tenth of the rolling sphere radius,
the protection of small lateral protrusions could be solved,
and the several requirements of the LPS Classes are also
considered.
a) b)
Figure 15. Special applying the protection angle method,
rotating around a vertical axis;
a) at an air-termination rod, b) at a corner of conductor.
This application of the protection angle method gives a
solution to construct air-termination of structures higher
than the radius of the rolling sphere. The application of
this rule is detailed in another paper by the same author
with examples of high structures [2].
3. CONCLUSION
The IEC 62305-3 standard determines three methods
for adequate positioning the air-termination components,
which don’t harmonize among themselves, and represent
a) b) different safety.
A better harmonizing system could be created, if the
Figure 14. Special applying the protection angle method, rolling sphere method is taken a basis, while the protection
moving along a horizontal air-termination conductor; angle and the mesh size methods are defined on this base.
a) straight line; b) forming an arc.
The rolling sphere method is principally in order, but
The vertical plane of the generatrix is always the definition involves contradictions with itself and there
perpendicular to the horizontal air-termination conductor are false applications in the practical examples of the IEC
while moves along it. Fig. 14 shows two typical examples standard. These failures could be corrected.
1021 - 6
The protection angle method proved good for the
transmission lines, but it cannot suitably applied for three- 4. REFERENCES
dimensional structures. The standardized procedure is [1] Horváth T.: “Problems with application of the protection
based on a false idea, results in irrational solutions and it angle method at three-dimensional structures”.
cannot applied sometimes at all. It is generally unusable; 29th International Conference on Lightning Protection,
therefore, it should be omitted. However, the protection Paper 4-5, Pp. 1-9.Uppsala, Sweden, June 2008..
angle method can be used as an additional manner to solve [2] Horváth T.: “Problems and solution of utilizing the
some problems of tall structures, higher than the radius of protection angle method.” 30 th International Conference on
rolling sphere. Lightning Protection, Cagliari, Italy, September 2010.
[3] T. Horváth, “False application of the rolling sphere method
The IEC standard deals only with square meshes, which in the international standards.” 29 th International
can be easily generalized. The standardized mesh sizes Conference on Lightning Protection, Paper 10-03,
have no relation to the rolling sphere radius. With Uppsala, Sweden, June 2008.
consideration that the surface to be protected is usually [4] Darveniza, M., Hartono, Z. A., and Robiah, I.: “A
free of metal elements, a relation was found to the rolling Database of Lightning Damage caused by Bypasses of Air
sphere method. terminals on Buildings in Kuala Lumpur, Malaysia”,
6th SIPDA, Santos, Brazil, 2001.
1021 - 7