Professional Documents
Culture Documents
&
st
And 1 International Conference on
Lightning Physics and Effects
1st LPE Belo Horizonte - Brazil November, 2004
Franco D’Alessandro
ERICO Inc., USA
Abstract - An important consideration in the design of an air In other words, points with higher electric field
termination system is the maximum distance at which the intensification are more likely to be struck, confirming
terminations can be placed from the “vulnerable points” on that geometry plays an important role in the lightning
structures, i.e., typically those points that create the highest attachment process. This observation has been
degree of electric field intensification. Surprisingly, many confirmed by computer simulations of such strikes,
codes and standards provide very little, if any, guidance in taking into account the probabilistic aspects of the
this regard. This paper presents a preliminary analysis of
process [10].
the problem using numerical electric field computations
and two different criteria for determining whether the given
parameters are acceptable. The parameters include the
The motivation for the present paper came from the
type, height and distance of the air terminations, as well as regular observation of what can be considered “bad
the height of the structure on which they are installed. A practice” in the installation of standard air terminations
quantitative guideline is provided for the maximum on structures – the placement of those terminations at a
distance at which air terminations should be installed from considerable distance from the “vulnerable” points of
the vulnerable points of structures. structures. For example, Figure 1 shows a “bad”
installation – where a rod of height 0.3 m is placed too
far away from the pointed end of the roof. Figure 2 shows
1 - INTRODUCTION an example of lightning damage to a building which had
(short) rods installed beyond an effective distance.
Over its 250 year history, lightning protection has
evolved relatively slowly due to the: (i) stochastic nature
of lightning and the inherently long times needed to
gather field data, (ii) trial-and-error or empirical nature of
any investigation, and (iii) the difficulty of replicating the
effects of lightning under laboratory conditions.
Therefore, in recent times, we have seen the increasing
use of computer models and simulations of the lightning
phenomenon, its attachment to ground structures and
the direct and indirect effects on building contents once
lightning strikes a ground point.
In the first method, Rezinkina [2] found that the ratio kd = (a)
Eterm/Eedge, where Eterm and Eedge represent the electric
field strength at the air termination and at the structure
edge or vulnerable point respectively, could be used to
define a 95% interception efficiency. The value of 95%
was based on comparisons with experimental studies of
lightning rod reliability and protection of adjacent objects.
Rezinkina [2] found that kd > 2.0 ensures that objects at
the nominated distance from the air termination are
protected with an efficiency of 95%. Hereafter, this
criterion shall be abbreviated EFR (“electric field ratio”).
Eterm / Eedge
Eterm / Eedge
2
2
1
1
(a) (b)
0 0
0 1 2 3 4 0 1 2 3 4
d/h d/h
Figure 4 – Plot of the electric field ratio (termination-to-structure edge) as a function of d / h for horizontal conductors according to the
EFR criterion. (a) Structure height of 5 m. (b) Structure height of 50 m.
3 3
2 2
Eterm / Eedge
Eterm / Eedge
1 1
h = 0.25 m h = 0.25 m
h = 0.5 m h = 0.5 m
(a) (b)
h = 1.0 m h = 1.0 m
0 0
0 1 2 3 4 0 1 2 3 4
d/h d/h
Figure 5 – Plot of the electric field ratio (termination-to-structure edge) as a function of d / h for rods according to the EFR criterion, for
structure heights (a) 5 m, (b) 50 m.
1.5 1.5
h = 0.1 m h = 0.25 m
(a) h = 0.5 m (b) h = 0.5 m
1.4 1.4
h = 1.0 m h = 1.0 m
1.3 1.3
Eterm / Eedge
Eterm / Eedge
1.2 1.2
1.1 1.1
1.0 1.0
0.9 0.9
0 1 2 3 4 0 1 2 3 4
d/h d/h
Figure 6 – Plot of the electric field ratio (termination-to-structure edge) as a function of d / h for (a) horizontal conductors and (b) rods,
according to the CRFI criterion. The data for the two structure heights were combined as there was very little difference in the results.
The last two points can be explained by the difference in protected zones of 0.02, 0.1, 0.4 and 1.7 metres
where the electric fields are calculated – EFR is respectively.
computed at the surface whilst CRFI is computed at a
distance of 0.7 m. In the latter case, the electric field Hence, the RSM results in considerably larger assumed
distribution is more uniform because it is being measured shielding or protection zones than the present
further away from the structure, resulting in less calculations, which are based on electric field
dependence on structure height. calculations around the terminations and structures. This
is an example of an underlying weakness in the RSM,
Finally, bearing in mind that a wide-ranging parametric namely that it does not make any allowance for
study has not been carried out, a very rough, yet differences in electric field intensification. Note that this
generalised and quantitative relation can be obtained comparison is applicable, for example, to a structure of
from all of the results if they are combined into a single height 5 m, where H << R, but not, say, a 50 m structure,
plot. Figure 7 shows such a plot, where the absolute where H ~ R.
maximum air termination distance that will satisfy both
criteria has been plotted for all the parameters studied.
5 – CONCLUSIONS
5
Conductors, EFR criterion The motivation for the study presented in this paper
Rods, CRFI criterion came from the common observation of poor placement
Conductors, CRFI criterion of air terminations and the lack of definitive guidelines in
4 Rods, EFR criterion
codes and standards on lightning protection. In the
present work, a preliminary analysis was conducted on
3
dmax (m)
Main author
Dr Franco D’Alessandro
Senior Research Scientist
ERICO, Inc.
34600 Solon Road
Solon, OHIO. 44139. USA.
Tel - +1. 440 542 3965
Fax - +1. 440 542 7241
Email - fdalessandro@erico.com