Professional Documents
Culture Documents
Lightning Protection
Abstract – Lightning protection of buildings and electrical conductors, etc.). The same phenomenon arises between
installations includes also the controlling of separation electrical installations and the LPS. Fig. 1 illustrates the
distances to avoid uncontrolled side flashes between the relation between lightning current rate of rise, induced
different systems. A new solution for an insulated down- voltage and a possible puncture in the proximity area.
conductor will be proposed. The requirements on this
These can be avoided, if the required separation distance
insulated down-conductor are shown and an appropriate
test method is applied to determine an equivalent separation s is kept between earthed conductive parts of the building
distance. installation and/or the electrical installation and the LPS.
In practice, the control and the permanent keeping of the
1 INTRODUCTION separation distances has proved to be difficult and partly
impossible. Electrical installations are flush-mounted or
In the field of lightning protection for buildings and covered so that the exact position can often not be
electrical installations, also the question of a suitable located. If later installations are performed, the required
installation of down-conductors is important, apart from separation distance is often not controlled.
the question for the selection and construction of air
terminations for protection against direct lightning strikes
and preventing partial lightning currents to enter the 2 SEPARATION DISTANCE
inside of the building.
[1,2] describe the calculation of the required separation
Proximity Voltage u at the point of
proximity induced by
distance for avoiding proximities.
lightning impulse
ki ⋅ kc (1)
current i s= ⋅L
km
t
with s: Separation distance
ki: Factor - protection level of the LPS
250 ns
kc: Factor - lightning current distribution
1M km: Factor - material of the electrical isolation
Installation u
V
L: Vertical distance from the point, where the
MEB i separation distance s has to be determined
25 kA to the next point of the equipotential
bonding.
Fig. 1 - Puncture in the proximity area between the LPS and the The length of the separation distance depends on the
electrical installation at insufficient separation distances down-conductor length, the protection level, the division
of the lightning current over different down-conductors
and the material [3] in the isolating distance.
If the required separation distance s is not kept,
uncontrolled flashovers and/or punctures can occur In Bavaria an annual damage of two-digit amounts of
between earthed parts of the building construction (e.g. millions has been caused by lightning strikes into
steel girders, reinforcements, elevator rails, etc.) and the agricultural buildings. Therefore in a study over 100
lightning current carrying components of the lightning damage claims were investigated. A considerable number
protection system LPS (air terminations, down-
of fires was also caused in agricultural buildings with 3 USE OF INSULATING MATERIAL FOR THE
LPS. The main causes of this damage were REDUCTION OF THE REQUIRED SEPARATION
• incomplete equipotential bonding DISTANCE
The idea of a safe control of proximities by means of • Possibility of a lightning current proof connection
special insulating components was already performed in with the air termination via clamps, connectors or
1987 in the model installation “Guglhof“ as a pilot object alike with a standard dimension
of the ABB/VDB (Fig. 2). • Keeping the required separation distance by a
sufficient electrical strength in the zone of the
feeding point and along the down-conductor
• Sufficient current carrying capability
• Possibility to connect with the earth-termination
system or existing LPS via clamps, connectors or
alike with a standard dimension
By including insulating materials with a high electrical
withstand capability, the separation distance s can
basically be reduced. However the electrical strength of
the total system “down-conductor” is determined by the
arrangement itself as well as the coming up of creeping
Fig. 2 - Structure of the partly isolated LPS at the model discharges.
installation “Guglhof“ (1987)
In order to get independent from the arrangement of the
down-conductor, the use of unshielded insulated down-
The functional size of the used components, however, conductors becomes conceivable (Fig. 4). With this type
were undesirable under architectural and technical aspects of conductor the problem, however, is not resolvable.
(e.g. wind loads). This partly isolated LPS was further Experiments show, that already at relatively low induced
developed in 1997 (Fig. 3) and can now be integrated into impulse voltages creeping discharges may come up in the
e.g. an existing roof surface. proximity area which may cause a total flashover over
long conductor lengths.
Injection of the
lightning current
(feeding point)
Conductor
High-voltage resistant
isolation
External coating
(weather and UV
resistant)
15 m
6 COAXIAL CABLE WITH SEMI-CONDUCTIVE
M1,2
COVER
Installation loop
In order to fulfil the requirements on an insulated down-
5m conductor and to avoid partial lightning currents via the
earthed conductive cable sheath, a special coaxial cable
Fig. 7 - Magnetic coupling between an insulated down- with a semi-conductive cover has been developed. In
conductor an installation loop using an insulated down- order to optimize the field control, a specially adjusted
conductor with field control and conductive shield
cable entrance fitting was designed, that allows the
realisation of an equivalent separation distance s ≤ 0.75 m
It has to be considered, that an HV-insulated coaxial (Fig. 9).
cable with its metal and earthed cable shield can form a
part of an induction loop (Fig. 7).
αα Interception Rod
If the cable sheath is connected with the equipotential
bonding only at the earth side, the installation forms an Insulating cable entrance fitting area
open loop were a high voltage is induced. Depending on support tube
the size and position, the induced voltage can reach
amplitudes of some MV (Fig. 8). Antenna Insulated Downconductor
2 40 Corresponds to
s = 0,75m in air
MV kA
1 20 Connection to the
earth termination
Connection to the system
equipotential bonding
0 0 of the BTS