Professional Documents
Culture Documents
1023-1
components of a building, such as the inter-connected interconnected reinforcement bars embedded in columns
reinforcement bars embedded in concrete columns, and beams of a building. As seen in Figure 2, the
beams and floor. This structural metalwork is intended to structure is characterized by the length of L, the width of
drain the lightning discharge current from the air L and height of H. It has the grid size of W x W. The
termination down to the earth termination network, as distance between the isolated down conductor and the
seen in Figure 1(a). In the second case, an dedicated nearest structure corner is denoted by D. This wire-grid
down conductor, which is electrically isolated from the structure is not intended to carry the discharge current. It
building structure, is connected to the air termination for may carry the induced current due to electromagnetic
draining the lightning current to the Earth, as seen in coupling from the isolated down conductor.
Figure 2. The isolated down conductor is usually l
mounted on the façade of a building (external down
conductor), or installed in the service core in the building w
(internal down conductor). This down conductor is not
allowed to connect to the structural work of the building.
In this paper, the magnetic field environment in the h
building protected with isolated down conductors is
addressed.
1023-2
B1
SF = × 100% (1)
Bo
where B1 and B0 are the magnetic fields in the presence
and absence of the building structure, respectively. Note
that B0 is solely contributed by the current in the isolated
down conductor shown in Figure 2, while B1 is
contributed by both the current in the down conductor
and induced current in the building structure. Generally
speaking, SF varies with location of the observation point
within the building. For simplicity of the discussion in
this paper, SF is evaluated on the diagonal line shown in
Figure 2. It is plotted or expressed against the x-
coordinate of the observation point on this diagonal line.
(a) SF on a plane
4 REGION OF SHIELDING FACTOR OF A 60
WIRE-GRID STRUCTURE
SF curve
50
It was revealed in a preliminary study that the shielding Fitting line
situated in the central point of the structure (x=0 and Figure 4. Distribution of shielding factor along a vertical line in
y=0). It is found in the figure that SF remains constant if the center of the building
the distance to the roof of the building is 10m or above.
It, therefore, is concluded that a three-dimensional region 5 SHIELDING CHARACTERISTICS OF A
can be identified in the structure. In this region SF varies WIRE-GRID STRUCTURE
moderately, and can be approximated by a straight line. It is noted from the preliminary study that shielding
This region is called the steady region, and is limited by factor varies with structure parameters, such as structure
horizontal boundaries [ − L 2 + W , L 2 − W ] and vertical length L, height H and grid width W. In this section, the
boundaries of [ 0, H − 10m] . It is known that in this region impact of these parameters on the shielding factor is
investigated via computer simulations. The observation
a moderate shielding effect is observed, and the shielding line is the diagonal line from one corner of the structure
factor is predictable. This region is good for installation to opposite corner at the height of 5m above the ground.
of sensitive equipment in modern buildings. The structure of concern has the reference height of 40m,
1023-3
reference length of 20m, and reference grid width of 2m. of D<W and D>W, respectively. After analyzing the
simulation results, the following are obtained;
5.1 Influence of Grid Width W
To investigate the influence of grid with W, we varied
the grid width W only from 2m to 6m, and calculated the
SF on the horizontal line. Fig. 5 shows the SF curves with
three different grid widths. It is noted that the larger the
grid width is, the greater the SF value is. This indicates
that the structure with a large grid size will have a poor
shielding effect because of strong flux leakage through
the opening. In general, the SF curve is shifted upwards
linearly if the grid width is increased.
is less than 4%. This indicates that the SF does not vary
D=2.00m
SF
0.2
with the structure height as long as the steady region is of
concern.
1 0.1
w=2
0.8 w=4
w=6 0
2 3 4 5 6 7 8
0.6 X (m)
SF
(a) d < w
0.4
0.4
D=2m
0.2 D=3m
0.3 D=4m
D=5m
0 D=10m
2 3 4 5 6 7 8 9 10 D=25m
SF
0.2 D=50m
X (m)
Figure 5. SF curves in the structure against grid width W
0.1
5.3 Influence of Distance to the Down Conductor D
It was noted in the preliminary study that SF is 0
significantly affected by the distance to the isolated down 2 3 4 5 6 7 8
1023-4
• When W≤D≤10W, the SF curve twists around a point at where
x = −0.32 L with increasing D. At this time, both 0.079
k 0 ( D, L , W ) = ( − 0.123)(
1
− 2.6)
1/ 3
gradient and interception point of the SF curves are W D
dependent of distance D. 0.6485
• When 10W≤D, the SF curve twists around the center +( − 0.01539)
L /W
point at x=0 and y=0 with increasing D. Similarly both
gradient and interception point of the SF curves are k1 ( D ) = −0.0044 − 0.01339e( − D / 52.98) − 0.01142e ( − D / 3.117)
dependent of distance D. −0.18446 1
k2 (W , L) = −0.47 + ( + 1.0083)(+ 0.4)
W L /W
5.4 Influence of Structure Length L
−0.1843 1
To investigate the impact of structure length L, we k3 (W , L) = −0.06 + ( + 0.9479)( − 0.1)
W L /W
varied the structure length from 4m to 16m, and
calculated the SF again on the diagonal line at the height Shielding formulas given in (2) have been validated
of 5m. The simulation results are presented in Figure 8. numerically using a sample wire-grid structure. The
It is noted from the figure that when structure validation was made by comparing the results from (2)
parameters of H, D and W are fixed, the SF curve will with those from numerical calculation In the comparison
shift downward with increasing L. This indicates that the structure height H, length L and grid size W were fixed to
gradient of the fitted lines keeps constant and only the be 40m, 10m, and 2m, respectively.
interception point is changed. So it can be inferred that Two different values of distance D were selected for
the gradient of the SF curves is independent of L while the comparison, that is, D=0.25m (D<W), and D=5m
the intercept is determined by L. These phenomena are (W≤D≤10W). The corresponding formulas are given by
also observed for the structure with other values of SF ( x) = −0.024 x + 0.1505 x ∈ [−3,3] (3)
parameters W, H and D. It is also found that the wider is SF = −0.0189( x + 1.8) + 0.2738 x ∈ [−3,3] (4)
the structure, the lower the SF is. This means that the Figures 9 and 10 shows the curves of SF obtained from
wider the structure is, the better its shielding effect is. the numerical calculation. It is noted that two curves in
0.6 the center region match very well.
L=4m
0.5
L=6m
L=8m
0.4 0.4
Numerical
L=10m
Empirical
L=12m
SF
0.3
L=16m
SF
0.2 0.2
0.1
0
-8 -6 -4 -2 0 2 4 6 8 0
-5 -4 -3 -2 -1 0 1 2 3 4 5
X (m) x (m)
Figure 8. SF along the diagonal line in a structure with different Figure 9. SF curves obtained from numerical simulation and
structure empirical formula (D=0.25m)
0.7
6 EMPIRICAL SHIELDING FORMULAS
0.6 Empirical
Based on the discussion in the previous sections, Numericcal
0.3
of the structure. Shielding formulas are given for
difference distance D. Given by horizontal distance x of 0.2
⎪ x (m)
SF ( x) = ⎨k1 ( D)( x + 0.18 L) + k2 (W , L) W<D<10W Figure 10. SF curves obtained from numerical simulation and
⎪k ( D ) x + k ( D, L ) D>10W empirical formula (D=0.25m)
⎩ 1 3
(2)
1023-5
7 CONCLUSIONS [4]. R. Cortina, A Porrino, “Calculation of impulse current
distributions and magnetic fields in lightning protection
This paper discussed the shielding characteristics of a structures-A computer program and its laboratory
metallic wire-grid structure against the magnetic field validation,” IEEE trans. on Magnetics, Vol.28, No.2,
emitted from an indirect lightning stroke. The structure March 1992
was made of a series of interconnected reinforcement [5]. C.A.F. Sartori, J.R. Cardoso and A. Orlandi, “Transient
bars embedded in columns and beams of a modern induced voltage computation in a high building struck by
building. The shielding factor of the structure was lightning,” Magnetics,” IEEE Trans. on EMC, Vol. 34 No.
investigated with the equivalent circuit approach. The 5 Part: 1, Sept. 1998 pp. 2815 –2818
[6]. C. Buccella, S.Cristina and A. Orlandi, “Frequency
computer simulations were performed, and the following analysis of the induced effects due to the lightning stroke
conclusions were obtained. radiated electromagnetic field,” IEEE Trans. on EMC,
Shielding factor near a column can exceed one, which Vol.34, No.3, 1992, pp.338-344
indicates the resultant magnetic field with the structure is [7]. G. Ala and P. Buccheri, “Transient electromagnetic hazard
more serious than that without the structure. It is not wise inside a lightning protection system,” Procs. of Eleventh
to install any sensitive equipment in this region. The International Symposium on High-voltage Engineering,
magnetic field in the central region can be, however, Vol.1, 1999, pp. 275 -278
reduced significantly, but the reduction of the field is [8]. C. Buccella, “Calculation of current distribution in a
greatly affected by geometrical parameters of the lightning stroked metal structure considering the nonlinear
ground impedance,” Procs. of IEEE Thirty-Sixth IAS
structure. This steady region is normally determined by Annual Meeting, Vol.4, 2001, pp. 2703 –2708
the grid size of the structure. [9]. C. Buccella, S. Cristina and A. Orlandi, “Shielding
It is found that the shielding factor does not vary performances of reinforced walls to the field radiated by
significantly with the structure height, as log as the lightning,” Procs. of Eighth International Conference on
observation point is located in the steady region. EMC, 1992, pp.60 –66
Reducing grid size not only improves shielding effect of [10]. A. Karwowski, A. Zeddam, “Transient currents on
the structure, but also increases the steady region within lightning protection systems due to the indirect lightning
the structure. Similarly, increasing structure length or effect,” Science, IEE Proceedings of Measurement and
width leads to the improvement of the shielding effect Technology, Vol 142 No. 3, May 1995, pp. 213 –222
[11]. A. Orlandi, “Lightning induced transient voltages in
and the expansion of the steady region. presence of complex structures and nonlinear loads,” IEEE
The distance to an isolated down conductor has a great Trans. on EMC, Vol.38, No.2, May 1996, pp.150-155
impact on the shielding effect of the structure. In case of [12]. M. Rubinstein and M.A. Uman, “Methods for calculating
small distance (D≤W), the SF curve shifts upwards with the electromagnetic fields from a known source
increasing D. Its gradient is generally constant, and distribution: application to lightning,” IEEE Trans. on
independent of distance D. In case of lager distance EMC, Vol. 31 Issue: 2, May 1989, pp.183 -189
[13]. IEC 62305-4 Protection against Lightning—Part 4:
(W≤D), the SF curve twist around the central point at x=0
Electrical and electronic systems within structures, IEC
with increasing D. Both gradient and interception point of Standard, 2006
the SF curves are dependent of distance D.
8 REFERENCES
The work leading to this paper was supported by
grants from the Research Committee of the Hong Kong
Polytechnic University, and the Research Grants Council
of the Hong Kong Special Administrative Region
(Project No. 516008 and 516809)
9 REFERENCES
[1]. S. Cristina and A. Orlandi, “Calculation of the induced
effects due to a lightning stroke,” IEE Proceedings-Part B,
vol.139, July 1992, pp.47-55
[2]. A. Orlandi, and F. Schietroma, “Attenuation by a lightning
protection system of induced voltages due to direct strikes
to a building,” IEEE Trans on EMC, Vol 38 No.1, 1996,
pp.43-50
[3]. A. Sowa, “Surge current distribution in building during a
direct lightning stroke,” Procs. of Inter. Symp. on EMC,
1991, pp. 103-105
1023-6