You are on page 1of 9

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO.

1, JANUARY 2012 205

The Use of Underbuilt Wires to Improve the


Lightning Performance of Transmission Lines
Silverio Visacro, Member, IEEE, Fernando H. Silveira, and Alberto De Conti

Abstract—An unconventional technique to improve the lightning rameter typically used to characterize the response of electrodes
performance of transmission lines, consisting of the addition of subjected to lightning currents. Nevertheless, the measurement
grounded wires properly positioned below the phase conductors, of this impedance is not feasible in field conditions. Since, under
is assessed. Overvoltages developed across insulator strings of ex-
isting 230-kV lines in response to direct strikes to the towers were certain circumstances, both parameters are related, the mea-
simulated using an electromagnetic model. Minimum reductions sured low-frequency resistance is used to verify the grounding
of these voltages in the ranges of 19%–32% and 26%–44% were quality instead of the impedance, as discussed in [4].
achieved for 20- to 80- tower-footing grounding resistances due The literature refers to some nonconventional practices
to the addition of one and two underbuilt wires, respectively. This to improve the lightning performance of transmission lines.
practice was shown to be more efficient than reducing the tower
grounding resistance to its half value.
These practices explore effects of parameters that influence
the amplitude of overvoltages developed across insulator
Index Terms—Lightning, lightning overvoltage, lightning per- strings when lightning strikes the line, notably the tower surge
formance of transmission lines, transmission lines.
impedance, and the electromagnetic coupling between shield
wires and phases. It suggests the possibility of using guy
I. INTRODUCTION wires, continuous counterpoise, or metallic wires placed below
phase conductors, as alternative solutions to improve the line
IGHTNING is a frequent cause of transmission-line out-
L ages, reducing the availability of electrical networks. Ba-
sically, three mechanisms are responsible for developing light-
response to direct strikes [6], [7]. Despite these suggestions,
the literature deals very poorly with the problems involved in
their implementation, and no quantitative evaluation of their
ning overvoltages in high-voltage lines that might result in elec- efficiency is provided.
trical discharges across insulator strings, leading to faults: the In this perspective, this paper addresses an unconventional
flashover, associated with strikes to phase conductors; the back- technique and quantifies the improvement it might produce on
flashover, associated with strikes to the tower or to shield wires the lightning performance of lines, taking as reference an ex-
at the tower vicinities; and the midspan flashover, as detailed in isting 230-kV line, used as a case study.
[1] and [2].
For transmission lines below 500 kV installed in regions of II. DEVELOPMENTS
unfavorable soil-resistivity conditions, the backflashover largely
prevails [3]. Therefore, this mechanism, which is mainly gov- A. Describing the Technique
erned by the value of tower-footing grounding impedance, is The technique consists of the addition of metallic wires
the main focus of techniques intended to improve the lightning installed below the phase conductors at proper distances and
performance of such lines. connected to the tower that requires lightning performance
The conventional practices to decrease the frequency of back- improvement. The underbuilt wires are extended only along the
flashover events comprise basically two actions: 1) the reduc- two spans adjacent to the tower. In this paper, steel wires were
tion of tower footing resistance and 2) the installation of surge tested, though any metallic wire could be used. This technique,
arresters to prevent flashovers. Most power utilities concentrate explored by the authors in a sequence of works since 2002
their efforts in the first practice due to the costs associated with [8]–[12], has provided encouraging results in terms of reducing
the installation and maintenance of line surge arresters. It is lightning overvoltages developed in response to direct strikes
worth mentioning that reducing grounding resistance is an in- to the line, and it is here refined.
direct way to achieve the actual goal, which is to decrease the Two arrangements of practical interest were identified in sim-
tower-footing grounding impedance. As explained in [4] and ulations, corresponding to the addition of one and two under-
[5], the low-frequency grounding resistance can be quite dif- built wires as indicated in Fig. 1. Observing a minimum distance
ferent from impulsive grounding impedance, which is the pa- “ ” is required to avoid diminishing the electrical insulation of
the transmission line.
Manuscript received April 03, 2011; revised July 12, 2011; accepted August
27, 2011. Date of publication October 18, 2011; date of current version De- B. Methodology of Development
cember 23, 2011. Paper no. TPWRD-00260-2011.
The authors are with the Lightning Research Center (LRC) of Federal Uni- The proposed arrangements and the efficiency of this tech-
versity of Minas Gerais (UFMG), Belo Horizonte 31270-901, Brazil (e-mail: nique were accessed by systematic simulation using the hybrid
LRC@cpdee.ufmg.br). electromagnetic model (HEM). This frequency-domain model,
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. described in detail in [13], has been widely employed to deter-
Digital Object Identifier 10.1109/TPWRD.2011.2168546 mine voltage and current distributions in lightning-related prob-
0885-8977/$26.00 © 2011 IEEE
206 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 1, JANUARY 2012

Fig. 3. Geometric configuration of the simulated line. (a) Dimension of the


Fig. 1. Proposed arrangement of underbuilt mettallic wires to improve the mast sustained by guy wires and position of conductors. (b) Grounding electrode
lightning response of towers for the case-study line. (a) One additional wire. arrangement.
(b) Two additional wires.

In their original configuration, the towers of this line sus-


tain four conductors comprising a single superior shield wire
and three-phase conductors distributed in a triangular arrange-
ment, as depicted in Fig. 3 along with the grounding electrode
arrangement.
The tower mast around 40 m high has a 1.25-m lateral square-
shaped internal structure and was represented by 1- to 5-m-long
segments. The simulated heights of the single shield wire, the
upper and lower phase conductors are 37.6, 31.4, and 25.6 m as
indicated in Fig. 3(a). The structures responsible for sustaining
Fig. 2. Simulated condition: direct strike to the tower. the upper and lower insulators strings were assumed to be 34.2
m and 28.4 m high, respectively.
The phase conductors and shield wire have 0.5- and 0.3-cm
lems. In particular, its application in the calculation of lightning radii, respectively, and were represented by 5-m-long segments.
overvoltages due to direct strikes to transmission lines is con- The 50-m-long counterpoise of the 0.5-cm-radius grounding
sidered in [14]. Frequencies in the range of 1 Hz to 5 MHz with electrodes buried 0.5 m deep in the ground is comprised of radial
a 12.5-kHz step were used in the simulations of this work. wires departing from the base of tower mast and connected to
The model was applied to determine the overvoltage devel- guy-wire anchors. The radial electrodes are bent half a meter
oped across insulator strings of the real line in response to light- from the limits of the 35-m-wide right of way. The concrete
ning strikes to the tower, as represented in Fig. 2. The reduc- encased metallic components of each anchor were represented
tion of developed overvoltages due to the addition of underbuilt by a 5-cm-radius electrode, 2.4 m long, while the central mast
wires to the original configuration of the line was evaluated in foundation was represented by a 10-cm-radius electrode, 2.4 m
different conditions. long. The buried conductors were represented by 0.5- to 3.5-m-
In the first evaluations, the incident lightning current was ap- long segments.
proached by a triangular 2/50- s wave with 50-kA peak current. The first simulated configuration used to include the tower
The peak current and front time were defined to represent a se- under analysis and the two adjacent towers along with all of
vere condition associated with a first stroke current. The eval- the aerial conductors along the 300-m-long spans and extended
uations of this work do not focus on the absolute value of the 30 m after the adjacent towers were followed by matching im-
overvoltage but on the relative decrease of this quantity. Since pedances to avoid reflections. After observing that the pres-
the triangular shape is not expected to affect the relative decrease ence of adjacent towers and the long wires were not able to af-
of the overvoltage, it was chosen to ease sensitivity analysis. fect the simulated peak overvoltage, they were suppressed in
Later, the impact of this approach on the results is evaluated in simulations and only the tower under analysis with 30-m-long
Section IV-B. The current wave was supposed to be impressed matched-impedance wires was represented in each span to re-
on the tower top from a lumped current source. duce time consumption in simulations. The procedure to match
Taking advantage of the linear relationship between over- impedances includes the matching of self and mutual impedance
voltage across insulator strings and peak current, the results pre- and, therefore, preserves the electromagnetic coupling between
sented in this paper were adjusted to the unit “kV/kA.” This al- phase conductors and underbuilt wires.
lows one to promptly calculate the expected overvoltage devel-
III. RESULTS AND ANALYSIS
oped for any incident current simply by multiplying the values
in the graphs by the peak current. A. Results Used as Reference: Improvements of Lightning
Performance Achieved by Grounding-Resistance Reduction
C. Transmission Line Used in Evaluations
As mentioned, the grounding impedance has a fundamental
In order to obtain realistic results from the application of the role in backflashover. Basically, this impedance is responsible
technique, the evaluations were developed considering an ex- for defining the amplitude of lightning overvoltages developed
isting 230-kV transmission line. across insulator strings due to direct strikes to the tower or to
VISACRO et al.: USE OF UNDERBUILT WIRES 207

TABLE I
PEAK VALUES OF OVERVOLTAGES ACROSS THE UPPER AND LOWER INSULATOR
STRINGS AS A FUNCTION OF GROUNDING-RESISTANCE VALUES

Fig. 4. Overvoltage across (a) upper and (b) lower insulator strings for different
grounding-resistance values (2/50-s triangular current wave).

Fig. 5. Reduction of overvoltage across the upper insulator string as a function Fig. 6. Effect of the addition of underbuilt wires on the overvoltages developed
of grounding-resistance value. across the upper (a) and lower (b) insulator strings (Rg = 20 and d = 4 m).

the shield wires at tower vicinities, with this amplitude dimin- tion around 66 and 71%, respectively, across upper and lower
ishing with decreasing impedance [15]. This explains why the insulator strings.
most common practice to improve lightning performance con- Considering a 50-kA peak-current strike, the overvoltage de-
sists in reducing the grounding impedance, with this measure veloped for of 40 would be decreased from about 1.4 MV
being quantified through the value obtained for the grounding to 700 kV for of 10 , achieving a value quite lower than the
resistance [4]. 230-kV-line critical flashover voltage (CFO), around 1.2 MV.
In order to establish references to measure the improvement Voltages above this CFO would be developed for values of
obtained from the application of the proposed unconventional a little above 30 .
technique, this section considers the effect of decreasing
grounding resistance on reducing overvoltages developed B. Applying the Technique: First Results Concerning the
across insulator strings of the existing line during direct strike Effect of Using One and Two Underbuilt Wires
events. Two simple arrangements of special interest because of their
Fig. 4 shows the overvoltage waves resulting across the upper practical feasibility and efficiency were identified from the sys-
and lower insulator strings due to a strike to the tower top with tematic application of the HEM model. They correspond to the
all of the assumptions indicated in Sections II-B and C, and addition of one and two underbuilt wires as indicated in Fig. 1.
considering the tower grounding resistance ( ) varying from Fig. 6 shows overvoltage waves developed across insulator
10 to 80 . The values of were obtained assuming the same strings (in kilovolt/kiloamperes) in response to the impression
arrangement of electrodes of Fig. 3(b) was buried in soils of of a 2/50- s triangular current wave on the tower top associated
different resistivity. The peak values of such overvoltages and with a direct lightning strike, considering the addition of one and
the percentage of voltage reduction are indicated as a function two underbuilt wires according to the arrangement of Fig. 1 and
of in Table I and Fig. 5. 4 m for distance “ .” A soil resistivity of 1600- m was used in
The results in Figs. 4 and 5 and Table I reveal the efficiency simulations, corresponding to a 20- grounding resistance for
of decreasing grounding resistance to improve the lightning per- the electrode arrangement defined in Fig. 3(b).
formance of transmission lines. While this resistance decreased The addition of underbuilt wires decreases the overvoltages
from 80 to 10 , the overvoltage varies from the order of 44 to very significantly and this reduction is larger for the lower in-
15 kV/kA. This corresponds to a lightning overvoltage reduc- sulator string. The addition of one wire promotes a reduction of
208 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 1, JANUARY 2012

TABLE II TABLE V
DECREASE OF PEAK OVERVOLTAGE DUE TO THE APPLICATION DECREASE OF PEAK OVERVOLTAGE DUE TO THE APPLICATION
OF THE UNCONVENTIONAL TECHNIQUE FOR Rg = 10 OF THE UNCONVENTIONAL TECHNIQUE FOR Rg = 80

TABLE III wire reduces the overvoltage across the upper and lower insu-
DECREASE OF PEAK OVERVOLTAGE DUE TO THE APPLICATION
OF THE UNCONVENTIONAL TECHNIQUE FOR Rg = 20 lator strings to 77% and 69% of the original value, respectively.
This effect is more pronounced than the reduction obtained by
decreasing the grounding resistance to 30 . The addition of
two underbuilt wires promotes reductions to 69% and 58%. This
result is better than that obtained by decreasing to 20 .
This means this technique is more efficient than reducing the
grounding resistance to its half value. If one considers a 50-kA
strike to the 40- grounding-resistance tower, the peak-voltage
of 1.35 MV across upper string, exceeding the line CFO, would
TABLE IV
DECREASE OF THE PEAK OVERVOLTAGE DUE TO THE APPLICATION OF THE
be decreased to 935 kV, lower than the line CFO.
NONCONVENTIONAL TECHNIQUE FOR Rg = 40 The aforementioned analysis denotes the possibility of em-
ploying such a technique as a complementary resource in a
very unfavorable soil-resistivity condition, where no efficient
grounding solution is obtained to ensure appropriate lightning
performance of transmission lines. These conditions occur
frequently; for example, when the limited length of long
lines crosses mountainous regions, presenting rocky and high
resistivity soils that make it unfeasible to achieve values of
tower-footing grounding resistance low to the extent required
around 19 and 28% for the upper and lower string, respectively, to ensure appropriate lightning performance along this length.
while the reduction is much larger for the addition of two wires, It is worth mentioning that underbuilt wires are not expected
around 26 and 38%. to cause losses due to low-frequency circulating currents, since
It is worth mentioning the very small increase of costs of an their use is typically recommended along short lengths of line.
intervention to install two underbuilt wires instead of one. Since
a return of about 40% is obtained when two wires are used in- D. Influence of the Distance Between Underbuilt Wires and
stead of one (overvoltage reduction of 26% against 19%), the Phase Conductors
use of two underbuilt wires is rather preferable. The distance “ ” indicated in Fig. 1 varied from 4 to 8 m.
Some parameters might influence the decrease of lightning Distances shorter than 4 m would jeopardize the line insulation
overvoltages obtained from the technique application as ex- level. Table VI shows the effect of varying the distance between
plained next. underbuilt wire(s) and phase conductors, considering a 20-
grounding-resistance tower. It is shown that increasing this dis-
C. Influence of Tower Grounding Resistance tance decreases the overvoltage reduction. Similar results were
In order to verify the sensitivity of the overvoltage reduction obtained for towers with of 10 and 40 . Therefore, the dis-
in relation to the grounding-resistance value, the same simu- tance “ ” should be the lowest value that still ensures the insu-
lation of the preceding section was developed considering the lation level of the line.
tower resistance , varying from 80 to 10 . Tables II–V show Increasing distance “ ” contributes to reducing the electro-
the overvoltage reduction in each case. magnetic coupling between phase conductors and underbuilt
The results provided by the technique are improved with in- wires, and the drain off part of the lightning current that would
creasing tower-footing grounding resistance. The voltage reduc- otherwise flow through one tower’s grounding resistance. Both
tions across the upper insulator string for a 10- grounding-re- mechanisms are responsible for decreasing lightning overvolt-
sistance tower, around 16% and 24% for one and two underbuilt ages, as discussed in Section III-F. This explains the decrease
wires, are increased to 32% and 44% for a 80- tower-footing. of overvoltage reductions with increasing “ .”
Across the lower strings, such values evolve from 26% and 36%
to 39% and 53%, respectively. E. Effect of Adjacent Towers
The comparison of the results of Table I with those of Ta- So far, the presented results correspond to simulations
bles II–V reveals the high potential of this unconventional tech- that represent all wires sustained by the tower as 30-m-long
nique. Considering 40 , the addition of one underbuilt impedance-matched conductors, as described in Section II-C .
VISACRO et al.: USE OF UNDERBUILT WIRES 209

TABLE VI
PEAK OVERVOLTAGES AS A FUNCTION OF DISTANCE BETWEEN PHASE
CONDUCTORS AND UNDERBUILT WIRES FOR Rg = 20

Fig. 8. Effect of adjacent-tower grounding resistance on overvoltages devel-


oped across the upper string of the struck tower. Rg of adjacent towers: 10, 20,
and 40 . Rg of central tower: 20 . (a) One underbuilt wire. (b) Two under-
built wires.

F. On the Source of the Overvoltage Reduction


The reduction of the lightning overvoltage peak due to under-
built wires is achieved not only by means of the coupling effect
between phase conductors and underbuilt wires but also by the
draining off part of the lightning current that would otherwise
flow through one tower’s grounding resistance [16].
The relevance of each mechanism depends on several factors,
notably on the value of the tower-footing grounding resistance.
Fig. 7. Overvoltage waves across upper insulator strings considering the effect In this paper, a specific simulation was developed to estimate the
of the two adjacent towers (300-m spans between towers) for a 20- grounding- impact of each mechanism. A pair of 300-m-long impedance-
resistance tower. (a) One underbuilt wire. (b) Two underbuilt wires (2/50-s
triangular current wave). matched horizontal underbuilt wires was placed in a position
orthogonal to the phase conductors, considering the same tower
configuration of Fig. 2. This arrangement is very attractive since
Therefore, these results do not take into account the effect of it is able to basically promote the decoupling of underbuilt wires
the adjacent towers, and this issue is addressed in this section. and phase conductors, without significantly affecting the parcel
Two conditions are simulated: 1) the presence of adjacent of the lightning current drained off by the underbuilt wires.
towers 300 m away from the central tower under analysis, The results are very interesting. Table V indicates an over-
with all 660-m-long wires followed by matching imped- voltage reduction of 43.56% due to the addition of two un-
ances, with the exception of the underbuilt wires (terminated derbuilt wires for the 80- tower-footing grounding resistance.
at the towers) and 2) the same as 1) but using 660-m-long Simulations show that the drain off current is responsible for ap-
impedance-matched underbuilt wires. The tower-footing resis- proximately 72% of this overvoltage reduction, while coupling
tance of adjacent towers were assumed equal to the central one. is responsible for 28%. This conclusion is different from the as-
The corresponding overvoltage waves developed across the sumption of [6] that attributes most of the overvoltage reduction
upper string for 20 are shown in Fig. 7 and denote that, to the increase of the coupling coefficient from shield wires to
in the evaluated condition, the presence of the adjacent towers phases.
does not affect the peak overvoltage either for the underbuilt The results also show that the coupling effect is raised for de-
wires terminated at the adjacent towers or 30 m away. creasing grounding resistance. The drain off current and the cou-
The conclusions of the aforementioned paragraph are pre- pling effect are responsible, respectively, for 59% and 41% for a
served even when the tower-footing resistance of the adjacent 40- tower-footing grounding resistance and 44% and 56% for
towers is varied in the 10- to 40- range. Fig. 8 shows that this a 20- grounding resistance.
variation has no effect on peak voltages.
The results also indicate that extending the underbuilt wires IV. DISCUSSION ON THE REPRESENTATIVENESS OF RESULTS
along only the spans adjacent to the tower is enough to ensure Taking into account all of the approaches adopted so far to
the overvoltage decrease. This finding makes this technique suit- ease the developed sensitivity analysis, notably concerning the
able for mitigation at hot spots (e.g., where a tower is very ex- lightning current waveform, and the fact that all evaluations
posed due to its excessive height). were developed for only one transmission-line configuration, it
210 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 1, JANUARY 2012

Fig. 9. Influence of the current front time on the reduction of the developed
overvoltage across (a) upper- and (b) lower-insulator strings due to a direct strike
to the tower (triangular current wave).

Fig. 11. Overvoltage developed across insulator strings due to the strike of a
realistic current wave to the tower top with one and two underbuilt wires. (a)
Upper insulator string. (b) Lower insulator string.
Fig. 10. Representation of the first-stroke return current. Adapted from [21].

TABLE VIII
PEAK OVERVOLTAGES ACROSS INSULATOR STRINGS DUE TO THE STRIKE OF A
REALISTIC CURRENT WAVE TO THE TOWER TOP (Rg = 20 )
TABLE VII
MEDIAN PARAMETERS OF THE FIRST NEGATIVE STROKE CURRENTS ADOPTED
TO REPRESENT THE CURVE ILLUSTRATED IN FIG. 10

seems prudent to check the impact on the results of considering


more realistic representation of lightning current and other line
The impression of the current represented in Fig. 10 on the
configurations.
tower top was simulated to evaluate how representative are the
A. Influence of the Current Front-Time on the Overvoltage results previously developed. The overvoltages across insulator
Reduction Obtained From the Technique strings were calculated considering the application of the un-
conventional technique and a 20- grounding- resistance tower.
In this perspective, the influence of the front time on the re- The results are shown in Fig. 11. In order to make the results
sults was evaluated varying this parameter within a typical range compatible with the previous ones, the instantaneous values of
of first-stroke currents, from 2 to 6 s, still considering the tri- resulting voltage were divided by the peak current, 45.3 kA, to
angular current waveform. find the results in kilovolts/kiloamperes.
The simulated results presented in Fig. 9 show that basically The results indicated in Table VIII show basically the same
the shorter the front time, the more effective the technique is, percentage of overvoltage reductions promoted by the technique
though the effect of this parameter in the investigated range for the 2/50- s triangular current wave and for the typical first
seems quite reduced. stroke current. Similar results were obtained for towers with
equal to 10 and 40 .
B. Reduction of Overvoltages Developed for a Realistic In order to speculate on the impact of the recommended prac-
Representation of Lightning Currents tice on the lightning performance of transmission lines, rough
As discussed in [17], the individual downward first-stroke estimates of the outage-rate decrease due to the use of two un-
lightning current presents very particular waveform character- derbuilt wires were developed for lightning strikes to the towers,
istics, including an initial concavity followed by an abrupt rise considering the current waveform of Fig. 10.
around the half-peak value and several subsidiary peaks, with The integration method [22] was used with the coefficients
the second peak being usually higher than the first one. Fig. provided by Hileman in [23] to determine the peak voltage re-
10 and Table VII depict such typical waveform and the me- quired to flashover, assuming a CFO of 1.2 MV for the 230-kV
dian parameters of first-stroke currents measured at Morro do line. Based on the cumulative distribution of first-stroke peak
Cachimbo Station [18]. This waveform is quite similar to the currents of the Morro do Cachimbo Station [18], the percent-
typical waveform of Berger measurements [19], [20]. ages of currents expected to flash over due to lightning strikes
VISACRO et al.: USE OF UNDERBUILT WIRES 211

TABLE IX
PERCENTAGE OF CURRENTS EXCEEDING THE PEAK REQUIRED TO FLASH OVER
AS A FUNCTION OF TOWER-FOOTING GROUNDING RESISTANCE

Fig. 13. Details of the underbuilt-wires positioning. C, Le, and Ri mean cen-
tral, left and right insulator strings. The distance d for (a) and (b) is about 5 m,
whereas for (c) and (d), d is about 4 m. The dotted line and the “x” indicate that
the underbuilt wire reaches the tower on its right side and departs from its left
side.

TABLE X
PEAK OVERVOLTAGE REDUCTION DUE TO THE APPLICATION OF THE
UNCONVENTIONAL TECHNIQUE FOR THE LINE CONFIGURATION OF FIG. 12(a).
INJECTED CURRENT TO THE TOWER TOP: 2/50-s TRIANGULAR CURRENT
WAVE. Rg = 20

Fig. 12. Other tested configurations of towers (lightning strike to the right
shield wire at the tower top).

to the towers are indicated in Table IX for different grounding


resistance values.
The authors feel it is instructive to develop a rehearsal of the
TABLE XI
line response to the use of underbuilt wires, as described next. PEAK OVERVOLTAGE REDUCTION DUE TO THE APPLICATION OF THE
An average lightning collective zone around 100-m wide UNCONVENTIONAL TECHNIQUE FOR THE LINE CONFIGURATION OF FIG. 12(b).
for the line with 40-m-high towers and a flash density of 4 INJECTED CURRENT TO THE TOWER TOP: 2/50-s TRIANGULAR CURRENT
WAVE. Rg = 20
flash km year are assumed, leading to an expectation of 40
strikes/100 km/year to the line. In this simplified approach, the
distribution of tower-footing grounding resistances is consid-
ered to have the values 40, 30, 20, and below 10 with 10%,
10%, 20%, and 60% percentages, respectively. The outage rate
of 3.27 outages/100 km/year is calculated from the values of
Table IX.
It is assumed that a two-step improvement of the line is
developed.
First, all 30- resistances are decreased to 20 , working derbuilt wires is illustrated in Fig. 13. The simulated results are
only on the grounding electrode arrangement and length. This presented in Tables X–XI.
single improvement decreases the outage rate to 2.54 outage/ The results show reductions of overvoltage of the same mag-
100 km/year (23% less than the original value). nitude obtained for the line configuration of Fig. 2 since similar
In the following improvement, two underbuilt wires are distances are observed between phase conductors and underbuilt
installed, but only at the 40- grounding resistance towers. wires. An exception to this rule is the use of only one under-
This further improvement decreases the ratio to the half value, built wire in Fig. 13(c), where the reduction is a little lower.
1.26 outages/100 km/year. They are also consistent with evaluations previously performed
Even this rough estimate denotes that the use of underbuilt by the authors with lines of lower voltage levels, in particular,
wires can promote a significant reduction of the outage rate. those shown in [10] for a 69-kV line. In fact, for such lines with
a lower voltage level, it is possible to diminish the distance be-
C. Overvoltage Reductions Obtained for Different tween phase conductors and underbuilt wires to obtain an ad-
Transmission-Line Configurations ditional reduction of overvoltages, with further improvement of
The validity of the previous results when the unconventional results.
technique is applied to other line configurations was also evalu-
ated in this work. Two other configurations represented in Fig. V. SUMMARY AND CONCLUSIONS
12 and corresponding to existing 230-kV lines, extensively in- Results of reducing overvoltage across the insulator strings of
stalled in Brazil, were considered. The positioning of the un- a lightning-struck tower for existing 230-kV transmission lines
212 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 1, JANUARY 2012

with the addition of underbuilt wires are presented and denote [4] S. Visacro, “A comprehensive approach to the grounding response
the high potential of this technique to improve the lightning per- to lightning currents,” IEEE Trans. Power Del., vol. 22, no. 1, pp.
381–386, Jan. 2007.
formance of transmission lines. [5] R. Verma and D. Mukhedkar, “Impulse impedance of buried
The results were obtained by means of simulation using the ground wire,” IEEE Trans Power App. Syst., vol. PAS-99, no. 5,
HEM model and they showed that, for a given tower, the in- pp. 2003–2007, Sep. 1980.
[6] IEEE Guide for Improving the Lightning Performance of Transmission
stallation of additional wires along only the two adjacent spans Lines, IEEE Standard 1243-1997, 1997.
yields significant lightning overvoltage reduction. [7] Working Group 01 (Lightning), Study Committee 33, “CIGRE guide
The reduction effect results from the coupling between phase to procedures for estimating the lightning performance of transmission
lines,” 1991.
conductors and underbuilt wires and the draining off part of the [8] S. Visacro, M. A. Felipe, and R. Z. Oliveira, “Non-conventional
lightning current that would otherwise flow through one tower’s methodology to improve the lightning performance of transmission
grounding resistance. For tower-footing grounding resistances lines,” in Proc. Int. Conf. Grounding and Earthing, Rio de Janeiro,
Brazil, 2002, pp. 267–270.
around and above 40 , the draining-off effect prevails as the [9] S. Visacro, A. J. Soares, R. Oliveira, M. Felipe, A. Silva, and M. H.
main mechanism to reduce overvoltage. This is just the recom- Vale, “Non-conventional measures for improvement of lightning per-
mended range for the use of underbuilt wires. The relevance of formance of transmission lines,” in Proc. 27th Int. Conf. Light. Protec-
tion, Avignon, France, 2004, pp. 684–687.
the coupling mechanism increases with decreasing grounding [10] A. P. Silva, “Improvement of lightning performance of transmission
resistances. lines: A system to provide required information and analyses of cases,”
For the analyzed 230-kV lines, the reductions of lightning (in Portuguese) M.Sc. dissertation, Electrical Eng. Graduate Program
(PPGEE), Federal Univ. Minas Gerais (UFMG), Belo Horizonte,
overvoltage across upper insulator strings are very significant, Brazil, 2005.
around 19% and 26% for 20- grounding-resistance towers, [11] S. Visacro, E. P. Antunes, V. G. Machado, and V. T. Guedes, “Im-
respectively, for the addition of one and two underbuilt wires. proving the lightning performance of 69 KV to 230 KV transmission
lines,” in Proc. Int. Conf. Ground. Earth. and 2nd Int. Conf. Light. Phys.
These reductions are larger with increasing values of grounding Effects, Maceió, Brazil, 2006, pp. 329–332.
resistance, being around 23% and 31% for 40- grounding re- [12] S. Visacro, F. H. Silveira, M. Batista, and B. D. Rodrigues, “Exploring
sistance, and 32% and 44% for 80- grounding resistance. The a non-conventional technique to improve the lightning performance
of transmission lines,” in Proc. Int. Conf. Ground. Earth. and 4th Int.
effect is so significant that it exceeds the one promoted by re- Conf. Light. Phys. Effects, Salvador, Brazil, 2010, pp. 188–191.
ducing the value of the tower-footing grounding resistance to a [13] S. Visacro and A. J. Soares, “HEM: A model for simulation of light-
half. ning-related engineering problems,” IEEE Trans. Power Del., vol. 20,
no. 2, pt. 1, pp. 1206–1208, Apr. 2005.
A relevant parameter to determine the intensity of voltage [14] A. J. Soares, M. A. O. Schroeder, and S. Visacro, “Transient voltages
reduction is the distance between underbuilt wires and phases. in transmission lines caused by direct lightning strikes,” IEEE Trans.
The shorter the distance, the larger the reduction is. That means Power Del., vol. 20, no. 2, pt. 2, pp. 1447–1452, Apr. 2005.
[15] W. A. Chisholm, Y. L. Chow, and K. D. Srivastava, “Lightning surge
that for lines with lower voltage level, whose distance can response of transmission towers,” IEEE Trans.Power App Syst., vol.
be decreased to values below 4 m without compromising the PAS-102, no. 9, pp. 3232–3242, Sep. 1983.
electrical insulation, the overvoltage reduction can be further [16] “Handbook for improving overhead transmission line lightning perfor-
mance,” EPRI, Palo Alto, CA, 2004, Rep. 1002019.
increased. [17] S. Visacro, “A representative curve for lightning current waveshape
The evaluations with representative conditions of lightning of first negative stroke,” Geophys. Res. Lett., vol. 31, p. L07112, Apr.
current and different configurations of line ensure a certain gen- 2004.
[18] S. Visacro, M. A. O. Schroeder, A. J. Soares, L. C. L. Cherchiglia,
erality to the results of this paper that indicate that the uncon- and V. J. Sousa, “Statistical analysis of lightning current parameters:
ventional technique might promote minimum reductions of the Measurements at Morro do Cachimbo station,” J. Geophys. Res., vol.
overvoltages in the ranges of 19% to 32% and 26 to 44% for 20- 109, no. D01105, pp. 1–11, 2004.
[19] K. Berger, R. B. Anderson, and H. Kroninger, “Parameters of lightning
to 80- tower-footing grounding resistances with the addition flashes,” Electra, no. 80, pp. 223–237, 1975.
of one and two underbuilt wires, respectively. This denotes the [20] R. B. Anderson and A. J. Eriksson, “Lightning parameters for engi-
worthiness of this technique as a complementary practice to be neering application,” Electra, vol. 69, pp. 65–102, 1980.
[21] A. De Conti and S. Visacro, “Analytical representation of single- and
used in critical spots along the line that present so unfavorable double-peaked lightning current waveforms,” IEEE Trans. Electro-
soil-resistivity conditions that decreasing the grounding resis- magn. Compat., vol. 49, no. 2, pp. 448–451, May 2007.
tance to ensure an appropriate response to lightning strikes is [22] M. Darveniza and A. E. Vlastos, “The generalized integration method
for predicting impulse volt-time characteristics for non-standard wave
not feasible. shapes—A theoretical basis,” IEEE Trans. Elect. Insul., vol. 23, no. 3,
It is prudent to observe the need for an in-depth evaluation of pp. 373–381, Jun. 1988.
the impact of using such techniques in existing lines, taking into [23] A. H. Hileman, Insulation Coordination for Power Systems. Boca
Raton, FL: CRC, 1999, pp. 627–640.
account all side effects, such as efforts due to the wind forces
acting on the additional wires. This effect, in particular, can be Silverio Visacro (M’00) received the B.Sc. and
compensated by including guy wires to the tower. M.Sc. degrees in electrical engineering from the
Federal University of Minas Gerais (UFMG), Belo
Horizonte, in 1980 and 1984, respectively, and the
REFERENCES Ph.D. degree from the University of Rio de Janeiro,
[1] S. Visacro, “Direct strokes to transmission lines: Considerations on the Rio de Janeiro, Brazil, in 1992.
mechanisms of overvoltage formation and their influence on the light- Since 1980, he has been with UFMG, working in
ning performance of lines,” J. Light. Res., vol. 1, pp. 60–68, 2007. Applied Electromagnetics. Currently, he is Full Pro-
[2] “Electrical Transmission and Distribution Reference Book,” 4th ed. fessor of the Electrical Engineering Department and
Central Station of Engineers of the Westinghouse Electric Corporation, the Head of the Lightning Research Center (LRC).
East Pittsburgh, PA, 1964. He has developed many investigation projects of a
[3] S. Visacro, Lightning: An Engineering Approach (in Portuguese). theoretical and applied nature and is responsible for a successful relationship
São Paulo, Brazil: Artliber Editora, 2005, pp. 1–272. between his university and industry in his fields of activity. He has authored
VISACRO et al.: USE OF UNDERBUILT WIRES 213

or coauthored many scientific papers published in reviewed journals and Alberto De Conti was born in Belo Horizonte,
presented at international conferences. He is the author of two books on Brazil, on August 3, 1975. He received the Techni-
lightning and grounding, respectively. He is an Associate Editor of the Journal cian degree in industrial electronics from the Federal
of Lightning Research. He is a regular reviewer of the IEEE TRANSACTIONS ON Center of Technologic Education (CEFET-MG),
ELECTROMAGNETIC COMPATIBILITY and the IEEE TRANSACTIONS ON POWER Belo Horizonte, Brazil, in 1994 and the B.Sc., M.Sc.,
DELIVERY. His current research interests include electromagnetic modeling, and Ph.D. degrees in electrical engineering from the
lightning physics, as well as protection and grounding. Federal University of Minas Gerais (UFMG), Belo
Prof. Visacro is an effective member of the American Geophysical Union Horizonte, in 2000, 2001, and 2006, respectively.
(AGU) and International Council on Large Electric Systems (CIGRE), where he In 2006, he was a Guest Researcher in the Divi-
convened the Working Group “Response of Grounding Electrodes to Lightning sion for Electricity and Lightning Research, Uppsala
Currents.” University, Uppsala, Sweden. Currently, he is a Full-
Time Lecturer with the Department of Electrical Engineering, UFMG, where
he is also an Associate Researcher with the Lightning Research Center (LRC).
His research interests include lightning, lightning interaction with electrical sys-
Fernando H. Silveira was born in São Paulo, Brazil, tems, electromagnetic transients, electromagnetic modeling, and electromag-
on May 18, 1977. He received the B.S., M.S., and Dr. netic compatibility.
Eng. degrees in electrical engineering from the Fed-
eral University of Minas Gerais (UFMG), Belo Hor-
izonte, Brazil, in 2000, 2001, and 2006, respectively.
Currently, he is a Full-Time Lecturer with the
Department of Electrical Engineering, UFMG,
where he is also an Associate Researcher with
the Lightning Research Center (LRC). His current
research interests include electromagnetic modeling,
electromagnetic transients, lightning, lightning-in-
duced voltages, lightning interaction with electrical systems, and lightning
performance of transmission lines.
Dr. Silveira is a regular reviewer of the IEEE TRANSACTIONS ON
ELECTROMAGNETIC COMPATIBILITY and the IEEE TRANSACTIONS ON POWER
DELIVERY.

You might also like