Professional Documents
Culture Documents
Abstract—An unconventional technique to improve the lightning rameter typically used to characterize the response of electrodes
performance of transmission lines, consisting of the addition of subjected to lightning currents. Nevertheless, the measurement
grounded wires properly positioned below the phase conductors, of this impedance is not feasible in field conditions. Since, under
is assessed. Overvoltages developed across insulator strings of ex-
isting 230-kV lines in response to direct strikes to the towers were certain circumstances, both parameters are related, the mea-
simulated using an electromagnetic model. Minimum reductions sured low-frequency resistance is used to verify the grounding
of these voltages in the ranges of 19%–32% and 26%–44% were quality instead of the impedance, as discussed in [4].
achieved for 20- to 80- tower-footing grounding resistances due The literature refers to some nonconventional practices
to the addition of one and two underbuilt wires, respectively. This to improve the lightning performance of transmission lines.
practice was shown to be more efficient than reducing the tower
grounding resistance to its half value.
These practices explore effects of parameters that influence
the amplitude of overvoltages developed across insulator
Index Terms—Lightning, lightning overvoltage, lightning per- strings when lightning strikes the line, notably the tower surge
formance of transmission lines, transmission lines.
impedance, and the electromagnetic coupling between shield
wires and phases. It suggests the possibility of using guy
I. INTRODUCTION wires, continuous counterpoise, or metallic wires placed below
phase conductors, as alternative solutions to improve the line
IGHTNING is a frequent cause of transmission-line out-
L ages, reducing the availability of electrical networks. Ba-
sically, three mechanisms are responsible for developing light-
response to direct strikes [6], [7]. Despite these suggestions,
the literature deals very poorly with the problems involved in
their implementation, and no quantitative evaluation of their
ning overvoltages in high-voltage lines that might result in elec- efficiency is provided.
trical discharges across insulator strings, leading to faults: the In this perspective, this paper addresses an unconventional
flashover, associated with strikes to phase conductors; the back- technique and quantifies the improvement it might produce on
flashover, associated with strikes to the tower or to shield wires the lightning performance of lines, taking as reference an ex-
at the tower vicinities; and the midspan flashover, as detailed in isting 230-kV line, used as a case study.
[1] and [2].
For transmission lines below 500 kV installed in regions of II. DEVELOPMENTS
unfavorable soil-resistivity conditions, the backflashover largely
prevails [3]. Therefore, this mechanism, which is mainly gov- A. Describing the Technique
erned by the value of tower-footing grounding impedance, is The technique consists of the addition of metallic wires
the main focus of techniques intended to improve the lightning installed below the phase conductors at proper distances and
performance of such lines. connected to the tower that requires lightning performance
The conventional practices to decrease the frequency of back- improvement. The underbuilt wires are extended only along the
flashover events comprise basically two actions: 1) the reduc- two spans adjacent to the tower. In this paper, steel wires were
tion of tower footing resistance and 2) the installation of surge tested, though any metallic wire could be used. This technique,
arresters to prevent flashovers. Most power utilities concentrate explored by the authors in a sequence of works since 2002
their efforts in the first practice due to the costs associated with [8]–[12], has provided encouraging results in terms of reducing
the installation and maintenance of line surge arresters. It is lightning overvoltages developed in response to direct strikes
worth mentioning that reducing grounding resistance is an in- to the line, and it is here refined.
direct way to achieve the actual goal, which is to decrease the Two arrangements of practical interest were identified in sim-
tower-footing grounding impedance. As explained in [4] and ulations, corresponding to the addition of one and two under-
[5], the low-frequency grounding resistance can be quite dif- built wires as indicated in Fig. 1. Observing a minimum distance
ferent from impulsive grounding impedance, which is the pa- “ ” is required to avoid diminishing the electrical insulation of
the transmission line.
Manuscript received April 03, 2011; revised July 12, 2011; accepted August
27, 2011. Date of publication October 18, 2011; date of current version De- B. Methodology of Development
cember 23, 2011. Paper no. TPWRD-00260-2011.
The authors are with the Lightning Research Center (LRC) of Federal Uni- The proposed arrangements and the efficiency of this tech-
versity of Minas Gerais (UFMG), Belo Horizonte 31270-901, Brazil (e-mail: nique were accessed by systematic simulation using the hybrid
LRC@cpdee.ufmg.br). electromagnetic model (HEM). This frequency-domain model,
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. described in detail in [13], has been widely employed to deter-
Digital Object Identifier 10.1109/TPWRD.2011.2168546 mine voltage and current distributions in lightning-related prob-
0885-8977/$26.00 © 2011 IEEE
206 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 1, JANUARY 2012
TABLE I
PEAK VALUES OF OVERVOLTAGES ACROSS THE UPPER AND LOWER INSULATOR
STRINGS AS A FUNCTION OF GROUNDING-RESISTANCE VALUES
Fig. 4. Overvoltage across (a) upper and (b) lower insulator strings for different
grounding-resistance values (2/50-s triangular current wave).
Fig. 5. Reduction of overvoltage across the upper insulator string as a function Fig. 6. Effect of the addition of underbuilt wires on the overvoltages developed
of grounding-resistance value. across the upper (a) and lower (b) insulator strings (Rg = 20 and d = 4 m).
the shield wires at tower vicinities, with this amplitude dimin- tion around 66 and 71%, respectively, across upper and lower
ishing with decreasing impedance [15]. This explains why the insulator strings.
most common practice to improve lightning performance con- Considering a 50-kA peak-current strike, the overvoltage de-
sists in reducing the grounding impedance, with this measure veloped for of 40 would be decreased from about 1.4 MV
being quantified through the value obtained for the grounding to 700 kV for of 10 , achieving a value quite lower than the
resistance [4]. 230-kV-line critical flashover voltage (CFO), around 1.2 MV.
In order to establish references to measure the improvement Voltages above this CFO would be developed for values of
obtained from the application of the proposed unconventional a little above 30 .
technique, this section considers the effect of decreasing
grounding resistance on reducing overvoltages developed B. Applying the Technique: First Results Concerning the
across insulator strings of the existing line during direct strike Effect of Using One and Two Underbuilt Wires
events. Two simple arrangements of special interest because of their
Fig. 4 shows the overvoltage waves resulting across the upper practical feasibility and efficiency were identified from the sys-
and lower insulator strings due to a strike to the tower top with tematic application of the HEM model. They correspond to the
all of the assumptions indicated in Sections II-B and C, and addition of one and two underbuilt wires as indicated in Fig. 1.
considering the tower grounding resistance ( ) varying from Fig. 6 shows overvoltage waves developed across insulator
10 to 80 . The values of were obtained assuming the same strings (in kilovolt/kiloamperes) in response to the impression
arrangement of electrodes of Fig. 3(b) was buried in soils of of a 2/50- s triangular current wave on the tower top associated
different resistivity. The peak values of such overvoltages and with a direct lightning strike, considering the addition of one and
the percentage of voltage reduction are indicated as a function two underbuilt wires according to the arrangement of Fig. 1 and
of in Table I and Fig. 5. 4 m for distance “ .” A soil resistivity of 1600- m was used in
The results in Figs. 4 and 5 and Table I reveal the efficiency simulations, corresponding to a 20- grounding resistance for
of decreasing grounding resistance to improve the lightning per- the electrode arrangement defined in Fig. 3(b).
formance of transmission lines. While this resistance decreased The addition of underbuilt wires decreases the overvoltages
from 80 to 10 , the overvoltage varies from the order of 44 to very significantly and this reduction is larger for the lower in-
15 kV/kA. This corresponds to a lightning overvoltage reduc- sulator string. The addition of one wire promotes a reduction of
208 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 1, JANUARY 2012
TABLE II TABLE V
DECREASE OF PEAK OVERVOLTAGE DUE TO THE APPLICATION DECREASE OF PEAK OVERVOLTAGE DUE TO THE APPLICATION
OF THE UNCONVENTIONAL TECHNIQUE FOR Rg = 10 OF THE UNCONVENTIONAL TECHNIQUE FOR Rg = 80
TABLE III wire reduces the overvoltage across the upper and lower insu-
DECREASE OF PEAK OVERVOLTAGE DUE TO THE APPLICATION
OF THE UNCONVENTIONAL TECHNIQUE FOR Rg = 20 lator strings to 77% and 69% of the original value, respectively.
This effect is more pronounced than the reduction obtained by
decreasing the grounding resistance to 30 . The addition of
two underbuilt wires promotes reductions to 69% and 58%. This
result is better than that obtained by decreasing to 20 .
This means this technique is more efficient than reducing the
grounding resistance to its half value. If one considers a 50-kA
strike to the 40- grounding-resistance tower, the peak-voltage
of 1.35 MV across upper string, exceeding the line CFO, would
TABLE IV
DECREASE OF THE PEAK OVERVOLTAGE DUE TO THE APPLICATION OF THE
be decreased to 935 kV, lower than the line CFO.
NONCONVENTIONAL TECHNIQUE FOR Rg = 40 The aforementioned analysis denotes the possibility of em-
ploying such a technique as a complementary resource in a
very unfavorable soil-resistivity condition, where no efficient
grounding solution is obtained to ensure appropriate lightning
performance of transmission lines. These conditions occur
frequently; for example, when the limited length of long
lines crosses mountainous regions, presenting rocky and high
resistivity soils that make it unfeasible to achieve values of
tower-footing grounding resistance low to the extent required
around 19 and 28% for the upper and lower string, respectively, to ensure appropriate lightning performance along this length.
while the reduction is much larger for the addition of two wires, It is worth mentioning that underbuilt wires are not expected
around 26 and 38%. to cause losses due to low-frequency circulating currents, since
It is worth mentioning the very small increase of costs of an their use is typically recommended along short lengths of line.
intervention to install two underbuilt wires instead of one. Since
a return of about 40% is obtained when two wires are used in- D. Influence of the Distance Between Underbuilt Wires and
stead of one (overvoltage reduction of 26% against 19%), the Phase Conductors
use of two underbuilt wires is rather preferable. The distance “ ” indicated in Fig. 1 varied from 4 to 8 m.
Some parameters might influence the decrease of lightning Distances shorter than 4 m would jeopardize the line insulation
overvoltages obtained from the technique application as ex- level. Table VI shows the effect of varying the distance between
plained next. underbuilt wire(s) and phase conductors, considering a 20-
grounding-resistance tower. It is shown that increasing this dis-
C. Influence of Tower Grounding Resistance tance decreases the overvoltage reduction. Similar results were
In order to verify the sensitivity of the overvoltage reduction obtained for towers with of 10 and 40 . Therefore, the dis-
in relation to the grounding-resistance value, the same simu- tance “ ” should be the lowest value that still ensures the insu-
lation of the preceding section was developed considering the lation level of the line.
tower resistance , varying from 80 to 10 . Tables II–V show Increasing distance “ ” contributes to reducing the electro-
the overvoltage reduction in each case. magnetic coupling between phase conductors and underbuilt
The results provided by the technique are improved with in- wires, and the drain off part of the lightning current that would
creasing tower-footing grounding resistance. The voltage reduc- otherwise flow through one tower’s grounding resistance. Both
tions across the upper insulator string for a 10- grounding-re- mechanisms are responsible for decreasing lightning overvolt-
sistance tower, around 16% and 24% for one and two underbuilt ages, as discussed in Section III-F. This explains the decrease
wires, are increased to 32% and 44% for a 80- tower-footing. of overvoltage reductions with increasing “ .”
Across the lower strings, such values evolve from 26% and 36%
to 39% and 53%, respectively. E. Effect of Adjacent Towers
The comparison of the results of Table I with those of Ta- So far, the presented results correspond to simulations
bles II–V reveals the high potential of this unconventional tech- that represent all wires sustained by the tower as 30-m-long
nique. Considering 40 , the addition of one underbuilt impedance-matched conductors, as described in Section II-C .
VISACRO et al.: USE OF UNDERBUILT WIRES 209
TABLE VI
PEAK OVERVOLTAGES AS A FUNCTION OF DISTANCE BETWEEN PHASE
CONDUCTORS AND UNDERBUILT WIRES FOR Rg = 20
Fig. 9. Influence of the current front time on the reduction of the developed
overvoltage across (a) upper- and (b) lower-insulator strings due to a direct strike
to the tower (triangular current wave).
Fig. 11. Overvoltage developed across insulator strings due to the strike of a
realistic current wave to the tower top with one and two underbuilt wires. (a)
Upper insulator string. (b) Lower insulator string.
Fig. 10. Representation of the first-stroke return current. Adapted from [21].
TABLE VIII
PEAK OVERVOLTAGES ACROSS INSULATOR STRINGS DUE TO THE STRIKE OF A
REALISTIC CURRENT WAVE TO THE TOWER TOP (Rg = 20 )
TABLE VII
MEDIAN PARAMETERS OF THE FIRST NEGATIVE STROKE CURRENTS ADOPTED
TO REPRESENT THE CURVE ILLUSTRATED IN FIG. 10
TABLE IX
PERCENTAGE OF CURRENTS EXCEEDING THE PEAK REQUIRED TO FLASH OVER
AS A FUNCTION OF TOWER-FOOTING GROUNDING RESISTANCE
Fig. 13. Details of the underbuilt-wires positioning. C, Le, and Ri mean cen-
tral, left and right insulator strings. The distance d for (a) and (b) is about 5 m,
whereas for (c) and (d), d is about 4 m. The dotted line and the “x” indicate that
the underbuilt wire reaches the tower on its right side and departs from its left
side.
TABLE X
PEAK OVERVOLTAGE REDUCTION DUE TO THE APPLICATION OF THE
UNCONVENTIONAL TECHNIQUE FOR THE LINE CONFIGURATION OF FIG. 12(a).
INJECTED CURRENT TO THE TOWER TOP: 2/50-s TRIANGULAR CURRENT
WAVE. Rg = 20
Fig. 12. Other tested configurations of towers (lightning strike to the right
shield wire at the tower top).
with the addition of underbuilt wires are presented and denote [4] S. Visacro, “A comprehensive approach to the grounding response
the high potential of this technique to improve the lightning per- to lightning currents,” IEEE Trans. Power Del., vol. 22, no. 1, pp.
381–386, Jan. 2007.
formance of transmission lines. [5] R. Verma and D. Mukhedkar, “Impulse impedance of buried
The results were obtained by means of simulation using the ground wire,” IEEE Trans Power App. Syst., vol. PAS-99, no. 5,
HEM model and they showed that, for a given tower, the in- pp. 2003–2007, Sep. 1980.
[6] IEEE Guide for Improving the Lightning Performance of Transmission
stallation of additional wires along only the two adjacent spans Lines, IEEE Standard 1243-1997, 1997.
yields significant lightning overvoltage reduction. [7] Working Group 01 (Lightning), Study Committee 33, “CIGRE guide
The reduction effect results from the coupling between phase to procedures for estimating the lightning performance of transmission
lines,” 1991.
conductors and underbuilt wires and the draining off part of the [8] S. Visacro, M. A. Felipe, and R. Z. Oliveira, “Non-conventional
lightning current that would otherwise flow through one tower’s methodology to improve the lightning performance of transmission
grounding resistance. For tower-footing grounding resistances lines,” in Proc. Int. Conf. Grounding and Earthing, Rio de Janeiro,
Brazil, 2002, pp. 267–270.
around and above 40 , the draining-off effect prevails as the [9] S. Visacro, A. J. Soares, R. Oliveira, M. Felipe, A. Silva, and M. H.
main mechanism to reduce overvoltage. This is just the recom- Vale, “Non-conventional measures for improvement of lightning per-
mended range for the use of underbuilt wires. The relevance of formance of transmission lines,” in Proc. 27th Int. Conf. Light. Protec-
tion, Avignon, France, 2004, pp. 684–687.
the coupling mechanism increases with decreasing grounding [10] A. P. Silva, “Improvement of lightning performance of transmission
resistances. lines: A system to provide required information and analyses of cases,”
For the analyzed 230-kV lines, the reductions of lightning (in Portuguese) M.Sc. dissertation, Electrical Eng. Graduate Program
(PPGEE), Federal Univ. Minas Gerais (UFMG), Belo Horizonte,
overvoltage across upper insulator strings are very significant, Brazil, 2005.
around 19% and 26% for 20- grounding-resistance towers, [11] S. Visacro, E. P. Antunes, V. G. Machado, and V. T. Guedes, “Im-
respectively, for the addition of one and two underbuilt wires. proving the lightning performance of 69 KV to 230 KV transmission
lines,” in Proc. Int. Conf. Ground. Earth. and 2nd Int. Conf. Light. Phys.
These reductions are larger with increasing values of grounding Effects, Maceió, Brazil, 2006, pp. 329–332.
resistance, being around 23% and 31% for 40- grounding re- [12] S. Visacro, F. H. Silveira, M. Batista, and B. D. Rodrigues, “Exploring
sistance, and 32% and 44% for 80- grounding resistance. The a non-conventional technique to improve the lightning performance
of transmission lines,” in Proc. Int. Conf. Ground. Earth. and 4th Int.
effect is so significant that it exceeds the one promoted by re- Conf. Light. Phys. Effects, Salvador, Brazil, 2010, pp. 188–191.
ducing the value of the tower-footing grounding resistance to a [13] S. Visacro and A. J. Soares, “HEM: A model for simulation of light-
half. ning-related engineering problems,” IEEE Trans. Power Del., vol. 20,
no. 2, pt. 1, pp. 1206–1208, Apr. 2005.
A relevant parameter to determine the intensity of voltage [14] A. J. Soares, M. A. O. Schroeder, and S. Visacro, “Transient voltages
reduction is the distance between underbuilt wires and phases. in transmission lines caused by direct lightning strikes,” IEEE Trans.
The shorter the distance, the larger the reduction is. That means Power Del., vol. 20, no. 2, pt. 2, pp. 1447–1452, Apr. 2005.
[15] W. A. Chisholm, Y. L. Chow, and K. D. Srivastava, “Lightning surge
that for lines with lower voltage level, whose distance can response of transmission towers,” IEEE Trans.Power App Syst., vol.
be decreased to values below 4 m without compromising the PAS-102, no. 9, pp. 3232–3242, Sep. 1983.
electrical insulation, the overvoltage reduction can be further [16] “Handbook for improving overhead transmission line lightning perfor-
mance,” EPRI, Palo Alto, CA, 2004, Rep. 1002019.
increased. [17] S. Visacro, “A representative curve for lightning current waveshape
The evaluations with representative conditions of lightning of first negative stroke,” Geophys. Res. Lett., vol. 31, p. L07112, Apr.
current and different configurations of line ensure a certain gen- 2004.
[18] S. Visacro, M. A. O. Schroeder, A. J. Soares, L. C. L. Cherchiglia,
erality to the results of this paper that indicate that the uncon- and V. J. Sousa, “Statistical analysis of lightning current parameters:
ventional technique might promote minimum reductions of the Measurements at Morro do Cachimbo station,” J. Geophys. Res., vol.
overvoltages in the ranges of 19% to 32% and 26 to 44% for 20- 109, no. D01105, pp. 1–11, 2004.
[19] K. Berger, R. B. Anderson, and H. Kroninger, “Parameters of lightning
to 80- tower-footing grounding resistances with the addition flashes,” Electra, no. 80, pp. 223–237, 1975.
of one and two underbuilt wires, respectively. This denotes the [20] R. B. Anderson and A. J. Eriksson, “Lightning parameters for engi-
worthiness of this technique as a complementary practice to be neering application,” Electra, vol. 69, pp. 65–102, 1980.
[21] A. De Conti and S. Visacro, “Analytical representation of single- and
used in critical spots along the line that present so unfavorable double-peaked lightning current waveforms,” IEEE Trans. Electro-
soil-resistivity conditions that decreasing the grounding resis- magn. Compat., vol. 49, no. 2, pp. 448–451, May 2007.
tance to ensure an appropriate response to lightning strikes is [22] M. Darveniza and A. E. Vlastos, “The generalized integration method
for predicting impulse volt-time characteristics for non-standard wave
not feasible. shapes—A theoretical basis,” IEEE Trans. Elect. Insul., vol. 23, no. 3,
It is prudent to observe the need for an in-depth evaluation of pp. 373–381, Jun. 1988.
the impact of using such techniques in existing lines, taking into [23] A. H. Hileman, Insulation Coordination for Power Systems. Boca
Raton, FL: CRC, 1999, pp. 627–640.
account all side effects, such as efforts due to the wind forces
acting on the additional wires. This effect, in particular, can be Silverio Visacro (M’00) received the B.Sc. and
compensated by including guy wires to the tower. M.Sc. degrees in electrical engineering from the
Federal University of Minas Gerais (UFMG), Belo
Horizonte, in 1980 and 1984, respectively, and the
REFERENCES Ph.D. degree from the University of Rio de Janeiro,
[1] S. Visacro, “Direct strokes to transmission lines: Considerations on the Rio de Janeiro, Brazil, in 1992.
mechanisms of overvoltage formation and their influence on the light- Since 1980, he has been with UFMG, working in
ning performance of lines,” J. Light. Res., vol. 1, pp. 60–68, 2007. Applied Electromagnetics. Currently, he is Full Pro-
[2] “Electrical Transmission and Distribution Reference Book,” 4th ed. fessor of the Electrical Engineering Department and
Central Station of Engineers of the Westinghouse Electric Corporation, the Head of the Lightning Research Center (LRC).
East Pittsburgh, PA, 1964. He has developed many investigation projects of a
[3] S. Visacro, Lightning: An Engineering Approach (in Portuguese). theoretical and applied nature and is responsible for a successful relationship
São Paulo, Brazil: Artliber Editora, 2005, pp. 1–272. between his university and industry in his fields of activity. He has authored
VISACRO et al.: USE OF UNDERBUILT WIRES 213
or coauthored many scientific papers published in reviewed journals and Alberto De Conti was born in Belo Horizonte,
presented at international conferences. He is the author of two books on Brazil, on August 3, 1975. He received the Techni-
lightning and grounding, respectively. He is an Associate Editor of the Journal cian degree in industrial electronics from the Federal
of Lightning Research. He is a regular reviewer of the IEEE TRANSACTIONS ON Center of Technologic Education (CEFET-MG),
ELECTROMAGNETIC COMPATIBILITY and the IEEE TRANSACTIONS ON POWER Belo Horizonte, Brazil, in 1994 and the B.Sc., M.Sc.,
DELIVERY. His current research interests include electromagnetic modeling, and Ph.D. degrees in electrical engineering from the
lightning physics, as well as protection and grounding. Federal University of Minas Gerais (UFMG), Belo
Prof. Visacro is an effective member of the American Geophysical Union Horizonte, in 2000, 2001, and 2006, respectively.
(AGU) and International Council on Large Electric Systems (CIGRE), where he In 2006, he was a Guest Researcher in the Divi-
convened the Working Group “Response of Grounding Electrodes to Lightning sion for Electricity and Lightning Research, Uppsala
Currents.” University, Uppsala, Sweden. Currently, he is a Full-
Time Lecturer with the Department of Electrical Engineering, UFMG, where
he is also an Associate Researcher with the Lightning Research Center (LRC).
His research interests include lightning, lightning interaction with electrical sys-
Fernando H. Silveira was born in São Paulo, Brazil, tems, electromagnetic transients, electromagnetic modeling, and electromag-
on May 18, 1977. He received the B.S., M.S., and Dr. netic compatibility.
Eng. degrees in electrical engineering from the Fed-
eral University of Minas Gerais (UFMG), Belo Hor-
izonte, Brazil, in 2000, 2001, and 2006, respectively.
Currently, he is a Full-Time Lecturer with the
Department of Electrical Engineering, UFMG,
where he is also an Associate Researcher with
the Lightning Research Center (LRC). His current
research interests include electromagnetic modeling,
electromagnetic transients, lightning, lightning-in-
duced voltages, lightning interaction with electrical systems, and lightning
performance of transmission lines.
Dr. Silveira is a regular reviewer of the IEEE TRANSACTIONS ON
ELECTROMAGNETIC COMPATIBILITY and the IEEE TRANSACTIONS ON POWER
DELIVERY.