Professional Documents
Culture Documents
Segmented fence grounding should be considered when the Separate grounding, 1 m beyond
Grounding to the grid
2.5
distance of the fence from the substation grounding grid 1.6
1.5
electrically isolated parts to ensure safety. This is not a
0.8
difficult task for relatively small installations; for larger 1.0
otherwise,
therwise, flashover may occur transferring dangerous Fig. 2. Touch voltage computed along profiles (a) 1 and (b) 2 (near points A
and B in Fig. 1) parallel to the fence at a distance of 1 m from the latter for
potentials from one fence to another. Furthermore, the length all evaluated fence grounding techniques.
of such sections should be long enough, to avoid accidental
TABLE II
bridging between fences and coupling through the ground. GROUNDING ANALYSIS RESULTS FOR THE 150/20 kV SUBSTATION
For the evaluated 150/20 kV substation the fence could be
Fence Fence
segmented at its section being in closest proximity to the GPR Etouch,max Etouch,ave* Estep,max
grounding Rg potential
(kV) (kV) (kV) (kV)
grounding grid, that is, at the section near the ultimate technique (kV)
transmission tower (Fig. 1). To achieve a more efficient Separately grounded inside: 2.47
0.458 11.34 7.32 0.45 1.22
fence outside: 1.75
grounding design, this part of fence is moved within the grid Separately grounded inside: 2.9
area, leaving the tower outside the substation (Fig. 1, dashed 0.459 11.36 7.11 0.45 1.20
fence, 1 m beyond outside: 1.76
red line segment). This fence section is grounded to the grid Fence connected to
0.378 9.36 9.36
inside: 1.31
0.63 0.72
the grounding grid outside: 1.98
whereas the remaining part of the fence is connected to a
Segmented inside: 1
separate ground electrode, buried under the fence (depth: 0.6 0.457 11.31 7.12 0.40 0.78
fence grounding outside: 1.49
m). Insulating fence sections 6 m in length (Fig. 1, green line *
Average touch voltage along the fence, computed at profiles parallel to the fence line
at a distance of 1 m from the latter.
segments) are used to isolate the two different fence parts.
The maximum touch voltage along the fence section III. 400 kV STEP-UP GIS SUBSTATION
grounded to the grid is 1 kV, considerably lower than the The 400 kV GIS substation (Fig. 3) covers an area of
corresponding values obtained for the previously examined ~4500 m2. The most dangerous ground fault in this substation
fence grounding techniques. The average touch voltage along is a 400 kV single phase ground fault (If=40 kA, tf=0.5 s,
the fence decreases by ~11% when compared to the case of Sf=0.7). The decrement factor, Df, is calculated as 1.0427 for
separately grounded fence; the maximum touch voltage is a X/R ratio equal to 13.7. Thus, the maximum grid current, IG,
700
600
Initial grounding design
Final grounding design It is well known that touch and step voltages near the grid
500
periphery depend on mesh geometry and size in this area.
400 Touch voltages can be mitigated by reducing the mesh size at
300 grid perimeter, increasing consequently the surface potential.
200 Step voltages outside the fence can be reduced by increasing
100
the burial depth of the outer grid conductors; this, however,
0
0 5 10 15 20 leading to lower surface potential, causes higher touch
Profile 1 length (m)
600
Initial grounding design
Final grounding design
voltages. An additional measure to reduce step voltages is to
500
install deep rods at the perimeter of the grid, reducing also
400 touch voltages.
300 For the evaluated GIS substation safety against dangerous
200 step voltages outside the substation area could be achieved by
100 burying the peripheral grid conductors at a depth of 1.5 m
0
0 5 10 15 20
instead of 0.5 m. Furthermore, it is necessary to increase the
Profile 2 length (m)
length of the rods at the grid perimeter from 3 to 9 m and
Fig. 3. Grounding grid for the 400 kV step-up GIS substation; red line:
fence, empty circles: ground rods; green and blue circles represent
install three additional rods as illustrated in Fig. 3. The
respectively removed and additional ground rods in the final design. Graphs ground resistance and GPR are estimated
show step voltages computed along profiles 1 and 2. 5.96 kV respectively. The maximum touch voltage is found
1.14 kV, lower than in the initial design. As shown in Fig. 3,
is 29.2 kA. Based on soil resistivity measurements [12], [13], the maximum step voltage is reduced to 0.27 kV,
it was found that a uniform soil model with a resistivity of approximately equal to the allowable voltage limit.
actual soil conditions. IV. PHOTOVOLTAIC POWER STATION
Fig. 3 shows the substation grounding grid, designed based
on safety of people against the danger of critical electric Large scale photovoltaic (PV) power stations cover large
shock due to ground faults. The grid (maximum mesh size: areas and typically deliver power to the medium voltage
8x8 m) covers the whole substation area and it is installed at a distribution network. In many actual cases the distance
depth of 0.5 m. It comprises ~1300 m of tinned copper between the fence and the installation grounding grid varies
conductors (185 mm2) and 27 copper-clad steel rods 19 mm widely; this depends on property area covered and on the
in diameter and 3 m in length. The building housing the GIS provision of future expansion. In case of a ground fault, high
buses and switchgear is grounded through a foundation potentials appearing on the fence could be transferred in areas
ground electrode connected to the grounding grid. The entire away from the grid, posing therefore a threat to persons.
substation area is covered with a high resistivity surface Hence, cautious treatment of fence grounding should be
material ( s=5000 m, hs=0.2 m). The allowable touch and applied in large scale PV power stations to ensure safety.
step voltage limits with and without surface material In this work fence grounding of a 3 MWp PV power station
application were respectively calculated according to the (Fig. 4) is investigated. The total property area is ~98300 m2
IEEE Std [1], [2] as Etouch70=1.58 kV, Estep70=5.67 kV and whereas the 12 PV panel array groups cover ~58000 m2. As
Etouch70=0.23 kV, Estep70=0.27 kV. detailed in [15], the most dangerous ground fault is a 20 kV
The substation is protected by a chain-link fence with single phase ground fault (If=1 kA, tf=0.5 s, Sf=1). The
outward-inclined barbed wire on top. As the grounding grid decrement factor, Df, was calculated 1.0127 for a X/R ratio
covers the whole substation area, the fence is grounded to the equal to 4. Hence, the maximum grid current, IG, was found
grid. To reduce touch voltages, the fence (~280 m in length) 1012.7 A. A two-layer soil model was derived for the
is installed within the grid area at a distance up to 1.5 m from installation area (upper and lower layer resistivities: 2796 and
the periphery conductors. 7250 m, respectively, upper layer thickness 4.45 m).
The ground resistance is computed 0.223 , hence, the The safe grounding grid design for this PV power station
GPR is 6.51 kV. The maximum touch voltage is 1.38 kV has been presented in [15]. The grid comprises the concrete-
(point A in Fig. 3), lower than the corresponding limit with encased part of the steel piles supporting the PV panel arrays
surface material application. However, outside the boundaries as well as copper-clad steel ground conductors buried next to
of the substation, specifically up to ~4 m from the fence, step the arrays at a depth of 0.5 m interconnecting all metal
voltages with a maximum of 0.65 kV exceed the allowable support structures. The total number of piles is 3766 and the
limit without surface material application. As the application total length of ground conductors is ~1.7 km. The substations
of surface material outside the substation area is not possible, and the auxiliary building are grounded via a foundation
other measures should be considered to reduce the arising ground electrode along with a ring electrode surrounding
hazardous step voltages. It is noteworthy that high step them at a distance of 1 m from their boundaries. According to
voltages outside the grounding grid are commonly found in common practice, surface material in large scale PV power
installations covering a limited area when high fault currents stations is used only in certain areas to achieve safety. Hence,
are dissipated to the ground. the allowable touch and step voltage limits without surface