You are on page 1of 9

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/322100748

Investigations on Tower Footing Impedance with regards to Frequency


Dependence

Conference Paper · May 2017

CITATIONS READS

0 176

4 authors, including:

François Grange Alexandre SELLIER


SES-EUROPE SES Europe
26 PUBLICATIONS   35 CITATIONS    30 PUBLICATIONS   187 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Towers impedance View project

Lightning View project

All content following this page was uploaded by Alexandre SELLIER on 28 December 2017.

The user has requested enhancement of the downloaded file.


Investigations on Tower Footing Impedance with
regards to Frequency Dependence
F. GRANGE1, I. TANNEMAAT2, A. SELLIER1 and S. FORTIN3

SES-EUROPE, 30 avenue du Général Leclerc, 38 200 Vienne, FRANCE


TENNET TSO B.V., Utrechtseweg 310, 6800 AS Arnhem, NETHERLANDS
Safe Engineering Services and technologies, Laval, CANADA
francois.grange@sestech.fr

Abstract grid, the soil characteristics and the keraunic level. For
When designing and maintaining a high voltage most functions (1a, 1b, and 2a) the impedance at power
overhead line the tower footing impedance is of great frequency of the tower is of importance. Lightning
importance. In most cases a value as seen by the current currents (2b) may however be considered to have high
at power frequency can be taken into account to frequency characteristics, which may lead to a different
characterize the grounding system. In some cases an value for the tower footing impedance to take into
impedance value at higher frequency might lead to account..
different values. Measurements are however often To check if a tower earthing is designed properly and
performed at relatively low frequencies (50 Hz to 5 kHz). complies with the requirements, measurements have to be
This paper explores frequency dependence of tower performed [1]. Various measurement techniques can be
footing impedance. A comparison between measurements applied, all with their advantages and disadvantages [3].
and simulations of tower footing impedance has been Some authors have shown that the low frequency
performed in order to assess the validity of the low methods used by most utilities can be inaccurate and
frequency approach. Ten different tower grounding inappropriate [4]. However, most of the commercial
structures are investigated in the frequency range from measurement equipment may be considered 'low
DC to 5 kHz. For comparison purpose they were chosen frequency' measurement devices, which measure from
based on the footing design, soil characteristics and around power frequency (50 Hz in Western Europe) to a
number of connected shielding wires. frequency that is higher than power frequency, circa
Main results have shown a good convergence 5 kHz. The main advantage of performing measurements
between measurements and simulations for DC results. at higher frequencies is that they can be carried out
High frequency measurement tests reveal major without disconnecting any shielding wire(s) connected to
limitations which require additional investigations. the tower: at such a frequency, the connected shielding
wire(s) will be seen as high impedances, preventing the
Keywords: Tower footing, impedance, measurement, current that is injected into the tower footing to flow to
calculation, earthing, insulation coordination, CDEGS adjacent towers through the shielding wires. Using low
frequency measurements to characterize tower footing
1. Introduction impedances is only valid under certain limited conditions
The goal of a grounding system in a high voltage [5]. To establish a representative value of tower footing
environment is to: impedances for lightning purposes, an impulse
1. guarantee the electrical safety regarding measurement may be performed. However, due to the
a. step- and touch potentials close to the tower lack of reliable dedicated instruments, impulse
b. conductive (through earth) influence on nearby measurements are not regularly performed and have until
objects recently not been performed before neither in the
2. ensure equipment integrity and service continuity Netherlands nor in France. More generally, most of the
regarding: measurement values and methods that can be found in the
a. fault currents technical literature and standards are based on 'low
b. lightning currents. frequency' measurements [6].
One of the important characteristics of a grounding In this paper, we focus on the comparison and
system is its ground impedance, i.e. the total impedance analysis of different measurement and modeling
seen by current injected into the grid and flowing through techniques of tower footing impedances with regards to
the earth to a point located (infinitely) far away. In frequency dependence. The goal of the work is to
lightning protection, measurement of the ground characterize the frequency dependence of the impedance
impedance of tower footings is of major interest [1]. of tower footings, in order to be able to determine the
Each of the above functions can have specific lightning performance of high voltage overhead lines.
requirements regarding the tower footing design, The main objective of this research work is to determine
depending on the local characteristics of the high voltage a method to theoretically evaluate tower footing

1
impedances in situations where the low frequency To inject a current in the tower, a current return probe is
resistance is not valid. needed. Whereas the fall-of-potential of the tower is the
subject of interest, the probe also has a fall-of-potential,
2. Determination of tower footing impedance refer to figure 3. The influence of this on the
A common way to determine the tower footing measurements depends on the size of the probe and the
impedance is by measuring the 'fall-of-potential'. In distance to the tower. It is therefore recommended to
theory the potential difference between the tower and perform the measurements into another direction, so that
earth is measured at varying distance while injecting a only the fall-of-potential of the tower is measured. An
current. The result will be a graph as shown in figure 1. A example is given in figure 4 with 'Profile 1'.
logarithmic shape can be recognized. When plotting the Due to limitations in space and accessibility it is not
values with the distance inverted (1/distance) a straight always possible to perform measurements in another
line can be drawn, see figure 2. direction. In that case it is common to perform a single
1,0 point of measurement at circa 61.8% of the distance of
the current return probe, in the same direction [9].
Impedance (Ω)

0,8

0,6 61,8 %

Impedance (Ω)
0,4

0,2
Profile 1
0,0 Profile 2
0 20 40 60 80
Distance (m) Distance (m)
Fig. 1. Potential difference between soil and tower Fig. 3. Different measurement profiles – example for item B2
1,0
This method is however not very accurate, since the
0,8 measured value may differ a few percent from the actual
Impedance (Ω)

value. To gather conservative results it might be best to


0,6 have the measurement point at >61.8% of the distance,
since the value will then be higher.
0,4

0,2

0,0
0 0,02 0,04 0,06 0,08
1/distance (1/m) Current
Fig. 2. Impedance value and slope; measured values and trend line return
M probe
Two important parameters can be extracted from
figure 2, being: Profile 2
1. The impedance value at zero-crossing, which
represents the actual tower potential (to far earth).
With 1A injection, the voltage is equal to the
Fig. 4. Visualization of measurement directions with respect to the
impedance. current return probe
2. The steepness/slope of the line, representing the
equivalent soil resistivity or soil characteristics as 2.2 Simulations
seen by the current that flows into the ground [8]. Simulations can be performed with specially
Note: The actual result depends on the tower footing designed computer software. The tower footing design is
configuration and the soil characteristics. Especially close represented in a model, and the soil characteristics need
to the tower (up to ca. 15 to 20 meter for a tower with a to be known. They can be acquired by performing
foot of 10 m by 10 m) the measured values may not measurements according to the Wenner-method. They are
follow the logarithmic shape of the curve. It is necessary to develop accurate simulation models to be
recommended to use the values that result in a line that is compared with the measured ground impedance of the
as straight as possible. towers. The impedance of a grounding system can be
obtained by measuring the fall of potential on the
2.1 Measurements surrounding earth during a current injection in the
Where the theory is quite simple and straight structure under study [7].
forward, there is a practical consideration to take into For this research all simulations are carried out with
account when measuring the tower footing impedance. the CDEGS package, which includes several calculation

2
modules based on different methods. Details are through it. It is a critical factor in the design of earthing
introduced later in this paper. Regarding the simulations systems. Soil resistivity measurements are performed to
the user has the option to perform the 'fall-of-potential'- build a model of the different layers of the soil, assumed
method, or simply have the software generate a to be horizontally stratified. Individual measurements
representative value (direct reading). must be carried out for various inter-electrode spacings to
establish the slope of the curve of apparent resistivity.
3. Scope of work Knowledge of the resistivity of the deeper layers is
The scope of the study concerns towers of different important because the spread of current in the ground
design at various locations within the Netherlands. For varies depending on the resistivity.
comparison purpose they were chosen based on the The soil resistivity measurements were carried out
footing design, soil characteristics and number of using the well-known Wenner 4-pin method at each
connected shielding wires. Table I gives an overview. tower site. The measurements have been performed using
a tellurometer CA 6472 by Chauvin Arnoux at a
TABLE I: Overview of the selected objects frequency of 128 Hz, and were analysed using the
Soil # RESAP module of the CDEGS package [11]. Based on a
ID Tower footing design resistivity shielding best fit using the steepest-descent approach with the
(Ω.m) wires Sunde-curves, RESAP can determine the characteristics
A-5 1x block (large) on 25 m poles ~ 15 0 of a multilayer soil that best reproduces specified
A-9 2x blocks (large) on 25 m poles ~ 10 2 apparent resistivity measurement results
A-10 2x blocks (large) on 25 m poles ~ 10 2
A-12 4x 10 m long poles ~ 10 2
A-19 4x blocks (small) on 2 m poles ~ 100 2 3.2 Tower footing impedance measurements
A-26 1x tube (driven); 10 m ~ 30 2 The tower footing impedance measurements are
A-27 2x horizontal blocks (small) ~ 20 2 performed according to the method of Fall-Of-Potential,
A-28 2x horizontal blocks (small) ~ 50 2 using tellurometers SYSCAL Junior from IRIS
B-2 4x 10 m long poles ~ 15 0 Instrument and CA 6472 from Chauvin Arnoux.
B-3 4x blocks (small) on 2 m poles ~ 15 0 For the study, the SYSCAL Junior is used for quasi-
DC measurements and the CA 6472 is used for Super
The general areas where the towers under study are Low Frequency (SLF-128 Hz), Ultra Low Frequency
located are highlighted with blue circles in Figure 5. In (ULF-2539 Hz) and Very Low Frequency (VLF-5078
general it may be assumed that the lighter parts (in the Hz) measurements. Also, selective readings were
East) have a higher soil resistivity. conducted for all towers with the Pylon Box from
Chauvin Arnoux to ensure results without external
influence.
With the C.A 6474, the pylon box allows to assess a
pylon's earth resistance even if it is part of a parallel earth
network, by selective measurement of the pylon in
question. The Chauvin Arnoux’s Pylon Box works with
four current sensors (Ampflex) positioned around the
footings of the pylon.
Since the 128 Hz measurements with and without
selective reading gave similar results they are not
separately mentioned in this paper.
Amsterdam
The Hague 4. Tower footing impedance modeling
The ground impedance calculations and
Arnhem measurement simulations are performed using three
different modules of the CDEGS software package,
namely the MALT, MALZ, and HIFREQ modules [11].
All three modules can compute the potential rise of
energized electrodes buried in layered soils. They use
similar techniques, based on the Moment Method. They
differ mainly by the approximations they make in the
calculations:
 MALT considers that all connected electrodes are
Source: Wikipedia.org equipotential: it ignores possible potential drop along
Fig. 5. Map of the Netherlands, with the locations of the systems under conductors due to their impedance or to induction
study effects.
3.1 Soil resistivity measurements  MALZ accounts for the potential drop due to the
Soil resistivity measurements characterize the impedance of conductors but ignores induction
capability of the soil to resist the flow of electric current effects.

3
 HIFREQ accounts for both the impedance of TABLE II: Measured soil resistance
conductors and for induction effects. It also allows Short Apparent Medium Apparent
modeling above-ground conductors, making it spacings resistance spacings resistance
possible to include adjacent towers including the (m) (Ω) (m) (Ω)
shielding wires in the simulations. 0.1 19.7 3 14.2
The computed values listed in the table for each 0.2 20.7 5 13.7
frequency correspond to the following six different 0.3 20.0 7 14.0
simulation techniques: 0.5 18.5 10 14.7
1. Direct reading with MALT 0.7 19.0 20 12.5
2. Direct reading with MALZ 1 17.8 30 8.0
3. Direct reading with HIFREQ 2 15.6 50 7.7
4. Fall-Of-Potential with MALZ
5. Fall-Of-Potential with HIFREQ (no shielding wires) The measurement results were analysed using the
6. Fall-Of-Potential with HIFREQ (with shielding RESAP module of the CDEGS package. The best fitting
wires) soil representation results in a three layer soil model,
In the Direct Reading type of simulation, only the refer to Table III. In most cases a three-layer soil model
tower footing is included in the simulation model. gave the best fit. In some cases a four-layer model was
Current is injected in the tower footing and the return used.
TABLE III: Soil resistivity
current electrode is not modelled. The impedance is
obtained simply by dividing the potential rise of the Layer Resistivity (Ω.m) Thickness (m)
tower footing by the injected current. 1 20.2 0.6
In the Fall-Of-Potential type of simulation, the actual 2 14.4 14
field measurement setup (including a return current 3 6.3 ∞
electrode and the measurement electrodes) was
reproduced in the model. Two variants of this approach 5.2 Tower footing impedance measurements
were used, one excluding the measurement and current results
injection cables and the other including those cables. This In most of the cases the measurements were
last type of simulation uses the capability of HIFREQ to performed in a different direction than that along which
take into account the inductive couplings due to the the current return probe was placed. The measurement
proximity of the measurement and injection cables, and points were determined from location '0', which is the
should in principle be the most realistic simulation middle of the tower, between the tower legs, and then
method to compare with the measurements. steps of 5 m or 10 m were taken. The values for the DC-
measurement for tower B-2 are given in Table IV.
5. Calculation and measurement results
The remainder of this section presents modeling TABLE IV: Tower footing impedance measurement values
details for structure B-2 as an example. In section 5.4 a Distance Value Distance Value
summary of all results is given. (m) (Ω) (m) (Ω)
0 0.47 30 0.71
5.1 Soil resistivity measurement results 5 0.53 40 0.73
As an example, Figure 6 shows the location of the 10 0.61 50 0.73
apparent soil resistivity measurement traverse for tower 15 0.64 60 0.75
B-2. The measurement profile is located symmetrically 20 0.67 65 0.75
with respect to the tower, and reaches a minimum 25 0.70 70 0.75
distance of 25 m from the tower. This configuration was
selected to minimize the influence of the tower footing on The result is plotted in figure 7 with the inverted
the measurements while recording the properties of the distance, ignoring the values that are close to the tower
soil as near as possible to the tower [10]. footing (0 m to 15 m).
1,0

0,8
Impedance (Ω)

0,6

0,4

0,2

Fig. 6. Apparent soil resistivity measurements location 0,0


0,000 0,020 0,040 0,060 0,080
The following values were measured up to an
electrode distance of 3x 50 meters, refer to Table II. 1/distance (1/m)
Fig. 7. Impedance value and slope

4
From this graph a steepness of 2.14 can be 5.4 Total overview
determined, which gives a soil resistivity of 13.4 Ω.m. The computed and measured values of the ground
The zero crossing on the X-axis results in a value of impedance for Tower B-2 are given in Table VI. The
0.78 Ω for the tower footing resistance. A similar table gives results for the four types of Fall-Of-Potential
approach leads to a result of 0.66 Ω for the measurements measurements mentioned in Section 2.2, namely:
at 128 Hz (both selective and non-selective  Quasi-DC (0.25 Hz)
measurements).  Super Low-Frequency (128 Hz)
 Very Low-Frequency (5078 Hz)
5.3 Tower footing impedance modeling results
The base of the tower is a square with a side length TABLE VI: Comparison of measured and simulated values for tower
B-2
of 7 m. A volume of reinforced concrete is placed at each
corner, supporting the feet of the tower. The volumes of Method DC 128 Hz 5078 Hz
concrete measure 1.8 m long by 1.8 m wide and have a Measurement (sp) 0.75 Ω 0.62 Ω 0,55
height of 1.2 m. There are also connections between those Measurement (fop) 0.78 Ω 0.66 Ω NA
volumes of concrete by beams of reinforced concrete. MALT (dr) 0.75 Ω -------------
The thickness of the concrete on each part of the footing MALT (sp) 0.73 Ω -------------
is 30 mm minimum.
A total of six metallic poles extending out of the MALT (fop) 0.73 Ω -------------
volumes of concrete complete the tower foundation. The MALZ (dr) 0.75 Ω 0.75 Ω 0.77 Ω
poles are 9.6 m long. Four of them are installed on one MALZ (sp) 0.73 Ω 0.73 Ω 0.75 Ω
side of the tower and two on the other side. MALZ (fop) 0.76 Ω 0.76 Ω 0.78 Ω
The foundation structures are embedded in concrete. HIFREQ (dr) 0.75 Ω 0.75 Ω 0.78 Ω
In the past, studies have indicated that concrete-
encapsulated grounding electrodes present a resistance HIFREQ (sp) 0.73 Ω 0.73 Ω 0.74 Ω
lower or equal to the value which could be obtained HIFREQ (fop) 0.78 Ω 0.78 Ω 0.81 Ω
without use of concrete [13]. A graphical representation
of the tower footing model is given in figure 8. This results in the following graphical representation,
where for the simulation results the values for direct
reading are taken.

1,5
MALZ
HIFREQ
MALT
Measurements
Impedance (Ω)

1,0

0,5

0,0
0,25Hz 128Hz 2539Hz 5078Hz
Frequency
Fig. 9. Representation of the tower footing model

The same modeling and measurement techniques


were used for the other towers. The following figures
Fig. 8. Representation of the tower footing model (Figures 10 to 12) show the results for the magnitude of
the tower footing impedance as a function of frequency
As mentioned in chapter 4 the values for the tower for towers A-5, A-10 and A-12.
footing impedance can be determined as a direct reading,
using the single point method or using the fall-of-
potential method. The calculated values are given in the
table below.

TABLE V: Tower B2 calculated results


MALT MALZ HIFREQ
Method
(Ω) (Ω) (Ω)
Direct reading 0.75 0.75 0.75
Single point 0.73 0.73 0.73
Fall-of-potential 0.73 0.76 0.78

5
0,5 FOP with HIFREQ FOP with MALZ
MALZ Direct reading with MALZ Direct reading with HIFREQ
HIFREQ FOP and cables with HIFREQ
0,4 MALT 32%

measurements/simulations
Measurements
Impedance (Ω)

0,3 27%

Relatve deviation
0,2 22% 128 Hz

17%
0,1
12%
0,0
0,25Hz 128Hz 2539Hz 5078Hz 7%

Frequency 2%
Fig. 10. Frequency dependence of the magnitude of A-5 tower footing
-3% A5 A9 A10 A12 A26 A27 A28 B2 B3
impedance Towers
Fig. 13. Relative deviations between measurements and simulations –
0,5 MALZ 128 Hz
HIFREQ
0,4 MALT
Measurements 50% FOP with HIFREQ
5078 Hz
Impedance (Ω)

0,3 45%
Direct reading with HIFREQ

measurements/simulations
40%
0,2 Relatve deviation 35% FOP and cables with HIFREQ
0,1 30%
25%
0,0 20%
0,25Hz 128Hz 2539Hz 5078Hz
15%
Frequency
10%
Fig. 11. Frequency dependence of the magnitude of A-10 tower footing
impedance 5%
0%
0,5 A5 A9 A10 A12 A19 A27 A28 B2 B3
MALZ Towers
HIFREQ
0,4 MALT
Measurements Fig. 14. Relative deviations between measurements and simulations –
Impedance (Ω)

0,3 5078 Hz
At 5 kHz, all simulation cases presented are in rather
0,2 poor agreement with the measurements.

0,1 6. Discussion
For better understanding we remind that the FOP
0,0
0,25Hz 128Hz 2539Hz 5078Hz
simulations with and without cables are done to be more
representative of the measurements setup. This is not
Frequency
necessarily closer to exact values but it introduces the
Fig. 12. Frequency dependence of the magnitude of A-12 tower footing
impedance same errors as those of the measurements as it takes into
account the real situation of finite distance remote earth.
HIFREQ and MALZ FOP simulations are in very It allows modelling the current return electrode at its
good agreement with the measurement results carried out actual location during the testing. Thus, FOP simulations
in DC. Regarding the 128 Hz results, the agreement with and without cables globally give better agreement
between the HIFREQ and MALZ FOP simulations and with measurements as expected. Actually, simulations
the measurements is again good for the A-5 and A-12 without FOP consider an infinitely remote earth.
towers whereas tower B-2 shows significant differences Concerning the frequency influence, capacitive
between the measurements and the simulations. coupling to earth might appear. At very low test
Figure 7 shows the relative deviation between the frequencies, capacitive coupling between the potential
measurements and simulations at 128 Hz for all towers measurement lead and the earth can result in distorted
and Figure 8 shows the same information at 5078 Hz. values, particularly if the contact resistance between the
potential probe and the earth is high. The greater the
length of potential measurement lead that is strung out,
the greater the coupling. To the degree that there is
coupling and poor potential probe contact with the earth,
the measured voltage tends to be representative of an
altered probe position, at a distance from the grounding

6
grid that is determined by a weighted average of the earth unacceptable. It is worth noting that this effect is very
potentials along the length of the lead. When the length of pronounced only for cases where the soil resistivity is
lead strung out is great, the measured value tends to low and thus resistance do not exceed 0.1 Ω. Thus, one
approach the actual grid impedance, particularly at higher can determine if the expected measured ground
frequencies. At the same time, the inductive coupling impedance is on the order of such value by using the
between the current injection lead and a parallel potential simplification presented in the measurements section.
lead located a few meters away cannot be ignored in very Consequently, for 5 kHz frequency simulations, only
low soil resistivity locations such as the present study. As the HIFREQ results are reliable. At the same time, the
proof, we observe large differences between the MALZ low frequency agreement gives a real validity to
and HIFREQ results at 5 kHz due to the fact that MALZ simulations. Nevertheless, on can note from comparisons
neglects inductive coupling. between measurements and simulations that relative
To explain simulations results divergences, a short deviations are quite large and above 10 % for 7 towers
description of the respective methodologies of the out of 9. Thus, 5 kHz measurements can be suspected to
HIFREQ and MALZ programs, based on Maxwell’s be misleading. As a rigorous process have been followed
equations in the frequency domain, is given in the sequel. according to Chauvin Arnoux method, we can consider
On the one hand, the HIFREQ software module that equipment performances are limited.
computes the electromagnetic fields due to energized
conductors in a multilayer medium, using a full wave 7. Conclusion
solution (i.e. without any approximation) for the Hertz A campaign of measurements was performed to
vector potential 𝛱⃗ caused by an electric dipole located in obtain soil resistivity and tower footing resistance of ten
the medium. Indeed, in the frequency domain, that is for a towers. Tower footing resistances were measured by the
single-frequency excitation, the electric field 𝐸⃗ , the Fall-Of-Potential testing procedure on a distance of
magnetic field 𝐻 ⃗ , and the scalar potential 𝜓 can be 110 m for each pylon. Measurements in the range from
conveniently expressed in terms of the Hertz vector Quasi-DC to 5 kHz have been performed. The analysis of
⃗ as 𝐸⃗ = 𝛾 2 𝛱⃗ − ∇𝜓 , 𝐻⃗ =𝜃∇×𝛱 ⃗ , 𝜓 = −∇ ⋅ measurements shows an important diversity of soils and
potential 𝛱
tower footing resistances. Models were developed for
⃗𝛱 , where 𝛾 is the propagation constant, and 𝜃 the
each tower using soil resistivity models obtained using
complex conductivity [14]. The Hertz vector potential is the RESAP software module and using the data on
found to satisfy the wave equation given by: foundations of pylon given by TenneT. Simulations using
1 the HIFREQ, MALT and MALZ software modules do
⃗ = 𝛾 2𝛱
∇2 𝛱 ⃗ − 𝐽
𝜃 not give the same results due to the use of different
where 𝐽 is the current density associated with the computation methods. HIFREQ gives the more accurate
energized conductor. By solving this equation, one can results as it takes propagation phenomena into account.
find that the general expressions for the components of 𝛱 ⃗ There is a very good agreement between
caused by current flowing along a conductor are measurements and simulations up to Super Low
determined by path integrals along the conductor, and are Frequencies. At 5 kHz, measurement results cannot be
expressed in terms of: fully trusted as no validation can be provided by the
𝑒 −𝛾𝑅 equipment manufacturers in spite of the use of their
𝑀= method. As simulations have been validated here, further
𝑅
where 𝑅 is the distance between the observation point and work is needed to identify the origin of the deviation in
the source. the measurements.
On the other hand, in the MALZ software module, As perspectives, high frequency and impulse
the computations of the electromagnetic fields are response of tower grounding systems requires additional
performed using a hybrid approach derived from a studies to characterize its behavior. An impulse generator
combination of the field theory approach and the circuit is under development to characterize tower footing
theory approach. This hybrid approach has been built in impedance response to lightning impacts. Further work
order to avoid the complicated analytical expressions and will emphasize on transient behavior of towers struck by
the serious computational difficulties arising from the lightning.
field theory approach [15]. Indeed, the use of the circuit
theory approach leads to a number of simplifications,
such as not taking into account the inductive coupling References
between conductors at very high frequencies, which
permits easy and accurate solutions of a large number of [1] V. Cooray, Lightning Protection Book. Lucknow, India: Inst. Eng.
problems. However, the effects of these simplifications Technol., 2010.
[2] IEEE Guide for measuring earth resistivity, earth impedance and
on the accuracy of the results can be variable depending earth surface potentials of a ground system, Part I - Normal
on several parameters, such as frequency, characteristics Measurements, IEEE Standard 81, 1983
of the medium, etc. For example, there may be a [3] N. Harid, D. Lathi, H. Griffiths and A. Haddad, “Characterization
frequency interval between very low and very high of Ground Electrodes Under Low Voltage Variable Frequency and
Impulse Energization,” in Proc. Asia-Pacific International
frequency cases where the simplification introduced by Conference on Lightning (APL), Nagoya, Japan, 2015,
neglecting the inductive mutual coupling becomes

7
[4] E. Petrache, W. A. Chisholm, and A. Phillips, “Evaluating the
transient impedance of transmission line towers,” in Proc. 9th Int.
Symp. Lightning Protection, Foz do Iguaçu, Brazil, Nov. 2007, pp.
1–5.
[5] S. Visacro, “A comprehensive approach to the grounding response
to lightning current,” IEEE Trans. Power Delivery, vol. 22, no. 1,
pp. 381–386, Jan. 2007.
[6] Earthing of power installations exceeding 1 kV a.c. CEI EN
50522,
07 2011.
[7] E. D. Sunde, Earth conduction effects in transmission systems,
Dover Publications, New York, 1968 (Book).
[8] EPRI, “Guide for Transmission Line Grounding: A Roadmap for
Design, Testing, and Remediation: Part I - Theory Book”
[9] G. F. Tagg, Earth resistances. Georges Newnes Limited, London,
1964 (Book).
[10] J. Ma and F.P. Dawalibi, “Study of Influence of Buried
Metallic Structures on Soil Resistivity Measurements IEEE
Journal Paper.
[11] CDEGS Software Package, Safe Engineering Services &
technologies ltd., Montreal, Quebec, Canada, Version 15, 2015.
[12] Principes de conception et de réalisation des mises à la terre, EDF,
Direction des Etudes et Recherches, NI (January 1984) H115
[13] Paul Wiener, « A Comparison of Concrete-Encased Grounding
Electrodes to Driven Ground Rods,” IEEE Transactions, Vol IGA-
6, No 3, May/June, 1970.
[14] F. D. Dawalibi and A. Selby, “Electromagnetic fields of energized
conductors,” IEEE Transactions on Power Delivery, Vol. 8, No.3,
July 1993, pp 1275-1284
[15] F. D. Dawalibi and R. D. Southey, “Analysis of Electrical
Interference from Power Lines to Gas Pipelines Part I:
Computation Methods,” IEEE Transactions on Power Delivery,
Vol. 4, No.3, July 1989, pp 1840-1846
[16] J. Ma, F.P. Dawalibi, "Influence of inductive coupling between
leads on resistivity measurements in multilayer soils", Power
Delivery IEEE Transactions on, vol. 13, pp. 999-1004, 1998,
ISSN 0885-8977.

View publication stats

You might also like