Professional Documents
Culture Documents
REVISION HISTORY
DATE
REV. DESCRIPTION APPROVED
(YYYY-MM-DD)
G General update. Added processor FM-IM-2UPLi63X 2017-11 Christophe VASINIS
SUMMARY
1 SCOPE: ................................................................................................................................................................... 3
2 ADJUSTMENT: .................................................................................................................................................... 3
1 SCOPE:
This specification applies to the adjustment at site of the TURCK flow sensors located in the air inlet
ducts of Gas Turbine and Gas Module acoustic enclosures.
It is applicable for the flow sensors 95BT of the gas turbine enclosure and for the flow sensors 95VL of
the gas fuel module enclosure.
2 ADJUSTMENT:
2.1 Applicable flow sensors
This specification is applicable to the following set of flow sensor, connector, and signal processors:
- Signal processor: MK96-LI01 (shown on left side) or FM-IM-2UPLi63X (shown on right side)
2.2 PRE-REQUISITES:
- The installation of the acoustic enclosure and ventilation system shall be completed. The enclosures shall
be sealed.
- The commissioning of the ventilation system shall be completed. The ventilation fans and dampers shall
work correctly.
- The flow sensors shall be mounted in line with the flow direction in the air duct as per installation
drawing and TURCK manual. The flow sensors shall have the correct type as indicated in § 2.1.
- Gas turbine shall be shut down and cooled after a minimum time of 2 hours.
- A suitable anemometer with operation manual shall be available to control the air velocity in the air inlet
duct.
- Air temperature during calibration shall not be less than the minimum operating temperature allowed by
the operation manual of the anemometer.
- For outdoor installation, the calibration shall not be done during windy conditions.
- If necessary temporary scaffolding for the installation and commissioning to facilitate the access to the
flow sensors.
- The P&ID (MLI 0436) and the installation drawing shall be available.
It is possible to remove each flow sensor and to measure the velocity of the air flow at the location of each
of the 3 sensors as stated before; in that case the measured velocities will be v1, v2, v3 and the average value
V will be V = (v1 + v2 + v3) / 3. One flow sensor shall be located close to the center of the duct, another
flow sensor shall be located in the half section of the duct and the last flow sensor shall be located in the
other half section of the duct. This last method provides a better estimation of the air flow in the section of
the duct.
The velocity V of the air flow shall meet the following criteria:
For frame 9E.03 9E.04 with 2 additional air inlets in accessory compartment:
Frame 9E.03
Enclosure Gas Module Enclosure Accessory Module Enclosure (**)
Measured velocity in m/s V V1, V2
Free section of inlet duct in m2 S S1, S2
Rated flow of fan 2 m3/s (88VL) 15 m3/s (88BT)
Maximum measured leak flow 30% 30%
3
Criteria V x S >1.40 m /s (V1xS1+V2xS2) >10.5 m3/s
The motorized damper of the accessory compartment at the up-stream end shall be fully closed.
See the process flow diagrams in annex 10.
(**) Not applicable for new design with pressure transmitters 96AT instead of flow sensors 96BT.
When the velocity V measured as required before does not meet the criteria, then the tightness of the
enclosure shall be improved until the criteria is met.
b) Calibration of XM signal:
When the air inlet of the accessory compartment (applicable for frames 6B.03 and 9E.03) in the up-stream
end is fitted with a motorized damper, this damper shall be fully opened as shown in annexes 7 and 11. The
access doors or hatches shall be fully closed.
Turn on one ventilation fan and when the flow in the air duct is stabilized at the rated flow in cold conditions
(the test shall be done with the fan providing the lower flow):
- Wait 60 seconds minimum.
- For signal processor MK96-LI01: Turn the potentiometer 1 (High flow) until the desired output current XM
is obtained as indicated in paragraph 2.4.2. Turning the potentiometer shall influence the 18.5 mA signal.
LED yellow and several LED green are lit depending on the output current level.
- For signal processor FM-IM-2UPLi63X: Refer to the instruction of the vendor manual for more
information. Hereafter an extract of the vendor manual is reported.
c) Calibration of X0 signal:
Turn on one ventilation fan and when the flow in the air duct is stabilized at the rated flow in cold
conditions:
- Remove the flow sensor located close to the center of the duct.
- Introduce the anemometer in line with the flow direction in the center of the air inlet duct.
- Follow the instruction of the operation manual of the anemometer.
- Seal the gap between the anemometer and the orifice in the inlet duct wall to avoid a leak flow.
- Open partly an access door of the gas module compartment and an access door of the accessory
compartment for frame 6B.03 and 9E.03. Open partly an access door of the gas module compartment and an
access door of the gas turbine compartment for frame 6F.01 and 6F.03. The door shall be opened partly to
obtain a minimum operating velocity (between 0.5 and 1 m/s) and kept opened.
- Re-install the hatch with the flow sensor.
- Wait 60 seconds minimum.
- For signal processor MK96-LI01: Turn the potentiometer 2 (Low flow) until the desired output current X0
is obtained as indicated in paragraph 2.4.1. Turning the potentiometer shall have influence the 4 mA signal.
- For signal processor FM-IM-2UPLi63X: Refer to the instruction of the vendor manual for more
information. Hereafter an extract of the vendor manual is reported.
It is recommended to repeat the operations b) and c); the last and final calibration will be made with the fan
providing the lower flow.
In this state, the signal processor is adjusted to the flow range and provides a correct current signal to the
Gas Turbine control panel.
Annex 6: Frame 6B.03 Process Flow Diagram with 2 additional inlets in accessory compartment
Annex 7: Frame 6B.03 Process Flow Diagram with additional inlets in accessory compartment
Annex 10: Frame 9E.03 Process Flow Diagram with additional inlets in accessory compartment
Annex 11: Frame 9E.03 Process Flow Diagram with additional inlets in accessory compartment