26 Electronic Protection System Cutler-Hammer

January 1999

sary and costly downtime. breaker is in use. Magnum Rating Plugs and Matching
Current Sensors
Rating Plugs Current Sensor
All Magnum circuit breaker trip Toroidally wound current sensors Breaker Frame Ratings
units use a fixed type rating plug. are installed at the rear of the cir- (Amperes) (Amperes)
Rating plugs are available in cuit breaker on the lower horizontal 200, 250, 300, 400,
ampere ratings of 200 through 6300 terminals. They are available in 800
600, 630, 800
amperes. The current rating of the ampere ratings of 200 through 6300
200, 250, 300, 400, 600,
rating plug must match the current amperes, and must match the cur- 1250
630, 800, 1000, 1200, 1250
rating of the integrally mounted rent rating of the installed rating
200, 250, 300, 400, 600, 630,
current sensors. Therefore, the plug. 1600
800, 1000, 1200, 1250, 1600
continuous current rating of the cir-
cuit breaker cannot be changed by The sensors produce an output cur- 200, 250, 300, 400, 600, 630,
rent proportional to the load cur- 2000 800, 1000, 1200, 1250, 1600,
only changing the rating plug. 2000
rent. Under preselected conditions
The rating plug performs a number of current magnitude and time, the 200, 250, 300, 400, 600, 630,
2500 800, 1000, 1200, 1250, 1600,
of functions: sensors furnish the trip unit with a 2000, 2500
signal and the energy required to
■ It tells the trip unit what the rat- open (trip) the circuit breaker. 200, 250, 300, 400, 600, 630,
ing is of the current sensors. A 3200 800, 1000, 1200, 1250, 1600,
label on the rating plug clearly The current rating of the installed 2000, 2500, 3000, 3150, 3200
states that the rating plug and sensors can be easily viewed from 4000 2000, 2500, 3200, 4000
current sensors must have the the rear of the circuit breaker
5000 2000, 2500, 3200, 4000, 5000
same rating. through small viewing windows.
The viewing windows are part of 6300 2000, 2500, 3200, 4000, 5000,
■ It determines the maximum instan- 6300
taneous setting which is a function the sensor cover plate which is
of the current sensor rating. removed to change the sensors.

Neutral current sensors are avail- Neutral Sensor (Unmounted)


If the rating plug is removed from able for customer installation.
the trip unit, the circuit breaker will The additional sensor is not sup-
open (trip) is it is carrying current. plied with the circuit breaker and
The rating plug should always be must be ordered separately. They
secured in position when the circuit are wired to the trip unit through
the secondary contacts on the

Current Sensor Cover in Place Over Sensors Current Sensor Cover in Place Over Sensors

Current
Current
Sensor
Sensor

Sensor
Rating
Sensor
Rating
Toroidal
Wiring Current
Plug Sensor