APPLICATIONS
(FOR DC TRACTION POWER SUBSTATIONS)
Interconnecting circuit breaker
I>
RC
MAIN BENEFITS
 Safe with a high insulation level.
MAIN BENEFITS
 Very low maintenance requirements with high electrical and mechanical endurances.
 Simple design with few moving parts resulting in high reliability.
 High rated short circuit making and breaking capacity.
 A large number of different options to match the various application requirements.
 Proven design with worldwide experience and acceptance.
PRODUCT RANGE
U [V=]
3,600
Arc
Arc chute 64
chute 64 UR26-64 UR40-64
1,800
Arc chute
Arc chute 82
82 UR26-82 UR40-82 UR46-82 UR60-82 UR80-82
900
Arc chute
Arc chute 81
81 UR26-81 UR40-81 UR46-81 UR60-81 UR80-81
I [A]
0 2,600 4,000 4,600 6,000 8,000
Note: points f, e and d represent fault conditions along the line at different
distances from the rectifier.
0.63 Iss
Icut off
di/d
0.63 Iss
Icut off = Cut-off current
t
di/t d
Icut off
Icut off
tc = Time-constant of the circuit
t
Id
Id
Id t ti = Opening time
V t
V t Uarc = Maximum arc voltage
Uarc V
Uarc UNe = Rated operational voltage
UNe Uarc
UNe
UNe ti
ti t
t
ti t
t l 20
///
[ms]
OPENING
18
TIME TI
t l 20
16
[ms]
18
14 Relationship between opening time tl and the initial rate of
16
12 rise of current di/dt for direct instantaneous over-current
UR36/40/46
10
14 release.
128
UR26
UR36/40/46
Example for a di/dt of 3x106 A/s:
106
- for UR26: ti ~ 4.3 ms,
4
8
2
6
UR26 - for UR60/80: ti ~ 4.1 ms.
0
4
3.105 5 7 106 3 5 7 107 3
2 di/dt [A/s]
Note: for a shorter opening time on low di/dt, the “indirect release” (shunt
0
3.105 5 7 106 3 5 7 107 3 trip) option can be used (refer to “Options” section page 12).
di/dt [A/s]
t l 10
[ms]
8
t l 106
[ms]
4
8
UR60/80
2
6
0
4
3.105 5 7 106 3 5 7 10 7
UR60/80 3
2 di/dt [A/s]
0
3.105 5 7 106 3 5 7 107 3
di/dt [A/s]
4 HIGH-SPEED DC CIRCUIT-BREAKERS FOR FIXED INSTALLATIONS, EN/IEC STANDARD, TYPE UR
DATA FOR PRODUCT SELECTION
Symbol Unit UR26 UR40 UR46 UR60 UR80
MAIN HIGH VOLTAGE CIRCUIT
Rated voltage
- arc chute type 81 UNe [VDC] 900 900 900 900 900
- arc chute type 82 1,800 1,800 1,800 1,800 1,800
- arc chute type 64 3,600 3,600 - - -
Rated insulation voltage
- arc chute type 81 UNm [VDC] 3,000 3,000 3,000 3,000 3,000
- arc chute type 82 3,000 3,000 3,000 3,000 3,000
- arc chute type 64 4,800 4,800 - - -
Conventional free air thermal current (1) Ith [A] 2,600 4,000 4,600 6,000 8,000
Rated short-circuit making & breaking capacity
- arc chute type 81 at UNe 900 VDC INss/TNc [kA]/[ms] 125/100 125/100 125/100 125/100 125/100
- arc chute type 82 at UNe 1,800 VDC 80/31.5 80/31.5 80/31.5 80/31.5 * 80/31.5
- arc chute type 64 at UNe 3,600 VDC 40/31.5 50/31.5 - - -
Peak & rated short-time withstand current (250 ms)(2) ÎNcw/INcw [kA]/[kA] - - - 75/53 75/53
Direct over-current instantaneous release
- (bi-directional) (3) [kA] 1.4-8.0 2-15 2-15 6-18 6-24
- (uni-directional) [kA] - - - 6 6
Power-frequency withstand voltage (50 Hz/1min) (4)
- arc chute type 81 Ua [kV] 12/15 (5) 12/15 (5) 12/15 (5) 15 15
- arc chute type 82 12 12 12 15 15
- arc chute type 64 15 15 (6) - - -
Rated impulse withstand voltage
- arc chute type 81 UNi [kVDC] 20 20 20 15 15
- arc chute type 82 20 20 20 20 20
- arc chute type 64 30 30 (6) - - -
Maximum arc voltage
- arc chute type 81 Uarc [V] ≤ 2,500 ≤ 2,500 ≤ 2,500 ≤ 2,500 ≤ 2,500
- arc chute type 82 ≤ 4,000 ≤ 4,000 ≤ 4,000 ≤ 4,000 ≤ 4,000
- arc chute type 64 ≤ 8,000 ≤ 8,000 - - -
(1)
At Tamb = +40°C and tested with high voltage connections according to standards EN50123 and IEC61992. • (2) For uni-directional version. For other configurations with higher value, please
contact Sécheron. • (3) For range selection, refer to the table page 6. • (4) Values applicable for factory tests on serial products. • (5) Based on the selected configuration. • (6) For higher values,
please contact Sécheron. • (*) Also tested at 100 kA (142 kApk).
B
Setting of maximum current release Setting of maximum current release
Optional DE type tripping device Specific configurations for rectifier circuit breakers
40 25 50 25
25
30
50
20 50
INFORMATION FOR PRODUCT INTEGRATION
4x Ø14
25
4x Ø18
51
69 frame is 0.5 mm.
51
R4
90
5
UR26-81/82
783
177 50
30
50.5784
238
120
D 95 100 60
25
120
HV R4
386
90
23
4x Ø11 8x Ø18
23
E
39 4x Ø11 39 LV 320 182
75.5
160 40
A
(1)
Arc chute 82
160160 40 40 160 240 C (2)
Arc chute 81
56 56 240 240 379 411 194 320 B
UR26-81/82 UR40/46-81/8
A
238
40 25 50 25
23
25
30
25
UR26-64S UR40-64S UR26/40-64S HV connections for
50 2525 50
20 50
4x Ø14 40 25 50 25
25
30
50 25 UR60 UR80 UR60/80
23 25 50
20 50
350 617
30
238 238
1025
419
140,5 4x Ø14 4x Ø18
69 4x Ø11
20 50
51
160 40 160
D 95 100
4x Ø18 90 90 HV56upper
240 connection 379
for UR46 only
371
HV UR60
783
40 25 50 25 350
23
177 50 238
30
23
4x Ø11
LV
25
30
50.5
120
60
50
160 40 160 C
20 50
25
56 240 379 194 320 B
25
120
A
4x Ø14 4x Ø18
23
4x Ø11 8x Ø18
39 39 320 182 17
75.5
160 40
160 40 240 A
Dimensions
56 240 [mm]
411 UR26 UR40 UR46 UR60 UR80
645 760 760 350
131 246 246 238 238
20 30 40
25
UR40-64S
176 176 177 39
UR26-64S UR26/40-64S
420 700 160 40
25
320 56 240
50
177
25
4x Ø14
HIGH-SPEED DC CIRCUIT-BREAKERS FOR FIXED INSTALLATIONS, EN/IEC STANDARD, TYPE UR 7
25
A
40 25 50 25
25
30
50
20 50
25
4x Ø14 4x Ø18
51
Standard closing device (3) :
Electric holding 717
Magnetic holding 760
Specific closing device : (4)
783
177 50 Electric holding 748
30
Magnetic holding 748
50.5
120
60
25 (1)
Arc chute 82
HV
120
(2)
Arc chute 81
23
4x Ø11 8x Ø18
(3)
ll breaker configurations excepted
A
LV
optional configuration of uni-
39 39 320 182 directional breaker.
75.5
160 40
A
(4)
Optional configuration of uni-
160 40 240
directional breaker
56 240 411
25 WEIGHTS
UR26-64S UR40-64S UR26/40-64S
420 700
25
1025
140,5
20 50
INSULATION DISTANCES
D 95 100
4x Ø18 90 90
FOR UR26/40/46/60/80
371
23
23
S-CC
it includes an arc chute lifting
lever located on connector side.
S-OC
it includes an arc chute lifting
S-CC S-OC lever located on the connector
opposite side.
SE
it includes two arc chute
locking levers. SI-CC
it includes an arc chute
Arc chute locking levers lifting lever located on
Arc chute lifting lever connector side and, for
Additional insulation installation of circuit breaker
SI-CC SI-OC without insulation walls, an
additional insulation around the
DESIGNATION CODE FOR ORDER FORM (ARC CHUTE 64 INSTALLATION) arc chute.
Arc Codification
chute Circuit breaker Arc chute installation SI-OC
type standard option it includes an arc chute lifting
SE 2 lever located on the connector
SI-CC 3 opposite side and, for
64 UR26/40 SI-OC 4 installation of circuit breaker
without insulation walls, an
S-CC 5
additional insulation around
S-OC 6 the arc chute.
• The circuit breaker remains closed • The circuit breaker remains closed
with a reduced ‘’holding’’ current. without any control current.
To open the circuit breaker the To open the circuit breaker it is UR26/40/46
holding current is cut-off. necessary to reverse the polarity V=
S
• With E-type closing device, the of the current flowing through the +
E1 F1
circuit breaker cannot remain closing coil. Rp
Rs
closed if the low voltage supply • With the M-type closing device,
is lost. the circuit breaker remains closed
when the low voltage supply is lost. F2 E2
It UR26/36/40/46
requires the control voltage to
UR26/36/40/46
UR26/36/40/46
–
110 11.7 6.3 7.0 19.9 210 0.5 0.4 0.6 40 20 1.6 1.0 2.3
125 10.5 5.6 6.3 17.8 272 0.4 0.3 0.6 52 26 1.4 0.9 2.0
220
Maintien magnétique pour5.9 3.2
UR60/80 3.5 9.9 840 0.3 0.2 0.3 160 80 0.8 0.5 1.1
A
(maintien électrique idem que UR26-36-40-46)
Notes: The breaker can also be controlled
B
with a rectified AC control voltage.
C
10 HIGH-SPEED DC CIRCUIT-BREAKERS FOR FIXED INSTALLATIONS, EN/IEC STANDARD, TYPE UR
D
22 22 22 22
20 1820 18
16 1416 14
12 1012 10
8 6 8 64 2 4 2 18 18
16 1416 14
12 1012 10
8 6 8 64 2 4 2
Schéma SG100312P1
Schéma SG100312P1 Type : 4O-4S
Type - Config
: 4O-4S C C
- Config Schéma SG100312P1
Schéma SG100312P1 Type : 4O-4S
Type - Config
: 4O-4S D D
- Config
22 22 22 22
/// T
YPICAL VALUE FOR CLOSING COILS UR60/80
18 18 16 1416 14
12 1012 10
8 6 8 64 2 4 2 18 18 16 1416 14
12 1012 10
8 6 8 64 2 4 2
Schéma SG10317P1
Schéma Type
SG10317P1 :Coil
Type characteristics
4O-3S - Indirect
: 4O-3S + config
- Indirect C C
+ config Schéma SG10317P1
Schéma SG10317P1 Type : 4O-3S
Type : 4O-3S - Coil
- Indirect characteristics
+ config
Indirect D D
+ config
19 19 19 19
(WI)(WI) 20 20
I I (I>) (I>) 20 20
I I
18 1718 17 Closing
13 13pulse
11 911 97 5 7 53 1 3 1 18 1718 17 13 13
11 911 97 5 7 53 1 3 1 Closing pulse opening pulse M-type
21 21
holding E-type 21 21
0.5 to 1s 0.5 to 1s 0.5 to 1s
Un22 22
Inom I14min12E10 Imax 4 R1
2
nom Inom
(2)
Imin16(2) Imax22 (2)22 Un Inom Imin M Imax Rsnom Inom Imin Imax
16 16 14 8 68 6
12 10 4 2 16 14 14
12 1012 10
8 6 8 64 2 4 2
[VDC] [A]
I> I> [A] [A] [Ω] [A] [A] [A] I> I> [VDC] [A] [A] [A] [Ω] [A] [A] [A]
48 63.9 40.8 85 12 3.8 3.1 4.2 48 47.1 30.1 62.8 2.7 12.6 10.3 14.2
60 53.6 34.2 71.2 18 3.2 2.5 3.4 110 21.3 13.5 28.3 15 5.4 4.1 6.3
110 25.0 16.6 33.2 56 1.8 1.5 2.0 125 18.4 11.7 24.5 18 5.0 3.8 5.8
125 22.5 14.9 29.9 75 1.6 1.3 1.7 220 11.6 7.4 15.5 56 2.9 2.2 3.3
(1)
Rectified 230VAC Note: The breaker can also be controlled
(2)
With selected economy resistor with a rectified AC control voltage
The following wiring schemes represent the low voltage connector pins
assignement in function of the selected connectors and the configuration
Only the pins related to your
selected configuration page
chosen for standard or optional functions. They are valid for all control voltages 16 will be wired according to
except 24 VDC. For 24 VDC control scheme, please contact Sécheron. the below’s pin assignment.
The connector will be delivered
Brochure
Brochure
Standard: xxxxx
Standard: xxxxx Standard: xxxx
Standard: xxxx with all 32 pins even if not all
wired.
HARTING
ANSI
ANSI
23 23 23 23
I I I I
HARTING HARTI
24 24 24 24
21 21
19 1719 17
15 1315 13
11 911 97 5 7 53 1 3 1
21 21
15 1415 14
12 1112 119 8 9 86 5 6 53 2 3 2 Legend of the schemes:
HART
HARTIN
HAR
a b a b (WI) I> I (I>) (WI) Circuit breaker
main contact
HARTIN
22 22 22 22
HARTI
20 1820 18
16 1416 14
12 1012 10
8 6 8 64 2 4 2 13 13 10 10 7 7 4 4 1 1
HART
Low voltage connector
Brochure Brochure
b b
a b a b (WI) I> I (I>) (WI)
I> I> a aI
> I> interface (male pin)
HARTI
BrochureHARTIN
Brochure Brochure
b b
a b a
1a+1b
b I>
(WI) - Switch PF I (I>) (WI)
a a
Harting type HAN 32 EE ®
BrochureHARTING H
Type
Type: :PF
PF Type
Type: :CO
CO
Brochure
b
a b a
b
b (WI) I> - SwitchI CO(I>)
1a+1b (WI)
(Standard) a a
Brochure
H
Brochure
HARTIN HA
Standard: xxxxx
Standard: xxxxx Standard: xxxx
Standard: xxxx
HA
a b a b b (WI) I>b I Indirect
(I>) (WI) overcurrent release
23 23 23 23
(I>) (I>) (WI)(WI) I I (I>) (I>) (WI)(WI) I I a a
EN
EN
24 24 24 24
HARTING
Brochure Brochure
HAR
31 2931 2927 2527 25
21 21
19 1719 17
15 1315 13
11 911 97 5 7 53 1 3 1 31 2931 2927 2527 25
21 21
12 1112 119 b8 9 86 5 6 53 b 2 3 2
15 1415 14 Circuit
a b abreaker
b (WI) closing
I> coil I (I>) (WI)
a a
H
Wear
I> b indicator switch
Brochure Brochure HA
Brochure Brochure
a b a b (WI) I b (I>) (WI)
22 22 22 22
(option)
32 3032 3028 2628 26 20 1820 18
16 1416 14
12 1012 10
8 6 8 64 2 4 2 32 3032 3028 2628 26 13 13 10 10 7 7 4 4 1 1 a a
HAR H
Overcurrent release
b b
I> I> I> I> a b a b (WI) I> I (I>) (WI)
a a detector switch (option)
Brochure Brochure
HAR
b b
a a Notes:
- Low voltage connectors are delivered
Légende
Légende with all pins mounted, even if not all
wired.
- Indirect release coils BIM6 & BIM8 are
connected to a low voltage connector
while BIM5 & BIM7 are connected to a
terminal block (refer to page 14).
a a b ab
HIGH-SPEED
a bb (WI)(WI) I> I>DC CIRCUIT-BREAKERS
I I (I>) (I>) (WI)(WI)
FOR FIXED INSTALLATIONS, EN/IEC STANDARD, TYPE UR 11
OPTIONS (SUBJECT TO ADDITIONAL COSTS)
MOBILE CONNECTOR - UR26/40/46/60/80
Mobile connector (without cable)
Auxiliary switches Fixed Number of pin
Control
connector (delivered with connector) Cable Sécheron’s
voltage Connector
type Size Size gland number
Device Number Type
2.5 mm² 1.5 mm²
UR26/40/46
(without ECO-Drive) Harting
with options 5a+5b PF 24 VDC 4 28 M32 SG104063R10800
HAN® 32 EE
( or ) and
UR26/40/46
(with ECO-Drive) Harting
with options 5a+5b PF 24 VDC 0 32 M32 SG104063R10900
HAN® 32 EE
( or ) and
UR26/40/46
(with or without 48, 64, 110,
Harting
ECO-Drive) 5a+5b PF 125, 200, 2 30 M32 SG104063R10100
with options HAN® 32 EE
220 VDC
( or ) and
the number of pins indicated in the above table does not include options such as wear indicator Note: crimping tools are not in the scope
switch, indirect overcurrent release, overcurrent release detector switch. of Sécheron
MAIN BENEFITS
MAIN BENEFITS
No need of additional hardware to control the breaker.
Compact integration.
Reduction of overall installation costs.
Reduction of operational costs with lower power consumption.
Reduction of the risks to damage the closing coil.
Full compliance with EN50121-3-2 standards for EMC
Full compliance with EN50155 § 5.1.1.2 class S2
(short interruption of voltage supply).
Full compliance with EN50155 § 5.1.3 class C1 (supply change over).
Note:
- Available for UR26/40/46
- Available for closing device
with E-type holding
19 17 15 13 11 9 7 5 3 1
28
k0 Harting connector
26 Vbat P
+
Un
25 Vbat N 4 Sécheron’s scope
- C
27
k1 D Customer’s scope
22 ORDP 3
+
UEF
- 21 ORDN
20 18 16 14 12 10 8 6 4 2
/// T
ECHNICAL DATA
(1)
ot included in the DC circuit breaker -
N
To be ordered separately
The terminal block allows the connection between The terminal block allows the connection between
2.5 mm² cables from the BIM5 and 2.5 mm² cables from 2.5 mm² cables from the BIM7 and 2.5 mm² cables from
the battery and 6 mm² cables from the CID-3. BIM6 is the battery and 6 mm² cables from the CID-3. BIM8 is
directly connected to the low voltage connector. directly connected to the low voltage connector.
MANUAL RELEASE
Manual releases are safety devices designed to withdrawing from the panel the trolley on which the
guarantee that the breaker is in OPEN position so as breaker is installed. The horizontal release must be
to access the breaker’s panel -e.g. for maintenance. manually actuated from the front side of the panel
The vertical release is automatically actuated while door before opening it.
Contact wear
indicator
with 22 characters when placing your order. UR26/40/46 with Harting HAN® 32
• The customer shall write down the setting of maximum current release connector and 24, 48, 60, 110VDC
control voltage.
value (Id) in its order form. (2)
UR60/80: only for electric holding
• For technical reasons some variants and options indicated in the designation (3)
Rectified 230VAC
code might not be combined. (4)
In case control type “Electric hold-
• The bold part of this designation code defines the device type, and ing with ECO-Drive is selected
(line 15), select “No” for Varistor on
the complete designation defines the identification number of the
Coil (line 17)
product, as displayed on the identification plate attached to the product.
Signature:
14 Arc chute installation (Refer to page 9 for selection)
UR26/40/46 (Arc chute type 81/82) - UR60/80 (Arc chute type 82) Opening on LV connector side 1
UR26/40- Arc chute 64 Type SE 2
UR60/80 - Arc chute 81 Vertical removal 8
For other selection, refer to codification table page 9 ..................... ....
15 Control type Electric holding - without ECO-Drive E
Magnetic holding - without ECO-Drive M
Electric holding - with ECO-Drive (1) 4
16 Nominal supply voltage
UR26/40/46 24 V DC A
UR26/40/46/60/80 48 V DC C
UR26/40/46/60/80 (2) (60) 64 V DC G
UR26/40/46/60/80 110 V DC E
UR26/40/46/60/80 125 V DC R
UR60/80 (2) 200 V DC (3) K
UR26/40/46/60/80 220 V DC J
17 Varistor in coil (4) No Ø
Yes (battery voltage) 1
18 Direct over-current release (bi-directional)
UR26 1.4 - 2.7 kA A
UR26/40/46 2.0 - 8.0 kA D
UR40/46 4.0- 15.0 kA F
UR60 13.0 - 18.0 kA L
Name:
UR80 16.0 - 24.0 kA P
For other selection, refer to codification table page 6 ..................... ....
Direct over-current release (uni-directional) - UR60/80 W W
19 Indirect release (shunt trip) No Ø
UR26/40/46 (includes horizontal manual release) BIM5 5
UR26/40/46 (includes horizontal manual release) BIM6 7
UR60/80 (includes horizontal manual release) BIM7 4
UR60/80 (includes horizontal manual release) BIM8 6
20 Auxiliary contacts
UR26/40/46/60/80 5a + 5b - (switch PF) A
UR26/40/46 5a + 5b - (switch CO) B
21 LV connector type on circuit breaker
UR26/40/46/60/80 Harting type HAN® 32 EE C
UR40/46 Veam type 22 pins B
22 Manual release No Ø
UR26/40/46/60/80 Horizontal 1
UR26/40/46/60/80 Vertical 2
23 Manual closing device (not compatible with line 25 nor 26) No Ø
UR26/40/46/60/80 Yes 3
24 Position indicator No Ø
Yes 2
25 Overcurrent release detector (not compatible with line 23 nor 26) No Ø
UR26/40/46 Yes 1 Place and date:
26 Contact wear indicator (not compatible with line 23 nor 25) No Ø
UR26/40/46 Yes 1
27 HV main connections (according to pages 7 and 8) Standard S S
28 Digit for Sécheron internal purpose
UR26/40/46 Arc chute 81 B
UR26/40/46 Arc chute 82 C
UR26/40 Arc chute 64 G
UR60/80 Arc chutes 81 & 82 L