P R O D U C T OV E R V I E W
—
Surge arresters
for medium-voltage systems
The protection of medium-voltage systems is not limited to protection of
transformers. Electrical equipment such as generators, motors, overhead lines,
capacitors, cables and cable sheath also require their own surge arresters.
Overvoltages in electrical supply systems result from the In fact, all electrical equipment and installations in high-
effects of lightning incidents and switching actions and voltage and medium-voltage systems need overvoltage
cannot be avoided. They endanger the electrical equipment protection. In particular, the following equipment needs
because, for economic reasons, the insulation cannot be protection:
designed to withstand all possible cases.
• Transformers
The aim of overvoltage protection is to guarantee an • Cables and cable sheaths
uninterrupted supply of electrical energy with high voltage • Capacitors and capacitor banks
stability to the greatest degree possible. Therefore, the • Overhead lines
costs for a set of surge arresters are not the primarily • Rotating machines (motors and generators)
consideration, but the costs that may arise on a long-term • Power electronics
basis if adequate overvoltage protection is not used. • Coils and line traps
• Traction equipment (rolling stock and power supply)
Overvoltage protection that is accurately applied reduces: AC and DC
• Outages of lines and substations
• Interruptions of critical manufacturing processes that
demand high voltage stability
• Costs due to interruptions in the energy supply
• Costs for the replacement and repair of electrical
equipment
• Ageing of the insulation (e.g. cables)
• Maintenance work
S U R G E A R R E S T E R S F O R M E D I U M - V O LTA G E S Y S T E M S 5
—
ABB’s Surge Arresters
Modern metal-oxide surge arresters with direct silicone molding
cover most requirements. In recent decades, they have proved to be the
most reliable protection elements in the system.
The surge arresters limit harmful overvoltages, which are The left column of the selection table lists the various fields
generated in the network by lightning strikes or switching of application or protected equipment. The recommended
actions and thereby improve the availability and security of arresters for those applications are marked with black dots
the power supply. The surge arresters fulfill special require- in the respective rows.
ments regarding ambient conditions, energy handling capa-
bility, protection levels and stability of service.
—
Surge arresters
for medium-voltage systems
Recommended applications:
Distribution transformers, pole mounted
transformers ● ●
Arc furnace transformer, power transformer ● ●
Overhead lines ● ● ●
Air-insulated switchgear ● ●
Reactors, PLC traps, other MV equipment ●
Capacitor banks, filters ● ● ●
MV Cable and cable termination ● ● ●
Motors and generators ● ● ●
1) For neutral arresters can be used in systems with higher system voltage
2) According to IEC 60099-4. The arrester classes correspond to the line discharge classes as follows: DH-class 1, SL - class 2, SM - class 3, SH - class 4 and 5.
S U R G E A R R E S T E R S F O R M E D I U M - V O LTA G E S Y S T E M S 7
Recommended applications:
Air-insulated switchgear ●
Gas-insulated switchgear ●
HV cable sheath ● ● ●
Power electronics ● ● ●
Secondary equipment ● ● ●
Motor ● ● ●
1) For neutral arresters can be used in systems with higher system voltage
2) According to IEC 60099-4. The arrester classes correspond to the line discharge classes as follows: DH-class 1, SL - class 2, SM - class 3, SH - class 4 and 5.
8 PRODUC T OVE RVI E W SURGE A RRESTER S
—
Surge arresters
for AC traction systems
ABB offers a complete range of metal-oxide
surge arresters for AC traction systems, intended for
fixed installations and rolling stock.
Recommended applications:
Rolling stock ● ● ●
High speed trains ● ●
Fixed installation ● ● ● ●
Power electronics and other secondary equipment ● ●
10 PRODUC T OVE RVI E W SURGE A RRESTER S
—
Surge arresters
for DC traction systems
ABB’s metal-oxide surge arresters for DC traction
systems are developed and tested with reference to
IEC 62848-1 and EN 50526-1.
Recommended applications:
Rolling stock ● ● ●
High speed trains ●
Fixed installation A1 function ● ● ●
Fixed installation A2 function ● ● ●
Power electronics and other secondary equipment ● ● ●
11
—
To know more about ABB’s
portfolio offering for railways,
please visit abb.com/railway
● ● ●
●
● ●
●
12 PRODUC T OVE RVI E W SURGE A RRESTER S
—
Surge arresters
for high-voltage gas-insulated switchgear
ABB is a leading manufacturer of surge arresters for high-voltage gas-insulated
switchgear (HV GIS). The special design with high-field metal-oxide resistors
allows reduction of the size of surge arresters and the amount of SF6 inside.
1)
Also available with an oil/SF6 bushing for direct mounting on power transformers.
—
1 Enclosure
2 Grading electrode
3 Metal oxide resistor discs
4 Bushing for leakage current measure-
3 ment and surge monitoring
—
Uc > 116 kV To know more about ABB’s port-
folio offering for HV GIS, please
visit abb.com/high-voltage/gis
14 PRODUC T OVE RVI E W SURGE A RRESTER S
—
Monitoring systems
for surge arrester
Apart from the surge arresters portfolio ABB offers the monitoring
systems to monitor the leakage current during normal operation and
register surge current pulses.
SAM 3.0 is capable of sensitively registering surges from ABB Ability™ Wireless Monitor for surge arrester is a condi-
lightning and switching in combination with total leakage tion monitoring solution that makes predictive maintenance
current. The values are shown digitally on an electronic possible for almost all high- and medium-voltage surge
display. It consists of a current sensor with selectable cable arresters.
lengths and a display device which can be mounted apart
from the arrester. By monitoring and analyzing data of leakage current and
overvoltage discharge currents, it enables substation and
grid operators to optimize maintenance. The solution helps
to reduce downtime, increase grid reliance and reduce
maintenance costs.
Surge arresters monitoring systems SAM 3.0 ABB AbilityTM Wireless Monitor
Climatic conditions Sealed water-tight design, IP65 Sealed water-tight design, IP67
Surge current amplitude measurement, kA Classification of surge current amplitude 0.1-100
in three classes: 0.1-1/1-10/10-100
Measurement range of leakage current (mA peak) 0-20 mA 0-12 mA
Memory capacity 2000 events One month on device, unlimited in the cloud
Power supply Battery Battery (recharges through solar panel)
Communication Display Wireless monitor: transmission of
measurements via LoRaWAN to the cloud
Additional features SAM sensor galvanically isolated from Measurement of humidity and ambient
(display can be mounted apart from temperature
surge arrester) Registering time-stamp of event
Registering time-stamp of event
—
To know more about ABB’s
portfolio offering for monitoring
systems, please visit
abb.com/arrestersonline
V O LTA G E L I M I T I N G D E V I C E A G A I N S T ‘ TO U C H ’ V O LTA G E 15
—
Voltage limiting device
to protect against impermissible
‘touch’ voltage
The voltage limiting device is represented with hybrid voltage limiter (HVL),
which is available in two arrangements, limiting the voltage up to 60 V
and up to 120 V.
Impermissible ‘touch’ voltages can occur in DC traction The HVL limits ‘touch’ voltages regardless of whether they
systems between track systems (return conductors) and are purely DC or mixed voltages (both DC and AC voltages)
earthed metal structures, as the track systems are laid to the permissible limit values defined for railway installa-
insulated. tions, workshops and other locations.
—
Design and testing –
quality in a foreground
With surge arresters of ABB you buy a complete solution to
overvoltages in your network.
—
In ABB we value quality and
customer satisfaction. Therefore,
we perform thorough tests on
our products and components.
17
Additional information
The information given in this document
inclusive of all illustrations covers key
technical data and application options.
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. With
regard to purchase orders, the agreed
particulars shall prevail. ABB does not
accept any responsibility whatsoever for
potential errors or possible lack of infor-
mation in this document. We reserve all
rights in this document and in the sub-
ject matter and illus-trations contained
therein. Any reproduction, disclosure to
third parties or utilization of its con-
tents – in whole or in parts – is forbidden
without prior written consent of ABB.
Copyright © 2019 ABB
All rights reserved
—
ABB Switzerland Ltd.
High Voltage Products
Surge Arresters
Jurastrasse 45
CH-5430 Wettingen/Switzerland
Phone +41 58 585 29 11
E-Mail sales.sa@ch.abb.com
abb.com/arrestersonline
1HC0075750 AG EN