Professional Documents
Culture Documents
Contents
Appendix A.1 Digital Data
A.1.1. Switchgear and Controller State Flags
A.1.2. Operator/Protection Flags for ACR
A.1.3. Protection Trip Flags ACR
A.1.4. Distributed Automation Flags
A.1.5. Pickup Flags
A.1.6. IOEX Inputs
A.1.8. Protocol IOEX Control Status
Appendix A.2 Analog Data
A.2.1. Line Currents
A.2.2. Voltage Measurements
A.2.3. System Power
A.2.4. SF6 Gas Pressure
A.2.5. Protection State
A.2.6. Protection Sequence and Trip Data
A.2.7. Switchgear Details
A.2.8. Controller Data
A.2.9. Distributed Automation
A.2.10. Daily Data
A.2.11. Supply Outage Measurement
A.2.12. Frequency Measurement
A.2.15. Sequence Components
Appendix A.3 Accumulator Data
A.3.1. Trip Counters
A.3.2. Pickup Counters
A.3.3. Fault Counters
Appendix A.5 LBS Points Data
A.5.1. Operator/Detection Flags for LBS
A.5.2. Detection Flags LBS
Appendix A.6 LBS Analog Data
A.6.1. Detection State
A.6.2. Fault Detection Data
Appendix A.7 Protocol-Specific Data
A.7.1. Protocol-Specific Digital status points.
A.7.2. Protocol-Specific Analog status points.
A.7.3. Protocol-Specific Counter status points.
Appendix A.8 Custom Data
A.8.1. Custom Variables
A.8.2. Custom Counters
A.8.3. Custom Timers
A.8.4. Custom Digitals
Version
Point Name Description Set = '1' Clear = '0'
Introduced
For any of the following
conditions:-
Capacitor charge
"status" is Failure.
Switchgear data
not valid (includes
connection to an
invalid switch
type).
Any vacuum
interrupter contact
life is less than
20%.
Mechanism Fail.
Switchgear not
connected.
Firmware
missmatch.
Power Supply is
"Over Voltage".
zeroed.
Shows the connection
state between the
switchgear and the
controller. When
connected the
Switchgear Switch disconnected Switch connected to
22 switchgear Trip, Close 41-00.00
Connection from control cubicle. control cubicle.
and Locked indications
are valid. When
disconnected switchgear
data will be forced
Invalid.
Indicates the wear of the Any vacuum interrupter All vacuum
Contact Life
23 contacts in the vacuum contact life is less than interrupters have 41-00.00
Low
interrupters 20%. contact life >= 20%.
SF6 Gas
Pressure
This point will only be set Normal.
when the switchgear is SF6 Gas
SF6 Gas connected, switchgear Pressure Not
Gas Pressure Low or
24 Pressure Low- data is valid, switchgear Known. 41-00.00
Invalid.
or-Invalid type has SF6 and the Switchgear
gas pressure is Low or Does Not Have
Invalid. SF6 Gas.
This includes :-
Note : Also part of
Battery Supply Battery supply
28 "Maintenance 41-00.00
Fail Battery Off. Normal.
Required".
Battery Overvolt.
Battery Low Volts.
The Trip/Close
Capacitor Capacitor Charge Capacitor Charge
29 Capacitors have failed to 41-00.00
Charge Failure Failed. OK.
charge.
The switchgear has
Mechanism
30 failed to Trip or Close Mechanism Failure. Mechanism OK. 41-00.00
Fail
electrically
The Dummy Circuit
Breaker is an internal
point used for SCADA
Dummy Circuit system testing. It can be
31 Breaker Tripped or Closed. The DCB Closed. DCB Not Closed. 41-00.00
Closed value of this point is non-
volatile, ie. Is retained
through power-downs
and restarts.
Directional blocking is
The directional blocking enabled and Vo is
Directional blocking
SEF/SGF High facility includes detection sustained (after
is not enabled or Vo
32 Residual of high residual voltage balancing) above the 41-00.00
is below the
Voltage Alarm (Vo) above the SEF/SGF Min SEF/SGF Vo
threshold.
threshold setting.(2) threshold for the High Vo
Alarm time or longer.
Supply Outage
Supply Outage Supply Outage
33 Measurement is 41-00.00
Measurement Measurement is ON.
OFF.
34 Door Open Status of cubicle door. Door open. Door closed. 41-00.00
Switch Function is Automatic Function is Load
35 41-00.00
Function Circuit Recloser Break Switch
Auxiliary Status of controller Auxiliary supply has Auxiliary supply
36 Supply Fail auxiliary supply failed for more than 120 restored for more 41-00.00
Delayed (delayed). seconds. than 20 seconds.
The Dummy Circuit
Breaker is an internal
point used for SCADA
Dummy Circuit system testing. It can be
37 Breaker Tripped or Closed. The DCB Tripped. DCB Not Tripped. 41-00.00
Tripped value of this point is non-
volatile, ie. Is retained
through power-downs
and restarts.
Status of a battery test.
This is the result of a
large load applied for 10 The battery has failed a
Battery Test
38 seconds, and then battery test and requires The battery is ok. 41-00.00
Fail
removed for 10 seconds replacement.
and comparing the three
resulting voltages
Battery Test in The battery test is in The battery test is
39 41-00.00
Progress progress. NOT in progress.
No controller settings
have been changed.
Cleared by binary
Settings The settings have been
40 output "Reset Fault 41-00.00
Changed changed by a user.
Flags", "Reset Fault
Flags and Currents"
or "Clear Settings
Changed".
There are no Non
Normal Alert A non critical alert is At least 1 normal alert is
41 Critical Alerts present 44-00.00
Active active on the controller. active on the controller
on the Controller.
There are no Critical
Critical Alert A critical alert is active on At least 1 critical alert is
42 Alerts present on the 44-00.00
Active the controller. active on the controller
Controller.
Normal state,
Cleared on next
Not suitable for poll Set when a Trip Request
49 Trip Request internal scan after 43-06.11
oriented protocols. is issued.
Set. Point cleared
after 1 second.
Point Cleared by
"Reset fault
flags and
currents"
control.
A trip operation was "Reset Fault
Point Cleared by
"Reset fault
flags and
currents"
control.
A close operation was "Reset Fault
attempted but could not Flags" control.
A Close operation has
51 Close Aborted be completed due to low Any successful 44-20.01
been aborted
battery capacity and was trip or close
aborted. operation.
Controller
software reset
(data is
volatile).
IOEX-A
52 Connection IOEX-A Connected IOEX-A Disconnected 44-04.19
Status
IOEX-B
flag for IOEX-B IOEX-B
53 Connection IOEX-B Connected 44-04.19
Connection Status. Disconnected
Status
This point is asserted
when the switchgear is in
the 'Closed' state, and
remains asserted for a
Extended Switchgear has been
period of 300 ms after
54 Switchgear Switchgear Closed Tripped for at least 44-28.20
the switchgear is 'NOT-
Closed 300ms
closed'. This point is
cleared immediately
when the switchgear has
been disconnected.
Circuit Breaker OK.
1-
This item indicates the status of the switchgear. It is recommended that it is always sent to a SCADA
system and displayed. It indicates in summary form the information which an operator can use to
determine if the switchgear is working correctly, if maintenance is required and if the local operator has
Version
Point Name Description Set = '1' Clear = '0'
Introduced
Earth/Ground
Earth/Ground Protection Earth/Ground
0 Protection 41-00.00
ON. Protection OFF.
Enabled
SEF/SGF
SEF/SGF protection
1 Protection SEF/SGF protection ON. 41-00.00
OFF.
Enabled
2 Auto Reclose Auto Reclose ON. Auto Reclose OFF. 41-00.00
Cold Load Pickup is in
Auto.This means the cold
Cold Load pickup is
load function is functioning
OFF. This means the
3 Cold Load Auto and may, or may not, be 41-00.00
cold load function is
affecting the threshold
completely disabled.
multiplier. This is indicated by
the Cold Load Active flag.
Cold Load is Idle or is
Cold load is NOT Idle. This
turned OFF. This
means the threshold
Cold Load See Protection means the threshold
4 multiplier is being raised by 41-00.00
Active State section. multiplier will not be
the cold load pickup function
affected by the cold
in order to raise cold load.
load function.
High Current
High Current Lockout
5 Lockout High Current Lockout ON. 41-00.00
OFF.
Enabled
Either Loss Of Phase
Loss of Phase Loss of Phase Trip Protection is OFF or
6 (1) 41-00.00
Protection ENABLED. Loss Of Phase Alarm
ENABLED.
Sequence Sequence Control
7 Sequence Control ON. 41-00.00
Control OFF.
Live Load Live Load Blocking
8 Live Load Blocking ON. 41-00.00
Blocking OFF.
Protection turned OFF.
Protection
9 Protection ON. No protection trips will 41-00.00
ON/OFF
occur.
Automatic
Automatic Protection
Protection Automatic Protection Group
10 Group Selection is 41-00.00
Group Selection is ON.
OFF.
Selection
The Under/Over
The Under/Over Frequency
Normal Freq Frequency protection
11 protection has "Normal Freq 41-00.00
Close On/Off has "Normal Freq
Close" ON.
Close" OFF.
In both cases the flags below are set to show what caused of the trips and whether the lockout state has
been reached or not.
Analog data is available which shows the fault currents during the sequence and how many trips occurred.
Refer A.2.6
Most of these flags are cleared by a protocol command, a switchgear trip/close by the operator, or when a
new protection sequence starts.
If there is more than one protocol running simultaneously in the controller this data is replicated between the
protocols so that each master station can clear its data independently from the others.
Version
Point Name Description Set = '1' Clear = '0'
Introduced
This shows that a
protection sequence has
Start of sequence ie. End of sequence.
started and not yet
Sequence in a protection trip or Either by lockout or
0 completed. Note that an 41-00.00
Progress sequence advance sequence reset
operator trip does not
has occurred. timeout.
cause a "Sequence in
Progress".
This shows that the
protection sequence is
over and the other flags
are set. Can be used to
drive an operator alarm End of sequence.
Protection Data through the SCADA Either by lockout or
1 41-00.00
Valid system to warn that a sequence reset
protection sequence has timeout.
occurred. Note that an
operator trip alone does
not cause a "Protection
Data Valid" .
Phase
Phase Overcurrent
2 Overcurrent Trip 41-00.00
Protection Trip 1
1
Phase
Phase Overcurrent
3 Overcurrent Trip 41-00.00
Protection Trip 2
2
Phase
Phase Overcurrent
4 Overcurrent Trip 41-00.00
Protection Trip 3
3
Phase
Phase Overcurrent
5 Overcurrent Trip All flags are cleared 41-00.00
Protection Trip 4
4 by:
Earth/Ground Earth/Ground
6 Overcurrent Trip Overcurrent "Reset fault flags 41-00.00
1 Protection Trip 1 and currents"
Earth/Ground Earth/Ground control.
7 Overcurrent Trip Overcurrent "Reset Fault 41-00.00
2 Protection Trip 2 Flags" control.
Any operator
Earth/Ground Earth/Ground close action.
8 Overcurrent Trip Overcurrent Start of a new 41-00.00
3 Protection Trip 3
sequence.
Earth/Ground Earth/Ground Controller
9 Overcurrent Trip Overcurrent software reset 41-00.00
4 Protection Trip 4 (data is volatile).
Protection turned
SEF/SGF Sensitive OFF.
protection sequence
cleared the fault.
A combination of an
One flag only because OCPM Operator Trip
Cleared by any close
25 Operator Trip operator trip forces OR an IOEX 41-00.00
action.
lockout. Operator Trip OR a
Protocol Trip.
Protection Flags are
Set if the most recent The most recent cleared by one of the
Protection Flag- protection operation was protection operation following actions:-
26 Phase caused by a Phase was caused by a 41-00.00
Overcurrent Overcurrent Protection Phase Overcurrent "Reset Fault
Trip. Protection Trip Flags and
Currents" control.
The most recent "Reset Fault
Set if the most recent Flags" control.
protection operation
Protection Flag- protection operation was Operator Close.
was caused by an
27 Earth/Ground caused by an At the time of the 41-00.00
Earth/Ground
Overcurrent Earth/Ground next trip the flags
Overcurrent
Overcurrent Protection. are 'refreshed'.
Protection Trip.
Old flags are
cleared and the
The most recent cause of the 'most
Set if the most recent recent' protection
protection operation
Protection Flag- protection operation was operation set.
was caused by an
28 SEF/SGF caused by an SEF/SGF Protection turned 41-00.00
SEF/SGF
Overcurrent Overcurrent Protection OFF.
Overcurrent
Trip.
Protection Trip.
Cleared by:
Any Operator
Close or Operator
The most recent trip
Trip. This includes
OCP Operator was caused by a
29 remote control 41-00.00
Trip local or remote
commands.
operator panel trip.
Start of a new
sequence.
Cleared by:
The most recent trip
IOEX Operator was caused by an Any Operator
30 41-00.00
Trip IOEX Operator Trip Close or Operator
input Trip. This includes
remote control
The most recent trip commands.
IOEX Protection was caused by an Start of a new
31 sequence. 41-00.00
Trip IOEX Protection
Input
Phase A
Phase A Overcurrent
41 Overcurrent Trip 41-00.00
Protection Trip 1
1
Phase A
Phase A Overcurrent
42 Overcurrent Trip 41-00.00
Protection Trip 2
2
Phase A
Phase A Overcurrent
43 Overcurrent Trip 41-00.00
Protection Trip 3
3
Phase A
Phase A Overcurrent
44 Overcurrent Trip 41-00.00
Protection Trip 4 Cleared by:
4
Phase B "Reset Fault flags
Phase B Overcurrent
45 Overcurrent Trip and Currents" 41-00.00
Protection Trip 1
1 control.
Phase B "Reset Fault
Phase B Overcurrent
46 Overcurrent Trip Flags" control. 41-00.00
Protection Trip 2
2 Any Operator
Phase B Close. This
Phase B Overcurrent includes remote
47 Overcurrent Trip 41-00.00
Protection Trip 3 control
3
Phase B commands.
Phase B Overcurrent Start of a new
48 Overcurrent Trip 41-00.00
Protection Trip 4 sequence.
4
Phase C
Phase C Overcurrent
49 Overcurrent Trip 41-00.00
Protection Trip 1
1
Phase C
Phase C Overcurrent
50 Overcurrent Trip 41-00.00
Protection Trip 2
2
Phase C
Phase C Overcurrent
51 Overcurrent Trip 41-00.00
Protection Trip 3
3
Phase C Overcurrent
52 Phase C 41-00.00
Protection Trip 4
Overcurrent Trip
4
Peak Fault Current
Instantaneous for trip was above the
53 41-00.00
Trip Flag 1 Instantaneous
Multiplier setting.
Peak Fault Current
Instantaneous for trip was above the
54 41-00.00
Trip Flag 2 Instantaneous
Multiplier setting.
Peak Fault Current
Instantaneous for trip was above the
55 41-00.00
Trip Flag 3 Instantaneous
Multiplier setting.
Peak Fault Current
Instantaneous for trip was above the
56 41-00.00
Trip Flag 4 Instantaneous
Multiplier setting.
Protection Flags are
The most recent trip cleared by one of the
Most Recent
was caused by an A following actions:-
57 Trip Phase A 41-00.00
Phase Overcurrent
Overcurrent
Protection Trip. "Reset Fault
Flags and
Currents" control.
The most recent trip "Reset Fault
Most Recent
was caused by a B Flags" control.
58 Trip Phase B 41-00.00
Phase Overcurrent Operator Close.
Overcurrent
Protection Trip At the time of the
next trip the flags
are 'refreshed'.
The most recent trip Old flags are
Most Recent
was caused by a C cleared and the 41-00.00
59 Trip Phase C
Phase Overcurrent cause of the 'most
Overcurrent
Protection Trip recent' protection
operation set.
Protection turned
The peak current for OFF.
Instantaneous the most recent trip Controller
60 Most Recent was greater than the Software Reset 41-00.00
Trip Instantaneous (data is volatile).
setting.
Cleared by:
Flags and
Currents" control.
The most recent trip "Reset Fault
Most Recent
was caused by an Flags" control.
66 Trip 41-00.00
Earth/Ground Operator Close.
Earth/Ground
overcurrent fault At the time of the
next trip the flags
are 'refreshed'.
Old flags are
cleared and the
The most recent Trip cause of the 'most
Most Recent was caused by a recent' protection
67 operation set. 41-00.00
Trip SEF/SGF SEF/SGF
overcurrent fault Protection turned
OFF.
"Reset Fault
Flags and
Currents" control.
"Reset Fault
Flags" control.
Operator Close.
At the time of the
Indicates if the most The most recent next protection
Protection Flag- recent protection protection operation trip the flags are
76 NPS operation was caused by was caused by an 'refreshed'. Old 41-00.00
Overcurrent an NPS Overcurrent NPS Overcurrent flags are cleared
Protection Trip. Protection Trip. and the cause of
the 'most recent'
protection
operation set.
Protection turned
OFF.
"Reset Fault
Flags and
Currents" control.
"Reset Fault
Flags" control.
Operator Close.
The most recent trip Protection turned
Most Recent was caused by a OFF.
77 41-00.00
Trip NPS NPS overcurrent Start of a new
fault. sequence.
At the time of the
next trip the flags
are 'refreshed'.
Old flags are
cleared and the
cause of the 'most
recent' trip set.
Controller reset
"Reset Fault
Flags and
Currents" control.
"Reset Fault
Flags" control.
Most recent trip
Most Recent Operator Close.
82 caused by an IOEX 41-00.00
Trip External Protection turned
Protection Input
OFF.
Start of a new
sequence.
"Reset Fault
The most recent trip Flags and
was caused by a Currents" control.
Automation Loop Automation, "Reset Fault
83 Flags" control. 41-00.00
Trip-B Generator Control, or
an Auto changeover Operator Close.
Trip request. At the time of the
next trip the flags
are 'refreshed' at
this time old flags
are cleared and
the cause of the
'most recent'
protection
operation set.
The most recent trip Protection turned
One flag only because OFF.
84 Mechanical Trip was caused by a 41-00.00
this trip forces lockout Start of a new
Mechanical Trip.
sequence.
Most Recent This flags whether the The most recent trip These flags are cleared
Trip Phase most recent trip was was caused by a by one of the following
85 41-00.00
Overcurrent- caused by a Phase Phase Overcurrent actions:
Close Reset Overcurrent Fault. Fault.
Most Recent This flags whether the "Reset Fault
The most recent trip
Trip most recent trip was Flags and
was caused by an
86 Earth/Ground caused by an Currents" control. 41-00.00
Earth/Ground
Overcurrent- Earth/Ground "Reset Fault
Overcurrent Fault.
Close Reset Overcurrent Fault. Flags" control.
Most Recent This flags whether the The most recent trip Any Close action.
Trip SEF/SGF most recent trip was was caused by an Protection turned
87 OFF. 41-00.00
Overcurrent- caused by an SEF/SGF SEF/SGF
Close Reset Overcurrent Fault. Overcurrent Fault. Controller
Most Recent This flags whether the The most recent trip software reset
Trip NPS most recent trip was was caused by an (data is volatile).
88 41-00.00
Overcurrent- caused by an NPS NPS Overcurrent
Close Reset Overcurrent Fault. Fault.
Reverse Phase Reverse Phase
89 Overcurrent Trip Overcurrent 41-00.00
1 Protection Trip 1
Reverse Phase Reverse Phase
90 Overcurrent Trip Overcurrent 41-00.00
2 Protection Trip 2
3 Protection Trip 3
Reverse Phase Reverse Phase
92 Overcurrent Trip Overcurrent 41-00.00
4 Protection Trip 4
Reverse Reverse
Earth/Ground Earth/Ground
93 41-00.00
Overcurrent Trip Overcurrent
1 Protection Trip 1
Reverse Reverse
Earth/Ground Earth/Ground
94 41-00.00
Overcurrent Trip Overcurrent
2 Protection Trip 2 All flags are cleared
Reverse Reverse by:
Earth/Ground Earth/Ground
95 "Reset fault flags 41-00.00
Overcurrent Trip Overcurrent
3 Protection Trip 3 and currents"
control.
Reverse Reverse
"Reset Fault
Earth/Ground Earth/Ground
96 Flags" control. 41-00.00
Overcurrent Trip Overcurrent
Any operator
4 Protection Trip 4
close action.
Reverse Start of a new
Reverse Sensitive
SEF/SGF sequence.
97 Earth/Ground Fault 41-00.00
Overcurrent Trip Controller
Protection Trip 1
1 software reset
Reverse (data is volatile).
Reverse Sensitive
SEF/SGF Protection turned
98 Earth/Ground Fault 41-00.00
Overcurrent Trip OFF.
Protection Trip 2
2
Reverse
Reverse Sensitive
SEF/SGF
99 Earth/Ground Fault 41-00.00
Overcurrent Trip
Protection Trip 3
3
Reverse
Reverse Sensitive
SEF/SGF
100 Earth/Ground Fault 41-00.00
Overcurrent Trip
Protection Trip 4
4
Single Shot
Only one flag provided
Reverse Single Protection was active
101 because a single shot 41-00.00
Shot Protection at the time of the
trip forces lockout.
reverse trip.
Cleared by:
Multiplier setting.
Peak Fault Current
Reverse for reverse trip was
121 Instantaneous above the 41-00.00
Trip Flag 4 Instantaneous
Multiplier setting.
The most recent Protection Flags are
Most Recent cleared by one of the
reverse trip was
Reverse Trip following actions:-
122 caused by an A 41-00.00
Phase A
Phase Overcurrent
Overcurrent "Reset Fault
Protection Trip.
Flags and
The most recent Currents" control.
Most Recent "Reset Fault
reverse trip was
Reverse Trip Flags" control.
123 caused by a B Phase 41-00.00
Phase B Operator Close.
Overcurrent
Overcurrent At the time of the
Protection Trip
next trip the flags
The most recent are 'refreshed'.
Most Recent Old flags are
reverse trip was
Reverse Trip cleared and the 41-00.00
124 caused by a C Phase
Phase C cause of the 'most
Overcurrent
Overcurrent recent' protection
Protection Trip
operation set.
Protection turned
The peak current for OFF.
the most recent Controller
Instantaneous
reverse trip was Software Reset
125 Most Recent 41-00.00
greater than the (data is volatile).
Reverse Trip
Instantaneous
setting.
Trip Flags are cleared
The most recent by one of the following
Reverse Most actions:-
Reverse Trip was
128 Recent Trip 41-00.00
caused by a Phase
Phase
overcurrent fault "Reset Fault
Flags and
Currents" control.
"Reset Fault
The most recent Flags" control.
Reverse Most Reverse Trip was Operator Close.
129 Recent Trip caused by an At the time of the 41-00.00
Earth/Ground Earth/Ground next trip the flags
overcurrent fault are 'refreshed'.
Old flags are
cleared and the
cause of the 'most
The most recent recent' protection
Reverse Most Reverse Trip was operation set.
130 Recent Trip caused by a Protection turned 41-00.00
SEF/SGF SEF/SGF OFF.
overcurrent fault
"Reset Fault
Flags and
Currents" control.
"Reset Fault
The most recent Flags" control.
Reverse Indicates if the most protection operation Operator Close.
"Reset Fault
Flags and
Currents" control.
"Reset Fault
Flags" control.
Operator Close.
The most recent Protection turned
Most Recent
Reverse Trip was OFF.
132 Reverse Trip 41-00.00
caused by aNPS Start of a new
NPS
overcurrent fault. sequence.
At the time of the
next trip the flags
are 'refreshed'.
Old flags are
cleared and the
cause of the 'most
recent' trip set.
Controller reset
"Reset Fault
Flags and
Indicates that the most Most recent close
Directional Currents" control.
recent close was caused caused by a
141 Protection Auto "Reset Fault 41-00.00
by a directional directional protection
Restore Flags" control.
protection auto restore. auto restore.
Any Close action.
Controller
software reset
(data is volatile).
Cleared by either:
Trips followed by a
Close due to Over
Excess Over Excess Over Voltage
Voltage Protection has
149 Voltage Sequecnes have 42-00.00
exceeded the allowed
Sequences occurred
number in the time
allocated
Active
150 Protection 42-00.00
Group A
Active
151 Protection 42-00.00
Group B
Active Cleared by one of the
152 Protection following actions 42-00.00
Group C
Active 'Reset Flags and
153 Protection Currents' protocol 42-00.00
Group D command.
Active Any operator
154 Protection close (including 42-00.00
The active protection The active protection
Group E remote
group for the most group for the most
commands).
Active recent protection recent protection
Start of a new
155 Protection sequence. sequence. 42-00.00
sequence. The
Group F time stamp
Active reflects this.
156 Protection Controller 42-00.00
Group G Software Reset
Active (data is volatile).
157 Protection 42-00.00
Group H
Active
158 Protection 42-00.00
Group I
Active
159 Protection 42-00.00
Group J
A Phase
A Phase Overcurrent Cleared by
160 Overcurrent 44-04.25
Fault
Fault Operator trip.
These flags show which
B Phase Any close.
elements were picked up B Phase Overcurrent
161 Overcurrent Reset Flags' 44-04.25
at the time of the most Fault
Fault Protocol
recent fault.
C Phase Command.
C Phase Overcurrent
162 Overcurrent 44-04.25
Fault
Fault
This point is a
combination (OR)
between Phase
Overcurrent Protection
Trip 1, Phase
Phase Phase Overcurrent
163 Overcurrent Protection 44-14.00
Overcurrent Trip Protection Trip
Trip 2, Phase
Overcurrent Protection
Trip 3, Phase All flags are cleared
by:
Overcurrent Protection
Trip 4.
"Reset fault flags
This point is a and currents"
combination (OR) control.
between Earth/Ground "Reset Fault
Overcurrent Protection Flags" control.
Trip 1, Earth/Ground Earth/Ground Any operator
1- Note: The phase designation A, B, C is determined by the user, refer to the Switchgear Details section
and the Switchgear Technical Manual.
Version
Point Name Description Set = '1' Clear = '0'
Introduced
Loop Automation Loop Automation is Loop Automation is
0 41-00.00
On ON. OFF.
Loop Automation Auto Restore is Auto Restore is
1 41-00.00
Auto Restore On ON. OFF.
The Tie Recloser will
only restore supply
The Tie Recloser is
Loop Automation to its Load side or
configured to
2 Tie Restore the Recloser Type is 41-00.00
restore supply in
Direction not set to 'Tie'.
both directions.
(1)
Loop Automation
Recloser Type is Recloser Type is not
3 Recloser Type 41-00.00
set to 'Feeder'. set to 'Feeder'.
Feeder
Loop Automation
Recloser Type is Recloser Type is not
4 Recloser Type 41-00.00
set to 'MidPoint'. set to 'MidPoint'.
MidPoint
Loop Automation Recloser Type is Recloser Type is not
5 41-00.00
Recloser Type Tie set to 'Tie'. set to 'Tie'.
Normal state,
Cleared on next
Set when Loop
Loop Automation Not suitable for poll internal scan after
8 Automation issues 41-00.00
Trip Request oriented protocols. Set. Point cleared
a Trip Request.
after 1 second.
Normal state,
Set when Loop Cleared on next
Loop Automation Not suitable for poll
9 Automation issues internal scan after 41-00.00
Close Request oriented protocols.
a Close Request. Set. Point cleared
after 1 second.
Auto-Changeover Auto-Changeover is Auto-Changeover Auto-Changeover is
13 44-36.00
Enabled Enabled/Disabled is ENABLED. DISABLED.
Auto-Changeover Auto-Changeover Device Device is the ACO Device is the ACO
15 44-36.00
Rank Rank Master. Slave.
Auto-Changeover Auto-Changeover ACO local device ACO local device is
18 44-36.00
Ready Ready/Not Ready is ready. not ready.
The ACO scheme is
Auto-Changeover Auto-Changeover Scheme The ACO scheme
19 enabled but has not 44-36.00
Running Waiting/Running is running.
started yet.
Auto-Changeover Auto-Changeover Master is supplying Slave is supplying
20 44-36.00
Load Supply Supplying Source the load the load
Auto-Changeover
21 Critical Load Live/Dead Critical load is Live Critical load is Dead 44-36.00
Critical Load Live
ACO
Auto-Changeover Auto-Changeover ACO
communications lost
22 Communications Communications communications 44-36.00
(ping or command
OK Connected/Disconnected OK
failure)
1- Notes
1.The power flow direction (source/load designation) is determined by the user, refer to Recloser and
Controller State Flags section, Power Flow Direction for status, Power Flow Direction for control.
A.1.5Pickup Flags
These flags show the pickup and reset of individual protection elements.
Version
Point Name Description Set = '1' Clear = '0'
Introduced
A-Phase
0 Overcurrent (1) Pickup. Pickup Reset. 41-00.00
Pickup
B-Phase
1 Overcurrent (1) Pickup. Pickup Reset. 41-00.00
Pickup
C-Phase
2 Overcurrent (1) Pickup. Pickup Reset. 41-00.00
Pickup
Earth/Ground
3 Overcurrent Pickup. Pickup Reset. 41-00.00
Pickup
SEF/SGF
4 Overcurrent Pickup. Pickup Reset. 41-00.00
Pickup
Under
5 Frequency Pickup. Pickup Reset. 41-00.00
Pickup
Over Frequency
6 Pickup. Pickup Reset. 41-00.00
Pickup
Phase A Pickup Phase A Current has
11 41-00.00
Latched exceeded its threshold Cleared by
"Reset fault
Under Measured frequency has flags and
16 Frequency fallen below the low currents" 41-00.00
Pickup latched frequency threshold. control.
"Reset Fault
Flags"
control.
Next pickup
detected and
Measured frequency has this pickup
Over Frequency has cleared. 41-00.00
17 risen above the high
Pickup Latched Protection
frequency threshold.
turned OFF.
"Reset fault
flags and
currents"
control.
"Reset Fault
Flags"
control.
Next pickup
NPS Current has detected and
NPS Pickup
22 exceeded the NPS this pickup 41-00.00
Latched
threshold setting. has cleared.
Protection
turned OFF.
"Reset Fault
Flags and
Currents"
This flags that a NPS
A NPS fault has been control.
27 NPS Alarm fault has been picked 41-00.00
picked up. "Reset Fault
up.
Flags"
control.
Controller
software
reset (data is
volatile).
"Reset Fault
Flags and
Currents"
This flags whether an control.
"Reset Fault
Flags and
This flags that a Loss Of Currents"
Phase condition has A Loss Of Phase control.
Loss Of Phase
30 been detected but Loss condition has been "Reset Fault 41-00.00
Alarm
Of Phase is in the Alarm detected. Flags"
mode. control.
Controller
software
reset (data is
volatile).
Reverse A-
Reverse Pickup
31 Phase (1) Reverse Pickup. 41-00.00
Reset.
Overcurrent
Reverse B-
Reverse Pickup
32 Phase (1) Reverse Pickup. 41-00.00
Reset.
Overcurrent
Reverse C-
Reverse Pickup
33 Phase (1) Reverse Pickup. 41-00.00
Reset.
Overcurrent
Reverse
Earth/Ground Reverse Pickup
34 Reverse Pickup. 41-00.00
Overcurrent Reset.
Pickup
Reverse
SEF/SGF Reverse Pickup
35 Reverse Pickup. 41-00.00
Overcurrent Reset.
Pickup
Reverse Phase Reverse Phase A Current
36 A Pickup has exceeded its Cleared by 41-00.00
Latched threshold setting.
"Reset fault
Reverse Phase Reverse Phase B Current
flags and
37 B Pickup has exceeded its 41-00.00
currents"
Latched threshold setting.
control.
Reverse Phase Reverse Phase C "Reset Fault
38 C Pickup Current has exceeded its Flags" 41-00.00
Latched threshold setting. control.
Reverse Earth/Ground Current Next pickup
"Reset fault
flags and
currents"
control.
"Reset Fault
Reverse NPS Current Flags"
Reverse NPS
42 has exceeded the NPS control. 41-00.00
Pickup Latched
threshold setting. Next pickup
detected and
this pickup
has cleared.
Protection
turned OFF.
reset (data is
volatile).
"Reset Fault
Flags and
Currents"
This flags whether a
control.
reverse NPS
"Reset Fault
Accumulated Overcurrent Trip One or more trips were
Flags"
47 Reverse NPS occured. This flag can caused by a reverse NPS 41-00.00
control.
Overcurrent Trip. be set at the same time Overcurrent protection.
Any operator
as other accumulated
close action.
flags.
Controller
software
reset (data is
volatile).
Start of a new
sequence.
Any Phase
Whether any phase has A phase reverse pickup All phase reverse
Reverse
48 detected reverse on any phase has been pickups have been 41-00.00
Overcurrent
overcurrent. detected. reset.
Pickup
The measured 'Source'
Under Voltage Voltage has fallen
49 Pickup Reset 42-00.00
Pickup below the Under
Voltage trip threshold
The measured 'Source'
Over Voltage Voltage has risen above
50 Pickup Reset 42-00.00
Pickup the Over Voltage trip
threshold
Cleared by
This alarm is
cleared by one of
the following
actions:
53 SEF/SGF Alarm 44-42.00
This flags that a
SEF/SGF fault has A SEF/SGF fault has Fault is
been picked up and been picked up and removed.
SEF/SGF Alarm definite SEF/SGF Alarm definite Controller
1- Note: The phase designation A, B, C is determined by the user, refer to switchgear details section and the
Switchgear Technical Manual.
2- If directional protection is ENABLED then this point only refers to the forward direction.
A.1.6IOEX Inputs
These flags reflect the raw states of the IOEX inputs after a 30ms debounce. These flags will be clear if the
associated IOEX card is not connected.
Version
Point Name Description Set = '1' Clear = '0'
Introduced
IOEX-A Input Input Not
0 41-00.00
Input 1 Asserted Asserted
IOEX-A Input Input Not
1 41-00.00
Input 2 Asserted Asserted
IOEX-A Input Input Not
2 41-00.00
Input 3 Asserted Asserted
IOEX-A Input Input Not
3 41-00.00
Input 4 Asserted Asserted
IOEX-A Input Input Not
4 41-00.00
Input 5 Asserted Asserted
IOEX-A Input Input Not
5 41-00.00
Input 6 Asserted Asserted
IOEX-A Input Input Not
6 41-00.00
Input 7 Asserted Asserted
IOEX-A Input Input Not
7 41-00.00
Input 8 Returned State changes after 30ms Asserted Asserted
IOEX-B debounce. Input Input Not
8 44-28.00
Input 1 Asserted Asserted
IOEX-B Input Input Not
9 44-28.00
Input 2 Asserted Asserted
IOEX-B Input Input Not
10 44-28.00
Input 3 Asserted Asserted
IOEX-B Input Input Not
11 44-28.00
Input 4 Asserted Asserted
IOEX-B Input Input Not
12 44-28.00
Input 5 Asserted Asserted
IOEX-B Input Input Not
13 44-28.00
Input 6 Asserted Asserted
IOEX-B Input Input Not
14 44-28.00
Input 7 Asserted Asserted
IOEX-B Input Input Not
15 44-28.00
Input 8 Asserted Asserted
"Protocol IOEX Control Status" points can be selected to stimulate IOEX outputs with the IOEX
configuratioon tool.
Version
Point Name Description Set = '1' Clear = '0'
Introduced
Protocol
0 IOEX Control 41-00.00
1 State
Protocol
1 IOEX Control 41-00.00
2 State
Protocol
2 IOEX Control 41-00.00
3 State
Protocol
3 IOEX Control 41-00.00
4 State
Protocol
4 IOEX Control 41-00.00
5 State
Protocol
5 IOEX Control 41-00.00
6 State
Protocol
6 IOEX Control 41-00.00
7 State
Protocol
7 IOEX Control 41-00.00
8 State Virtual RTU points that are set/cleared Protocol IOEX Protocol IOEX
directly by there respective "Digital Control 'x' Control 'x' NOT
Protocol Control:Protocol IOEX Controls" point. asserted. asserted.
8 IOEX Control 44-28.00
9 State
Protocol
9 IOEX Control 44-28.00
10 State
Protocol
10 IOEX Control 44-28.00
11 State
Protocol
11 IOEX Control 44-28.00
12 State
Protocol
12 IOEX Control 44-28.00
13 State
Protocol
13 IOEX Control 44-28.00
14 State
Protocol
14 IOEX Control 44-28.00
15 State
Protocol
15 IOEX Control 44-28.00
16 State
Version
Point Name Description Min Max Unit(s) Resolution Deadband
Introduced
0 A-Phase Current 0 16000 Amps 0.1 10 41-00.00
A.2.2Voltage Measurements
Both Phase/(Earth/Ground) and Phase/Phase voltages are available (three phase switchgear only). Usually
the utility requires only one of these to be sent to the SCADA system.
Voltages are provided for all terminals with voltage measurement. The number of terminals with voltage
measurement varies depending on the model of switchgear, refer to the equipment manual. The phase
designation is assigned by the user. Refer to Switchgear Details section. The table below distinguishes
between the I and X sides of the switchgear, some models refer to the 1 and 2 sides (eg. A1, A2).
Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
Phase to Earth/Ground
Ai Phase to voltage for Phase A on
0 0 30000 Volts 1 100 41-00.00
Earth/Ground Volts the I side of the
switchgear measured.
Phase to Earth/Ground
Bi Phase to voltage for Phase B on
1 0 30000 Volts 1 100 41-00.00
Earth/Ground Volts the I side of the
switchgear measured.
Phase to Earth/Ground
Ci Phase to voltage for Phase C on
2 0 30000 Volts 1 100 41-00.00
Earth/Ground Volts the I side of the
switchgear measured.
Phase to Earth/Ground
Ax Phase to voltage for Phase A on
3 0 30000 Volts 1 100 41-00.00
Earth/Ground Volts the X side of the
switchgear measured.
Phase to Earth/Ground
Bx Phase to voltage for Phase B on
4 0 30000 Volts 1 100 41-00.00
Earth/Ground Volts the X side of the
switchgear measured.
Phase to Earth/Ground
Cx Phase to voltage for Phase C on
5 0 30000 Volts 1 100 41-00.00
Earth/Ground Volts the X side of the
switchgear measured.
Phase A to Phase B
6 ABi Phase to Phase voltage on the I side of 0 38000 Volts 1 100 41-00.00
the switchgear.
Phase B to Phase C
7 BCi Phase to Phase voltage on the I side of 0 38000 Volts 1 100 41-00.00
the switchgear
the switchgear
Phase A to Phase B
9 ABx Phase to Phase voltage on the X side of 0 38000 Volts 1 100 41-00.00
the switchgear. (1)
Phase B to Phase C
10 BCx Phase to Phase voltage on the X side of 0 38000 Volts 1 100 41-00.00
the switchgear. (1)
Phase C to Phase A
11 CAx Phase to Phase voltage on the X side of 0 38000 Volts 1 100 41-00.00
the switchgear. (1)
Phase to Earth/Ground
I Side Voltages-
voltage averave of 3
Phase to
12 phases on the I side of 0 30000 Volts 1 100 41-00.00
Earth/Ground-
the switchgear
Average of 3 phases
measured.
I Side Voltages- Phase to Phase A
13 Phase to Phase- voltage on the X side of 0 38000 Volts 1 100 42-00.60
Average of 3 phases the switchgear. (1)
1- If no Xside CVTs present then value will always be zero.
A.2.3System Power
Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
Total Real Power flowing
through the switchgear. This
can be a signed quantity
which indicates direction of
Real power flow, or an unsigned -
0 1900000 kW 1 250 41-00.00
Power-P quantity which is always 1900000
positive regardless of the
direction of the power flow.
This is determined by the
controller configuration.
Apparent
1 Apparent power. 0 1900000 kVA 1 250 41-00.00
Power-S
Total Reactive Power flowing
through the switchgear.
configuration.
Apparent Power flowing
through the C phase. This is
C Phase
an unsigned quantity which
13 Apparent 0 1900000 kVA 1 250 41-00.00
is always positive
Power-S
irrespective of direction of
power flow.
Reactive Power flowing
through the C phase. This is
C Phase
an unsigned quantity which -
14 Reactive 1900000 kVAR 1 250 41-00.00
is always positive 1900000
Power-Q
irrespective of direction of
power flow.
C Phase Power factor. This
is calculated from the Real
C Phase
and Apparent power.
15 Power 0 1 N/A 0.01 0.01 41-00.00
Factor
See Technical Manual for
accuracy specification.
Point 0 and 1 are the same measurement, just in different units. Normally only one is sent back to the
SCADA system.
The pressure is zeroed if switchgear data is invalid. Refer to Recloser and Controller State Flags section.
Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
-
0 Gas Pressure SI 300 kPa 1 5 41-00.00
SF6 gas 100
Gas Pressure pressure.
1 -14 44 PSI 0.1 1 41-00.00
Imperial
A.2.5Protection State
Refer also to Operator/Protection flags for switchgear
Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
Value is zero when Cold Load is Idle
or OFF. When Cold Load is not idle
this shows the Operational Cold
0 Cold Load Load Time, i.e. the current time 0 480 Mins 1 1 41-00.00
being used to calculate the
Operational Cold Load Threshold
Multiplier.
0 = Protection Group A
Protection
1 Group in 1 = Protection Group B 0 9 N/A 1 1 41-00.00
service.
n = Other Protection Group
0 = NPS Protection OFF
NPS
2 protection 1 = NPS Protection ON 0 2 N/A 1 1 41-00.00
status
2 = NPS Protection Alarm only
Value is zero when Cold Load is Idle
Other data recorded includes the number of trips in the protection sequence and the Protection Group(s) that
were active at the start of the protection sequence.
Protection Sequence and Trip Data is cleared to zero by the following actions :-
When new values are stored, the event time stamp is the time of the end of the sequence to 10ms
resolution.
Similarly when the values are cleared the event is time tagged to 10ms resolution. Thus the time stamps
correspond to the digital time stamps in Appendix A.1.3.
Version
Point Name Description Min Max Unit(s) Resolution Deadband
Introduced
A-Phase
0 0 16000 Amps 1 1 41-00.00
Current Trip-1 A Phase current at trip.
A-Phase Written on a Protection Trip 0 16000
1 Amps 1 1 41-00.00
Current Trip-2 after a pickup has occurred.
A-Phase Four values are provided:
2 one for each possible trip in 0 16000 Amps 1 1 41-00.00
Current Trip-3
A-Phase the sequence.(1)
3 0 16000 Amps 1 1 41-00.00
Current Trip-4
B-Phase
4 0 16000 Amps 1 1 41-00.00
Current Trip-1 B Phase current at trip.
B-Phase Written on a Protection Trip 0 16000
5 Amps 1 1 41-00.00
Current Trip-2 after a pickup has occurred.
B-Phase Four values are provided:
6 one for each possible trip in 0 16000 Amps 1 1 41-00.00
Current Trip-3
B-Phase the sequence.(1)
7 0 16000 Amps 1 1 41-00.00
Current Trip-4
C-Phase
8 0 16000 Amps 1 1 41-00.00
Current Trip-1
C-Phase C Phase current at trip.
9 Written on a Protection Trip 0 16000 Amps 1 1 41-00.00
Current Trip-2
after a pickup has occurred.
10 C-Phase Four values are provided: 0 16000 Amps 1 1 41-00.00
0: No fault
1: A-E
2: B-E
3: C-E
4: A-B
Fault Phase(s) 5: A-C
37 0 11 N/A 1 1 45-06.02
Trip 1 6: B-C
7: A-B-E
8: A-C-E
9: B-C-E
10: A-B-C
11: A-B-C-E
0: No fault
1: A-E
2: B-E
3: C-E
4: A-B
Fault Phase(s) 5: A-C
40 0 11 N/A 1 1 45-06.02
Trip 2 6: B-C
7: A-B-E
8: A-C-E
9: B-C-E
10: A-B-C
11: A-B-C-E
0: No fault
1: A-E
2: B-E
3: C-E
4: A-B
Fault Phase(s) 5: A-C
43 0 11 N/A 1 1 45-06.02
Trip 3 6: B-C
7: A-B-E
8: A-C-E
9: B-C-E
10: A-B-C
11: A-B-C-E
0: No fault
1: A-E
2: B-E
Fault Phase(s) 3: C-E
46 4: A-B 0 11 N/A 1 1 45-06.02
Trip 4
5: A-C
6: B-C
7: A-B-E
8: A-C-E
9: B-C-E
10: A-B-C
11: A-B-C-E
1- Note: The phase designation A, B, C is determined by the user, refer to Switchgear Details section and
the Switchgear Technical Manual.
2- Note: Only valid when the respective protection element is 'Enabled' (Earth/Ground, NPS etc) and the
element current was greater than the "Zero Amps Indicated" threshold during the pickup.
3- Note: Only valid when Directional Protection is ENABLED.
A.2.7Switchgear Details
This is switchgear configuration data held in the switchgear memory or Controller.
Version
Point Name Description Min Max Unit(s) Resolution Deadband
Introduced
The serial number of
Switch Serial the switchgear.
0 0 2147483647 N/A 1 1 41-00.00
Number Requires full 32 bits
for this to work.
I Contact
1 0 100 % 0.01 1 41-00.00
Life The percentage of
II Contact vacuum interrupter
2 0 100 % 0.01 1 41-00.00
Life life remaining for
III Contact each phase.
3 0 100 % 0.01 1 41-00.00
Life
The count of the
Operations number of closes
4 0 65535 Operations 1 1 41-00.00
Counter performed by the
switchgear.
The low 4 decimal
digits of the serial
Switch Serial
number of the
6 Number [0- 0 9999 N/A 1 1 41-00.00
switchgear. Requires
9999]
16 bits for this to
work.
The high decimal
digits of the serial
Switch Serial
number of the
7 Number 0 65535 N/A 1 1 41-00.00
switchgear. Requires
[10000+]
16 bits for this to
work.
A.2.8Controller Data
Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
Battery The controller battery
0 0 32 Volts 0.01 1 41-00.00
Voltage voltage.
ADVC Serial The Controller serial
2 0 2147483647 N/A 1 1 41-00.00
Number number.
The code version is a six-
digit number that has the
Code
3 form yy-xx.xx with the dash 0 100000000 N/A 1 1 41-00.00
Version
and point formatting
removed.
Battery Status 0=Battery
Battery Overvolts, 1=Battery
A.2.9Distributed Automation
Refer also to Distributed Automation Flags.
This point is only valid when the loop automation option is enabled for the current configuration and is
otherwise always repeated as zero.
Version
Point Name Description Min Max Unit(s) Resolution Deadband
Introduced
This is the Loop Automation
timeout value while counting
LA Remaining down prior to a Trip or Close
0 0 1800 Seconds 1 10 41-00.00
Time action occurring. When no
action is pending the value is
zero.
Auto-Changeover Status.
Auto-
Refer to Auto-Changeover
1 Changeover 0 32767 N/A 1 1 44-36.00
Technical Manual for more
Status
info
Auto-Changeover Algorithm.
Auto-
0: One Way, 1: Make Before
3 Changeover 0 3 N/A 1 1 44-36.00
Break, 2: Break Before
Algorithm
Make, 3: Both Ways.
A.2.10Daily Data
Daily data is updated at midnight, but only when collected over a full 24-hour period.
Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
This is the maximum current
Maximum
average of all phases for the
0 Average 0 16000 Amps 0.1 1 41-00.00
previous full day ending at
Current
midnight (2sec filter window).
This is the end time of the
Time of maximum average demand
Maximum current of all relevant phases for
2 0 1439 Mins 1 1 41-00.00
Average the previous full day ending at
Current midnight. The time is in minutes
since midnight.
This is the maximum average
demand current of all relevant
Maximum
phases for the previous full day
Average
3 ending at midnight. Same as 0 16000 Amps 1 10 41-00.00
Demand
'MDI-Previous Day' except that it
Current
is reset on assertion of 'Reset
Maximum Demand Indicators'
Version
Point Name Description Min Max Unit(s)
Introduced
Source The number of supply outages on the source
0 0 2147483647 N/A 41-00.00
Outages terminals.(1) (2)
Source
The total duration of supply outages on the
1 Outages 0 2147483647 Seconds 41-00.00
source terminals, in seconds.(1) (2)
Duration
Load The number of supply outages on the load
2 0 2147483647 N/A 41-00.00
Outages terminals.(1) (2)
Load
The total duration of supply outages on the
3 Outages 0 2147483647 Seconds 41-00.00
load terminals, in seconds.(1) (2)
Duration
The count of the number of voltage Sags
4 Sag Count recorded since the last reset. A reset is done 0 2147483647 N/A 42-00.00
from the OCP or WSOS only!
The count of the number of voltage Swells
5 Swell Count recorded since the last reset. A reset is done 0 2147483647 N/A 42-00.00
from the OCP or WSOS only!
The accumulated time of all Sags since the
6 Sag Duration last reset. A reset is done from the OCP or 0 2147483647 Seconds 42-00.00
WSOS only.
The accumulated time of all Swells since the
Swell
7 last reset. A reset is done from the OCP or 0 2147483647 Seconds 42-00.00
Duration
WSOS only.
1- Power flow direction (source/load designation) is determined by the user. Refer to Recloser and
Controller State Flags section, Power Flow Direction for status and section B, Power Flow Direction for
control.
2- Data active only when Power Quality option Supply Outage Measurement is Available and ON.
A.2.12Frequency Measurement
Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
The measured Frequency. Returns
0 Frequency 0 65 Hz 0.1 1 41-00.00
a value of 0 for unavailable
A.2.15Sequence Components
Zero, Positive and Negative Phase Sequence currents and voltages, valid when controller is configured
"Sequence Componets Available.
Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
ZPS The zero phase sequence
0 0 16000 Amps 0.1 10 41-00.00
Current current.
PPS The positive phase sequence
1 0 16000 Amps 0.1 10 41-00.00
Current current.
NPS The negative phase
2 0 16000 Amps 0.1 10 41-00.00
Current sequence current.
ZPS The zero phase sequence
3 0 30000 Volts 1 10 41-00.00
Voltage voltage.
PPS The positive phase sequence
4 0 30000 Volts 1 10 41-00.00
Voltage voltage.
NPS The negative phase
5 0 30000 Volts 1 10 41-00.00
Voltage sequence voltager.
A.3.1Trip Counters
These counters do not increment when switchgear is an LBS. These counters are cleared by the following:
When the counters reach their max value, the next count will cause one of two actions; if the feature
"Counters Rollover ON" has been selected, then the counters rollover to one (1), else they 'stick' at the 'Max'
value, which is the default option.
If a counter does wrap around then it can wrap out of sync with the other counters. Note that combinational
counters may also wrap independantly of what points they are made up of. Counters should be used as
independent values because of this.
Unit Version
Point Name Description Min Max
(s) Introduced
A Phase O/C Trip The number of trips caused by an A Phase
0 0 99 N/A 41-00.00
Counter over current.
B Phase O/C Trip The number of trips caused by a B Phase
1 0 99 N/A 41-00.00
Counter over current.
C Phase O/C Trip The number of trips caused by a C Phase
2 0 99 N/A 41-00.00
Counter over current.
Earth/Ground O/C TripThe number of trips caused by a
3 0 99 N/A 41-00.00
Counter Earth/Ground Phase over current.
SEF/SGF O/C Trip The number of trips caused by a SEF/SGF
4 0 99 N/A 41-00.00
Counter Phase over current.
Loss Of Phase Trip The number of trips caused by a Loss Of
5 0 99 N/A 41-00.00
Counter Phase
The number of trips caused by an Under or
6 FRQ Trip Counter. 0 99 N/A 41-00.00
Over Frequency(2)
The number of trips caused by a NPS over
7 NPS O/C Trip Counter 0 99 N/A 41-00.00
current.
The number of trips caused by an External
8 Ext Trip Counter input (either a FTI or an IOEX Protection 0 99 N/A 41-00.00
Input).
A Phase O/C Reverse The number of reverse trips caused by an A
9 0 99 N/A 41-00.00
Trip Counter Phase over current.
B Phase O/C Reverse The number of reverse trips caused by a B
10 0 99 N/A 41-00.00
Trip Counter Phase over current.
C Phase O/C Reverse The number of reverse trips caused by a C
11 0 99 N/A 41-00.00
Trip Counter Phase over current.
Earth/Ground O/C The number of reverse trips caused by a
12 0 99 N/A 41-00.00
Reverse Trip Counter Earth/Ground Phase over current.
SEF/SGF O/C Reverse The number of reverse trips caused by a
13 0 99 N/A 41-00.00
Trip Counter SEF/SGF Phase over current.
NPS O/C Reverse Trip The number of trips caused by a reverse
14 0 99 N/A 41-00.00
Counter NPS over current.
A.3.2Pickup Counters
These counters are for ACR and LBS. They are cleared by the following:
When the counters reach their max value, the next count will cause one of two actions; if the feature
"Counters Rollover ON" has been selected, then the counters rollover to one (1), else they 'stick' at the 'Max'
value, which is the default option.
If a counter does wrap around then it can wrap out of sync with the other counters. Note that combinational
counters may also wrap independantly of what points they are made up of. Counters should be used as
independent values because of this.
Unit Version
Point Name Description Min Max
(s) Introduced
A Phase O/C The number of Pickups caused by an A Phase over
0 0 99 N/A 41-00.00
Pickup Counter current.
B Phase O/C The number of Pickups caused by a B Phase over
1 0 99 N/A 41-00.00
Pickup Counter current.
C Phase O/C The number of Pickups caused by a C Phase over
2 0 99 N/A 41-00.00
Pickup Counter current.
Earth/Ground O/C The number of Pickups caused by an Earth/Ground
3 0 99 N/A 41-00.00
Pickup Counter Phase over current.
SEF/SGF O/C The number of Pickups caused by a SEF/SGF Phase
4 0 99 N/A 41-00.00
Pickup Counter over current.
The number of Loss Of Phase Indications. (this is
Loss Of Phase
5 used to check for Loss Of Phase conditions when 0 99 N/A 41-00.00
Indication Counter
protection is OFF)
6 FRQ Pickup The number of pickups caused by an Under or Over 0 99 N/A 41-00.00
Counter. Frequency.(1)
The number of Pickups caused by a (Fwd) phase
Phase overcurrent. NOTE: Two or more phases picked up at
7 Overcurrent the same time count as one phase overcurrent pickup. 0 99 N/A 41-00.00
Pickup Counter This means the sum of the individual A/B/C phase
pickup counters may be greater than this counter.
NPS O/C Pickup The number of Pickups caused by a NPS over
8 0 99 N/A 41-00.00
Counter current.
A Phase Reverse
The number of Pickups caused by an A Phase
9 O/C Pickup 0 99 N/A 41-00.00
reverse over current.
Counter
B Phase Reverse
The number of Pickups caused by a B Phase reverse
10 O/C Pickup 0 99 N/A 41-00.00
over current.
Counter
C Phase Reverse
The number of Pickups caused by a C Phase reverse
11 O/C Pickup 0 99 N/A 41-00.00
over current.
Counter
Earth/Ground
The number of Pickups caused by an Earth/Ground
12 Reverse O/C 0 99 N/A 41-00.00
reverse over current.
Pickup Counter
SEF/SGF
The number of Pickups caused by a SEF/SGF
13 Reverse O/C 0 99 N/A 41-00.00
reverse over current.
Pickup Counter
The number of Pickups caused by a reverse phase
Reverse Phase overcurrent. NOTE: Two or more phases picked up at
14 Overcurrent the same time count as one phase overcurrent pickup. 0 99 N/A 41-00.00
Pickup Counter This means the sum of the individual A/B/C phase
pickup counters may be greater than this counter.
Reverse NPS O/C The number of Pickups caused by a reverse NPS
15 0 99 N/A 41-00.00
Pickup Counter over current.
Under Voltage The count of the number of Pickups caused by Under
16 0 99 N/A 42-00.00
Pickup Counter Voltage since the last reset.
Over Voltage The count of the number of Pickups caused by Over
17 0 99 N/A 42-00.00
Pickup Counter Voltage since the last reset.
The sum of all Pickups caused by all (Fwd) phase
Sum All Phase overcurrent. NOTE: Two or more phases picked up at
18 O/C Pickup the same time count as multiple phase overcurrent 0 99 N/A 44-36.76
Counter pickups. This means the sum of the individual A/B/C
phase pickup counters equals this counter.
The sum of all Pickups caused by all reverse phase
Sum All Rev overcurrent. NOTE: Two or more phases picked up at
19 Phase O/C the same time count as multiple phase overcurrent 0 99 N/A 44-36.76
Pickup Counter pickups. This means the sum of the individual A/B/C
phase pickup counters equals this counter.
The number of Pickups caused by forward and
reverse phase overcurrent. NOTE: Two or more
Phase O/C Both
phases picked up at the same time count as one
20 Dir Pickup 0 99 N/A 44-36.76
phase overcurrent pickup. This means the sum of the
Counter
individual A/B/C phase pickup counters may be
greater than this counter.
Earth/Ground O/C
The number of Pickups caused by an Earth/Ground
21 Both Dir Pickup 0 99 N/A 44-36.76
forward and reverse over current.
Counter
SEF/SGF O/C
The number of Pickups caused by a SEF/SGF
22 Both Dir Pickup 0 99 N/A 44-36.76
forward and reverse over current.
Counter
NPS O/C Both Dir The number of Pickups caused by a forward and
23 0 99 N/A 44-36.76
Pickup Counter reverse NPS over current.
Under and Over The count of the number of Pickups caused by Under
24 0 99 N/A 44-36.76
Voltage Pickup Voltage since the last reset.
Counter
A.3.3Fault Counters
These counters are only valid when the connected switchgear is operated in LBS mode. They are cleared by
the following:
When the counters reach their max value, the next count will cause one of two actions; if the feature
"Counters Rollover ON" has been selected, then the counters rollover to one (1), else they 'stick' at the 'Max'
value, which is the default option.
If a counter does wrap around then it can wrap out of sync with the other counters. Note that combinational
counters may also wrap independantly of what points they are made up of. Counters should be used as
independent values because of this.
Unit Version
Point Name Description Min Max
(s) Introduced
A Phase O/C The number of Faults caused by an A Phase over
0 0 99 N/A 41-00.00
Fault Counter current.
B Phase O/C The number of Faults caused by a B Phase over
1 0 99 N/A 41-00.00
Fault Counter current.
C Phase O/C The number of Faults caused by a C Phase over
2 0 99 N/A 41-00.00
Fault Counter current.
Earth/Ground O/C The number of Faults caused by a Earth/Ground
3 0 99 N/A 41-00.00
Fault Counter Phase over current.
SEF/SGF O/C The number of Faults caused by a SEF/SGF Phase
4 0 99 N/A 41-00.00
Fault Counter over current.
The number of Faults caused by any Phase over
Phase O/C Fault current. NOTE: if two or more phase faults occur at
5 0 99 N/A 41-00.00
Counter the same time, only the first phase fault will cause a
count.
NPS O/C Fault The number of Faults caused by a NPS Phase over
7 0 99 N/A 43-00.00
Counter current.
It may seem strange that points that do similar things on an ACR and LBS have been mapped twice.
However, experience has shown that the small differences in behaviour of the points have caused much
confusion both in the code and scada system in previous products. The cost to both the customer and
supplier is more than to maintain the points separately.
Version
Point Name Description Set = '1' Clear = '0'
Introduced
Detection
This group of points indicates what happened in the most recent fault detection. Unlike the ACR, these flags
don't attempt to reconstruct a fault sequence. The flags are not cumulative, they are cleared as each new
fault is detected. For example, if there is an earth fault followed by a phase fault, the earth fault flag will be
cleared when the phase fault flag is set.
In addition analogue data is available which shows the fault currents refer to Protection Sequence and Trip
Data Section A.2.6.
Most of these flags are cleared either by protocol command or when the switchgear is tripped/closed by the
operator or when a new fault is detected.
If more than one protocol is running simultaneously in the controller, this data is replicated between the
protocols so that each master station can clear its data independently from the others.
This table is not valid for ACR, see 1 for ACR equivalent.
Version
Point Name Description Set = '1' Clear = '0'
Introduced
This shows that a
Start of sequence. A SectionaliserTrip
Sequence in protection sequence
0 detection trip or sequence 43-00.12
Progress has started and not
advance has occurred. Sequence Reset
yet completed.
A Phase
1 Overcurrent A Phase Overcurrent Fault 43-00.12
Fault
B Phase Cleared by
2 Overcurrent B Phase Overcurrent Fault 43-00.12
Fault These flags show Operator trip.
C Phase which elements were Any close.
3 Overcurrent picked up at the time C Phase Overcurrent Fault Reset Flags' 43-00.12
Fault of the most recent Protocol
Earth/Ground fault. Command.
Earth/Ground Overcurrent
4 Overcurrent 43-00.12
Fault
Fault
SEF/SGF
SEF/SGF Overcurrent
5 Overcurrent 43-00.12
Fault
Fault
Cleared by
Operator trip.
Any close.
Sequence
Supply
6 Supply Interrupt. Supply Interrupt Reset. 43-00.12
Interrupt
'Reset Flags'
Protocol
Command.
Cleared by
Operator trip.
Any close.
Sectionaliser
7 Sectionaliser Trip. Sectionaliser Trip 'Reset Flags' 43-00.12
Trip
Protocol
Command.
'Reset Flags
and Currents'
protocol
Set if the most recent close
Live Load command
20 request was blocked due to 43-00.12
Block Occurred Controller
a Live Load condition
Software Reset
(data is volatile)
At the time of
the next Close
A Phase OC
Overcurrent Fault on Phase
22 Fault Non- 43-00.12
A
Latching
B Phase OC
Overcurrent Fault on Phase
23 Fault Non- Cleared by 43-00.12
B
Latching
C Phase OC These flags show Operator trip.
Overcurrent Fault on Phase
24 Fault Non- which elements have Any close. 43-00.12
C
Latching a fault. Reset Flags'
Earth/Ground Protocol
Overcurrent Fault on Command.
25 OC Fault Non- 43-00.12
Earth/Ground Fault current
Latching
Phase OC
Overcurrent Fault on A, B
27 Fault Non- 43-00.12
or C Phase
Latching
NPS Fault
28 Overcurrent Fault on NPS 43-00.22
Non-Latching
Cleared by
"Reset Fault
Flags and
This flags that a NPS Currents"
A NPS fault has been
30 NPS Alarm fault has been control. 43-00.31
picked up.
picked up. "Reset Fault
Flags" control.
Controller
software reset
(data is volatile).
A.6.1Detection State
Refer also to Operator/Protection Flags for LBS section.
Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
Value is zero when Cold Load is
Idle or OFF. When Cold Load is not
idle this shows the operational cold
0 Cold Load 0 480 Mins 1 1 43-00.00
load time, i.e. the current time being
used to calculate the operational
cold load threshold multiplier.
Detection
0 = Detection Group A 1 =
Group
1 Detection Group B n = Other 0 9 N/A 1 1 43-00.00
currently
Detection Group
selected
0 = NPS Detection OFF
NPS
2 detection 1 = NPS Detection ON 0 2 N/A 1 1 43-00.31
status
2 = NPS Detection Alarm only
For any one fault more than one fault current can be set. For example a Phase/Phase fault might set an A-
Phase current and a B-Phase current.
Other data recorded includes the supply interrupt count and the Detection Group that was active at the start
of the fault detection sequence.
"Reset Fault Flags and Currents" remote control command defined below.
Any Operator Close or Trip action.
New fault detected.
The time stamps correspond to the digital time stamps in Detection Flags LBS section.
If more than one protocol is running simultaneously in the controller, this data is replicated between the
protocols so that each master station can clear its data independently from the others.
Version
Point Name Description Min Max Unit(s) Resolution Deadband
Introduced
The number of the
Active Detection Detection Group which
0 0 9 N/A 1 1 43-00.00
Group was active at the start of
the sequence.
Supply Interrupt The number of Supply
1 0 10 N/A 1 1 43-00.00
Count Interrupts Counted.
Most Recent A- Written on a Max Current
2 0 16000 Amps 1 1 43-00.00
Phase Fault event for A Phase(1)
Most Recent B- Written on a Max Current
3 0 16000 Amps 1 1 43-00.00
Phase Fault event for B Phase(1)
Most Recent C- Written on a Max Current
4 0 16000 Amps 1 1 43-00.00
Phase Fault event for C Phase(1)
Earth/Ground Fault
Most Recent
Current-Written on an E-
5 Earth/Ground 0 16000 Amps 1 1 43-00.00
Max event. This includes
Fault
SEF/SGF Fault currents.
NPS Fault Current-
Most Recent
6 Written on an E-Max 0 16000 Amps 1 1 43-00.22
NPS Fault
event.
Fault distance from the
Fault Distance 10
7 controller (10 Metres) - -1 30000 1 1 45-06.02
Trip 1 Metres
Trip 1
0: No fault
1: A-E
2: B-E
3: C-E
4: A-B
Fault Phase(s) 5: A-C
9 0 11 N/A 1 1 45-06.02
Trip 1 6: B-C
7: A-B-E
8: A-C-E
9: B-C-E
10: A-B-C
11: A-B-C-E
0: No fault
1: A-E
2: B-E
3: C-E
4: A-B
Fault Phase(s) 5: A-C
12 0 11 N/A 1 1 45-06.02
Trip 2 6: B-C
7: A-B-E
8: A-C-E
9: B-C-E
10: A-B-C
11: A-B-C-E
0: No fault
1: A-E
2: B-E
Fault Phase(s) 3: C-E
15 0 11 N/A 1 1 45-06.02
Trip 3 4: A-B
5: A-C
6: B-C
7: A-B-E
8: A-C-E
9: B-C-E
10: A-B-C
11: A-B-C-E
0: No fault
1: A-E
2: B-E
3: C-E
4: A-B
Fault Phase(s) 5: A-C
18 0 11 N/A 1 1 45-06.02
Trip 4 6: B-C
7: A-B-E
8: A-C-E
9: B-C-E
10: A-B-C
11: A-B-C-E
1- The phase designation A, B, C is determined by the user, refer to Switchgear Details section and the
Switchgear Technical Manual.
Version
Point Name Description Set = '1' Clear = '0'
Introduced
The alarm is ON. The The alarm is OFF. No
Phase current high current on at least one phase currents have
DNP3 Alarm-
alarm, for DNP3 phase has risen above reached the high
1 Phase Current 44-31.00
only (this point is the high threshold and threshold yet, or they
High.
obsolete). has not been below the have gone below the
90% threshold since. 90% threshold since.
The alarm is ON. The The alarm is OFF. No
The phase current current on at least one phase currents have
DNP3 Alarm-
low alarm, for phase has gone below gone below the low
2 Phase Current 44-31.00
DNP3 only (this the low threshold and threshold yet, or they
Low.
point is obsolete). has not risen above the have risen above the
10% threshold since. 10% threshold since.
The alarm is ON. The The alarm is OFF. No
The phase voltage voltage on at least one phase voltages have
DNP3 Alarm-
high alarm, for phase has risen above reached the high
3 Phase Voltage 44-31.00
DNP3 only (this the high threshold and threshold yet, or they
High.
point is obsolete). has not been below the have gone below the
90% threshold since. 90% threshold since.
The alarm is ON. The The alarm is OFF. No
Phase voltage low voltage on at least one phase voltages have
DNP3 Alarm-
alarm, for DNP3 phase has gone below gone below the low
4 Phase Voltage 44-31.00
only (this point is the low threshold and threshold yet, or they
Low.
obsolete). has not risen above the have risen above the
10% threshold since. 10% threshold since.
These points are volatile and always reset on a power cycle irrespective of the feature "Counters Non-
Volatile ON".
Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
Transmitted frame
0 DNP3 TX Count 0 32768 N/A 41-00.00
count.
Received frame
1 DNP3 RX Count 0 32768 N/A 41-00.00
count.
DNP3 RX Length Received message
2 0 32768 N/A 41-00.00
Error length error.
Received message
3 DNP3 RX CRC Error 0 32768 N/A 41-00.00
CRC error.
DNP3 Master The DNP Master
4 0 65519 N/A 1 1 41-00.00
Address station address.
DNP3 Controller The DNP address of
5 0 65519 N/A 1 1 41-00.00
Address the controller.
DNP3 RX Error Received message
6 0 32768 N/A 41-00.00
Count error count.
7 MITS TX Count MITS Transmitted 0 4095 N/A 42-00.18
frame count.
MITS Received frame
8 MITS RX Count 0 4095 N/A 42-00.18
count.
MITS Received
9 MITS RX CRC Error 0 4095 N/A 42-00.18
message CRC error.
IEC 101/104 TX Transmitted frame
10 0 32768 N/A 42-00.00
Count count.
IEC 101/104 RX Received frame
11 0 32768 N/A 42-00.00
Count count.
IEC 101/104 RX Received message
12 0 32768 N/A 42-00.00
CRC Error CRC error.
IEC 101/104 RX Received message
13 0 32768 N/A 42-00.00
SYNC Error CRC error.
IEC 101/104 RX
Received message
14 Frame Time Out 0 32768 N/A 42-00.00
CRC error.
Error
Transmitted frame
15 MODBUS TX Count 0 99999 N/A 44-14.00
count.
Received frame
16 MODBUS RX Count 0 99999 N/A 44-14.00
count.
MODBUS RX Length Received message
17 0 99999 N/A 44-14.00
Error length error.
MODBUS RX CRC Received message
18 0 99999 N/A 44-14.00
Error CRC error.
Unit Version
Point Name Description Min Max
(s) Introduced
Accumulated KWh.
DNP3 KWh
0 0 2147483647 KWh 41-00.00
Cumulative Counter can be read, frozen, frozen
read, and reset.
Accumulated KWh in the forward
direction (ie Source to Load).
DNP3 KWh
1 0 2147483647 KWh 41-00.00
Cumulative Forward
Counter can be read, frozen, frozen
read, and reset.
Accumulated KWh in the reverse
direction (ie Load to Source).
DNP3 KWh
2 0 2147483647 KWh 41-00.00
Cumulative Reverse
Counter can be read, frozen, frozen
read, and reset.
Variable 03 2147483648
Custom -
3 2147483647 1 45-03.00
Variable 04 2147483648
Custom -
4 2147483647 1 45-03.00
Variable 05 2147483648
Custom -
5 2147483647 1 45-03.00
Variable 06 2147483648
Custom -
6 2147483647 1 45-03.00
Variable 07 2147483648
Custom -
7 2147483647 1 45-03.00
Variable 08 2147483648
Custom -
8 2147483647 1 45-03.00
Variable 09 2147483648
Custom -
9 2147483647 1 45-03.00
Variable 10 2147483648
Custom -
10 2147483647 1 45-03.00
Variable 11 2147483648
Custom -
11 2147483647 1 45-03.00
Variable 12 2147483648
Custom -
12 2147483647 1 45-03.00
Variable 13 2147483648
Custom -
13 2147483647 1 45-03.00
Variable 14 2147483648
Custom -
14 2147483647 1 45-03.00
Variable 15 2147483648
Custom -
15 2147483647 1 45-03.00
Variable 16 2147483648
Custom -
16 2147483647 1 45-03.00
Variable 17 2147483648
Custom -
17 2147483647 1 45-03.00
Variable 18 2147483648
Custom -
18 2147483647 1 45-03.00
Variable 19 2147483648
Custom -
19 2147483647 1 45-03.00
Variable 20 2147483648
Custom -
20 2147483647 1 45-03.00
Variable 21 2147483648
Custom -
21 2147483647 1 45-03.00
Variable 22 2147483648
Custom -
22 2147483647 1 45-03.00
Variable 23 2147483648
Custom -
23 2147483647 1 45-03.00
Variable 24 2147483648
Custom -
24 2147483647 1 45-03.00
Variable 25 2147483648
Custom -
25 2147483647 1 45-03.00
Variable 26 2147483648
Custom -
26 2147483647 1 45-03.00
Variable 27 2147483648
Custom -
27 2147483647 1 45-03.00
Variable 28 2147483648
Custom -
28 2147483647 1 45-03.00
Variable 29 2147483648
Custom -
29 2147483647 1 45-03.00
Variable 30 2147483648
Custom -
30 2147483647 1 45-03.00
Variable 31 2147483648
Custom -
A.8.2Custom Counters
Point Name Description Min Max Unit(s) Version Introduced
0 Custom Counter 01 0 2147483647 45-03.00
1 Custom Counter 02 0 2147483647 45-03.00
2 Custom Counter 03 0 2147483647 45-03.00
3 Custom Counter 04 0 2147483647 45-03.00
4 Custom Counter 05 0 2147483647 45-03.00
5 Custom Counter 06 0 2147483647 45-03.00
6 Custom Counter 07 0 2147483647 45-03.00
7 Custom Counter 08 0 2147483647 45-03.00
8 Custom Counter 09 0 2147483647 45-03.00
9 Custom Counter 10 0 2147483647 45-03.00
10 Custom Counter 11 0 2147483647 45-03.00
11 Custom Counter 12 0 2147483647 45-03.00
12 Custom Counter 13 0 2147483647 45-03.00
13 Custom Counter 14 0 2147483647 45-03.00
14 Custom Counter 15 0 2147483647 45-03.00
15 Custom Counter 16 0 2147483647 45-03.00
16 Custom Counter 17 0 2147483647 45-03.00
17 Custom Counter 18 0 2147483647 45-03.00
18 Custom Counter 19 0 2147483647 45-03.00
19 Custom Counter 20 0 2147483647 45-03.00
20 Custom Counter 21 0 2147483647 45-03.00
21 Custom Counter 22 0 2147483647 45-03.00
22 Custom Counter 23 0 2147483647 45-03.00
23 Custom Counter 24 0 2147483647 45-03.00
24 Custom Counter 25 0 2147483647 45-03.00
25 Custom Counter 26 0 2147483647 45-03.00
26 Custom Counter 27 0 2147483647 45-03.00
27 Custom Counter 28 0 2147483647 45-03.00
28 Custom Counter 29 0 2147483647 45-03.00
29 Custom Counter 30 0 2147483647 45-03.00
30 Custom Counter 31 0 2147483647 45-03.00
31 Custom Counter 32 0 2147483647 45-03.00
A.8.3Custom Timers
Unit Version
Point Name Description Min Max Resolution Deadband
(s) Introduced
Custom -
0 2147483647 1 45-03.00
Timer 01 2147483648
Custom -
1 2147483647 1 45-03.00
Timer 02 2147483648
Custom -
2 2147483647 1 45-03.00
Timer 03 2147483648
Custom -
3 2147483647 1 45-03.00
Timer 04 2147483648
Custom -
4 2147483647 1 45-03.00
Timer 05 2147483648
Custom -
5 2147483647 1 45-03.00
Timer 06 2147483648
Custom -
6 2147483647 1 45-03.00
Timer 07 2147483648
Custom -
7 2147483647 1 45-03.00
Timer 08 2147483648
Custom -
8 2147483647 1 45-03.00
Timer 09 2147483648
Custom -
9 2147483647 1 45-03.00
Timer 10 2147483648
Custom -
10 2147483647 1 45-03.00
Timer 11 2147483648
Custom -
11 2147483647 1 45-03.00
Timer 12 2147483648
Custom -
12 2147483647 1 45-03.00
Timer 13 2147483648
Custom -
13 2147483647 1 45-03.00
Timer 14 2147483648
Custom -
14 2147483647 1 45-03.00
Timer 15 2147483648
Custom -
15 2147483647 1 45-03.00
Timer 16 2147483648
Custom -
16 2147483647 1 45-03.00
Timer 17 2147483648
Custom -
17 2147483647 1 45-03.00
Timer 18 2147483648
Custom -
18 2147483647 1 45-03.00
Timer 19 2147483648
Custom -
19 2147483647 1 45-03.00
Timer 20 2147483648
Custom -
20 2147483647 1 45-03.00
Timer 21 2147483648
Custom -
21 2147483647 1 45-03.00
Timer 22 2147483648
Custom -
22 2147483647 1 45-03.00
Timer 23 2147483648
Custom -
23 2147483647 1 45-03.00
Timer 24 2147483648
Custom -
24 2147483647 1 45-03.00
Timer 25 2147483648
Custom -
25 2147483647 1 45-03.00
Timer 26 2147483648
Custom -
26 2147483647 1 45-03.00
Timer 27 2147483648
Custom -
27 2147483647 1 45-03.00
Timer 28 2147483648
Custom -
28 2147483647 1 45-03.00
Timer 29 2147483648
Custom -
29 2147483647 1 45-03.00
Timer 30 2147483648
Custom -
30 2147483647 1 45-03.00
Timer 31 2147483648
Custom -
31 2147483647 1 45-03.00
Timer 32 2147483648
A.8.4Custom Digitals
Logic functions can be created for the custom logic points.
Version
The same controls which an operator can use on the first system status screen of the Operator Control
Panel of the controller
Additional controls specific to the protocol such as "reset fault flags and currents".
Changes to protection are made by selecting a different active Protection Group in the same way an operator
makes changes.
Changes to a selection of protection features are provided for operational purposes. Changes to the main
configuration parameters of the protection are not permitted over the protocol. This is done either at the
control panel itself or by using the WSOS program that is specifically designed for the task.
Version
Point Name Description Set = '1' Clear = '0'
Introduced
Applies Work Tag.
Removes Work Tag.
Work tag can only
Rejected if:
be applied locally if
controller is in local
Work tag can only be
Applies/Removes mode, or remotely if
0 Work Tag removed locally if 41-00.00
the Work Tag controller is in
controller is in local
remote mode. Work
mode, or remotely if
tag is rejected if
controller is in remote
controller is closed
mode.
and it is not able to
trip.
Earth/Ground
Protection/Detection OFF
Earth/Ground and SEF/SGF
Protection/Detection Protection/Detection
Turn Earth/Ground ON. Rejected if: OFF. Rejected if:
Earth/Ground Fault Fault
1 41-00.00
Protection/Detection Protection/Detection Single phase Earth/ground fault
ON or OFF. measurement. OFF is not allowed.
Single phase
measurement.
SEF/SGF
Protection/Detection
ON and
Earth/Ground
Protection/Detection
ON. Rejected if:
Turn Sensitive
SEF/SGF
SEF/SGF Earth/Ground SEF/SGF is
2 Protection/Detection 41-00.00
Protection/Detection Protection/Detection not available.
OFF.
ON or OFF. Single phase
measurement.
Close or Trip
coil is isolated.
Controller
mode is
opposite to
location of
requester (i.e.
local/remote).
SF6 Gas Trip. Rejected if:
Pressure Low
(if applicable) Trip coil is isolated.
AND Gas Low Switchgear Data
Inhibit is ON. Invalid.
Work Tag is ACR AND SF6 gas
applied. pressure is low (if
Switchgear applicable) AND
Data Invalid. Gas Low Inhibit is
Operate the
Mechanically ON.
4 ACR/LBS Control recloser/load break 41-00.00
interlocked (if LBS AND SF6 gas
switch
applicable). pressure is low (if
Live load applicable).
blocking ON Mechanically
AND any load interlocked.
side terminal Trip capacitor is
live. charging or failed.
Trip and/or Hit and Run ON.
Close
capacitors are
charging or
failed.
Generator
Control has
close blocking
ON.
Hit and Run
ON.
Turn ALL
Protection/Detection
OFF. Rejected if:
Enable or disable all
Protection/Detection Enable
6 protection/detection 41-00.00
Control Protection/Detection Protection/Detection
functions.
OFF is not allowed.
Changes the
Source/Load
Power Flow
7 designation for the Source X, Load I Source I, Load X 41-00.00
Direction
recloser. See Note
(1).
Sets the operational
cold load time to
either zero or to the
maximum Sets Cold Load
configured value Time to its maximum
(including the value. This means
Sets cold load time to
reverse protection the Cold Load
zero. This means the
group if configured). Threshold Current
Threshold Multiplier will
This affects the will be set to its
not be affected by the
Operational Cold maximum value.
Cold Load function.
Load Threshold Rejected if:
Rejected if:
Multiplier. Rejected
11 Cold Load Idle/Max 41-00.00
if Cold Load is Cold load
Cold load support is
configured to OFF support is
OFF.
in the currently OFF.
Cold load is below
active protection Cold load is
the IDLE threshold.
group. After a new above the
time is set, the Cold IDLE
Load function will threshold.
immediately start to
increment or
decrement the
value depending on
the load current.
High Current
Lockout ON.
Controls the High Rejected if:
High Current High Current Lockout
12 Current Lockout 41-00.00
Lockout OFF.
Function. Switch is LBS.
Loss of Phase
Protection ON. Loss of Phase Protection
Rejected if: OFF. Rejected if:
Sequence Control
ON. Rejected if:
14 Sequence Control Sequence Control OFF. 41-00.00
Switch is LBS.
Loop Automation
ON. Rejected if:
Loop
automation
capability "Not
Available".
Trip coil
isolated.
Close coil
isolated.
Mechanism
fail.
Switchgear
Data Invalid.
Battery Not
Normal.
Capacitor
Loop Automation Controls Loop charge Not
19 Loop Automation OFF. 41-00.00
Control Automation. OK.
SF6 Gas
Pressure Low
(if applicable)
AND Low Gas
Interlock is
ON.
Tripped AND
(Midpoint OR
Feeder).
Closed AND
TIE.
No CVTs on
both sides
AND (TIE OR
Auto Restore
ON).
Turn Sectionalising
ON. Rejected if:
Turns Sectionalising
23 Sectionaliser Auto Turn Sectionalising OFF. 41-00.00
ON and OFF. Switch is ACR.
Switch is LBS.
No X side
voltage
Turns Dead Lockout
24 Dead Lockout measurement Turn Dead Lockout OFF. 41-00.00
ON and OFF.
possible and
power flow
direction is X
to I side.
Make Loss Of
Phase/Loop Linked.
Rejected if:
Links and unlinks
Loss Of the Loss Of Phase Make Loss Of
25 Switch is LBS. 41-00.00
Phase/Loop and Loop Auto ON Phase/Loop Unlinked.
Single phase
setting.
measurement.
Activates Group A
Activates Group A
as
Protection/Detection as
28 protection/detection No action 41-00.00
Group A Active protection/detection
group. Refer Note
group.
2.
Activates Group B
Activates Group B
as
Protection/Detection as
29 protection/detection No action 41-00.00
Group B Active protection/detection
group. Refer Note
group.
2.
Activates Group C
as Activates Group C
Protection/Detection protection/detection as
30 No action 41-00.00
Group C Active group. Refer Note protection/detection
2. group.
Activates Group D
Activates Group D
as
Protection/Detection as
31 protection/detection No action 41-00.00
Group D Active protection/detection
group. Refer Note
group.
2.
Activates Group E
Activates Group E
as
Protection/Detection as
32 protection/detection No action 41-00.00
Group E Active protection/detection
group. Refer Note
group.
2.
Activates Group F
Activates Group F
as
Protection/Detection as
33 protection/detection No action 41-00.00
Group F Active protection/detection
group. Refer Note
group.
2.
Activates Group G
Activates Group G
as
Protection/Detection as
34 protection/detection No action 41-00.00
Group G Active protection/detection
group. Refer Note
group.
2.
Activates Group H
Activates Group H
as
Protection/Detection as
35 protection/detection No action 41-00.00
Group H Active protection/detection
group. Refer Note
group.
2.
Activates Group I as
Activates Group I as
Protection/Detection protection/detection
36 protection/detection No action 41-00.00
Group I Active group. Refer Note
group.
2.
Activates Group J
as Activates Group J as
Protection/Detection
37 protection/detection protection/detection No action 41-00.00
Group J Active
group. Refer Note group.
2.
Enable the ACO
Disable the ACO
Scheme. Rejected
Scheme. Rejected if:
if:
Auto-Changeover Auto-Changeover
51 ACO feature is not 44-36.00
Control Enabled/Disabled. ACO feature is
available.
not available.
No auxiliary
supply.
No battery
supply.
In pickup or
Start/Stop Battery protection
60 No action 41-00.00
Test sequence
Within 15mins
of previous test
Clear 'Settings
Clear 'Settings
61 Changed' status No action 41-00.00
Changed'
flag.
Set the Maximum
Demand Indicator
values to the
present phase Set the Maximum
Reset Maximum values. Does not Demand Indicator
74 No action 41-02.35
Demand Indicators apply to the points: values to the present
LGVT, MDI-Today, phase values
MDI-Previous Day,
MDI-Previous 7
Days.
Sets the operational
cold load (reverse)
time to either zero Sets Cold Load
or to the maximum (reverse) Time to its
configured value. maximum value. Sets cold load (reverse)
This affects the This means the Cold time to zero. This means
reverse Operational Load Threshold the Threshold Multiplier
Cold Load Current will be set to will not be affected by the
Threshold Multiplier. its maximum value. Cold Load function.
Rejected if Cold Rejected if: Rejected if:
Cold Load Reverse Load is configured
75 41-02.43
Idle/Max to OFF in the Cold load Cold load support is
currently active support is OFF.
protection group. OFF. Cold load time is
After a new time is Cold load time below the IDLE
set, the Cold Load is above the threshold.
function will IDLE
immediately start to threshold.
increment or
decrement the
value depending on
the load current.
Sets the operational
cold load time to
either zero or to the
maximum Sets cold load time to
configured value. zero. This means the
This affects the Sets Cold Load Threshold Multiplier will
Operational Cold Time to its maximum not be affected by the
Load Threshold value. This means Cold Load function.
76 Cold Load Off/Max Multiplier. Rejected the Cold Load Rejected if: 41-02.50
if Cold Load is Threshold Current
configured to OFF will be set to its Cold load support is
increment or
decrement the
value depending on
the load current.
Sets the operational
cold load (reverse)
time to either zero
or to the maximum
Sets Cold Load
configured value.
(reverse) Time to its
This affects the Sets cold load time
maximum value.
Operational Cold (reverse) to zero. This
This means the Cold
Load Threshold means the Threshold
Load Threshold
Multiplier. Rejected Multiplier will not be
Current will be set to
if Cold Load is affected by the Cold Load
Cold Load Reverse its maximum value.
77 configured to OFF function. Rejected if: 41-02.50
Off/Max Rejected if:
in the currently
active protection Cold load support is
Cold load
group. After a new OFF.
support is
time is set, the Cold
OFF.
Load function will
immediately start to
increment or
decrement the
value depending on
the load current.
Controls the Normal
Normal Voltage Turns Normal Turns Normal Voltage
78 Voltage Close 42-00.00
Close Voltage Close ON Close OFF
setting.
Controls the Under
Turns Under Voltage Turns Under Voltage
79 Under Voltage Trip Voltage Trip 42-00.00
Tripping ON Tripping OFF
setting.
Controls the Over
Turns Over Voltage Turns Over Voltage
80 Over Voltage Trip Voltage Trip 42-00.00
Tripping ON Tripping OFF
setting.
Controls the Sag Turn Sag monitoring Turn Sag monitoring
81 Sag Monitoring 42-00.00
Monitoring setting. ON OFF
Controls the Swell Turn Swell Turn Swell monitoring
82 Swell Monitoring 42-00.00
Monitoring setting. monitoring ON OFF
Performs a reset of
Reset Sag/Swell Resets the Sag and
the Sag and Swell
83 Counters and Swell counters and No action 42-00.00
counters and total
Durations durations
duration
If the controller is If the controller is
operating as an operating as an ACR If the controller is
ACR then turn Auto then turn Auto operating as an ACR then
Reclose function Reclose ON. turn Auto Reclose OFF.
Auto Reclose or ON or OFF. If the
86 44-04.02
Sectionaliser Auto controller is If the controller is If the controller is
operating as a LBS operating as a LBS operating as a LBS then
then turn then turn turn Sectionaliser Auto
Sectionaliser Auto Sectionaliser Auto OFF.
ON or OFF. ON.
Clears all protection
This command trip or detection fault
88 Reset Fault Flags clears protocol fault status flags and No action 44-21.00
flags. Settings Changed
flag.
Turn SEF/SGF
Alarm ON. Rejected
if:
Fault Locator Controls the fault Turn the Fault Turn the Fault Locator
90 45-06.02
control locator setting. Locator On. Off.
Unit Version
Point Name Description Min Max Resolution
(s) Introduced
Protection/Detection
1 0 9 N/A 1 41-00.00
Group
0 = NPS
Protection/Detection
OFF
NPS 1 = NPS
2 Protection/Detection Protection/Detection 0 2 N/A 1 41-00.00
Control ON
2 = NPS
Protection/Detection
Alarm only
0 = Loss of phase
OFF
2 = Loss of phase
Alarm only
Change Custom -
5 2147483647 N/A 1 45-03.00
Variable 01 2147483648
Change Custom -
6 2147483647 N/A 1 45-03.00
Variable 02 2147483648
Change Custom -
7 2147483647 N/A 1 45-03.00
Variable 03 2147483648
Change Custom -
8 2147483647 N/A 1 45-03.00
Variable 04 2147483648
Change Custom -
9 2147483647 N/A 1 45-03.00
Variable 05 2147483648
Change Custom -
10 2147483647 N/A 1 45-03.00
Variable 06 2147483648
Change Custom -
11 2147483647 N/A 1 45-03.00
Variable 07 2147483648
Change Custom -
12 2147483647 N/A 1 45-03.00
Variable 08 2147483648
Change Custom -
13 2147483647 N/A 1 45-03.00
Variable 09 2147483648
Change Custom -
14 2147483647 N/A 1 45-03.00
Variable 10 2147483648
Change Custom -
15 2147483647 N/A 1 45-03.00
Variable 11 2147483648
Change Custom -
16 2147483647 N/A 1 45-03.00
Variable 12 2147483648
Change Custom -
17 2147483647 N/A 1 45-03.00
Variable 13 2147483648
Change Custom -
18 2147483647 N/A 1 45-03.00
Variable 14 2147483648
Change Custom -
19 2147483647 N/A 1 45-03.00
Variable 15 2147483648
Change Custom -
20 2147483647 N/A 1 45-03.00
Variable 16 2147483648
Change Custom -
21 2147483647 N/A 1 45-03.00
Variable 17 2147483648
Change Custom -
22 2147483647 N/A 1 45-03.00
Variable 18 2147483648
Change Custom -
23 2147483647 N/A 1 45-03.00
Variable 19 2147483648
Change Custom -
24 2147483647 N/A 1 45-03.00
Variable 20 2147483648
Change Custom -
25 2147483647 N/A 1 45-03.00
Variable 21 2147483648
Change Custom -
26 2147483647 N/A 1 45-03.00
Variable 22 2147483648
Change Custom -
27 2147483647 N/A 1 45-03.00
Variable 23 2147483648
Change Custom -
28 2147483647 N/A 1 45-03.00
Variable 24 2147483648
Change Custom -
29 2147483647 N/A 1 45-03.00
Variable 25 2147483648
Change Custom -
30 2147483647 N/A 1 45-03.00
Variable 26 2147483648
Change Custom -
31 2147483647 N/A 1 45-03.00
Variable 27 2147483648
Change Custom -
32 2147483647 N/A 1 45-03.00
Variable 28 2147483648
Change Custom -
33 2147483647 N/A 1 45-03.00
Variable 29 2147483648
Change Custom -
34 2147483647 N/A 1 45-03.00
Variable 30 2147483648
Change Custom -
35 2147483647 N/A 1 45-03.00
Variable 31 2147483648
Change Custom -
36 2147483647 N/A 1 45-03.00
Variable 32 2147483648
They can be accessed by any point configuration tool eg. Protocols, IOEX.
Version
Point Name Description Set = '1' Clear = '0'
Introduced
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
42 configurable access 41-00.00
Control 1 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
43 configurable access 41-00.00
Control 2 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
44 configurable access 41-00.00
Control 3 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
45 configurable access 41-00.00
Control 4 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
46 configurable access 41-00.00
Control 5 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
47 configurable access 41-00.00
Control 6 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
48 configurable access 41-00.00
Control 7 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
49 configurable access 41-00.00
Control 8 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
66 configurable access 44-28.00
Control 9 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
67 configurable access 44-28.00
Control 10 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
68 configurable access 44-28.00
Control 11 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
69 configurable access 44-28.00
Control 12 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
70 configurable access 44-28.00
Control 13 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
71 configurable access 44-28.00
Control 14 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
72 configurable access 44-28.00
Control 15 access point. access point.
point.(1)
Sets or clears a
Protocol IOEX Sets a configurable Clears a configurable
73 configurable access 44-28.00
Control 16 access point. access point.
point.(1)