Professional Documents
Culture Documents
ELECTRICAL
ENGINEERING DESIGN GUIDE
FOR
STANDARD ELECTRICAL PROTECTION SCHEMES
(INTERNATIONAL PROJECTS)
This document and the design it covers are the property of BECHTEL.
They are merely loaned on the borrower's express agreement that
they will not be reproduced, copied, loaned, exhibited, or used except
in the limited way and private use permitted and by any written
consent given by the lender to the borrower.
1.0 PURPOSE................................................................................................................4
2.0 SCOPE.....................................................................................................................4
3.0 CODES AND STANDARDS..................................................................................4
4.0 PROTECTION SCHEMES.....................................................................................4
4.1 LOW VOLTAGE MOTOR PROTECTION...............................................5
4.2 HIGH VOLTAGE MOTOR PROTECTION..............................................6
4.3 FEEDER PROTECTION.............................................................................8
4.4 TRANSFORMER FEEDER PROTECTION..............................................9
4.5 GENERATOR PROTECTION.................................................................10
4.6 SWITCHGEAR PROTECTION...............................................................11
Figure 3 One-line Diagram for L.V. Motors ³ 30 kW using Motor Protection Relay
Figure 12 One-line Diagram for L.V. Transformer (<1000 kVA) Incomer Sealed Type
Figure 13 One-line Diagram for L.V. Transformer (³ 1000 kVA) Incomer Sealed Type
Figure 14 One-line Diagram for L.V. Transformer (³ 500 kVA < 1000 kVA) Incomer
Conservator Type
Figure 15 One-line Diagram for L.V. Transformer (³ 1000 kVA) Incomer Conservator
Type
This engineering design guide outlines standard protection and control schemes to be
adopted for power systems within industrial plants. It also describes commonly
encountered variations to these schemes.
2.0 SCOPE
This guide covers industrial type power systems for voltages up to 33 kV and total
power consumption up to approximately 100 MVA and individual generators up to about
40MVA.
The following International Standards are relevant to the subject matter of this design
guide:
IEC 644 Specification for high-voltage fuse-links for motor circuit applications
Figures give protection and control schemes for the most common applications of low-
voltage and high-voltage ac squirrel cage induction motors, low-voltage and high-
voltage feeders, power transformers, directly connected power generators and
switchgear. These schemes are maintained as CAD cells for direct inclusion in one-line
diagrams. The schemes presented do not encompass special cases, but should be
adopted unless circumstances demand otherwise.
4.1.1 Where low voltage motors are supplied by contactor starters, fuses should be
selected to provide motor and cable short circuit protection while thermal relays
are provided for overload protection. Moulded Case Circuit Breakers (MCCBs)
having instantaneous overcurrent elements may be used in place of the
switch/fuse, provided that they have sufficient fault breaking capacity. The
MCCBs should be fitted with current limiters in order to limit the fault level, and
thus avoid oversizing cables.
4.1.2 Where fault rated circuit breakers are used for motor switching, separate
instantaneous overcurrent protection, usually combined into a comprehensive
motor protection relay is to be provided.
4.1.3 Single speed, unidirectional or reversing motors, require only a single overload
protection relay. Two speed motors require one overload relay for each speed
connection.
4.1.4 All thermal overload relays should include single phasing (phase failure)
protection
4.1.5 Direct acting thermal relays are normally provided for motors rated less than 30
kW (up to 40 A approximately). For motor ratings of 30 kW and above thermal
overload relays may be supplied via current transformers, if this is the
manufacturer's standard practice.
4.1.6 Sensitive earth fault protection should be provided for all motors of 30kW and
above as it is considered that fuse protection alone will not give acceptable earth
fault clearance times for low values of earth fault current. Consideration must be
given to coordination between the earth fault relay and the fuses to ensure that
the contactor is not called upon to break a fault current in excess of its rating. It
may be necessary to introduce a delay in the earth fault tripping time to achieve
this coordination.
'te' time is the time taken for any part of the motor to heat up to the limiting
temperature from the full load temperature, whilst the motor is stalled and
the windings carry locked rotor current under the maximum coolant
temperature conditions.
This can be achieved by a good conventional overload protection relay but
additionally a Positive Temperature Coefficient (PTC) element (e.g
Thermistor) in the motor with it's associated relay in the motor starter is
sometimes recommended.
e) On motors driving high inertia loads, the starting time may exceed the safe
stall time. In this case a speed switch may be fitted on the motor, or
alternatively an impedance relay which can sense whether the motor is
rotating, is provided to check that rotation has commenced and to override
the normal stall protection during run up.
4.2.1 Motors up to 1200 kW are generally supplied at voltages where contactor starters
are available. Short circuit protection is provided by high voltage fuses. High
voltage fuses should have striker pins to trip the contactor on fuse faulure.
Where circuit breakers are employed, separate instantaneous overcurrent
protection should be provided.
4.2.3 An electronic multifunction protective relay is preferred for high voltage motor
protection. Such relays should incorporate :-
c) Sensitive earth fault protection (with time delay for contactor applications
where necessary).
e) Stall protection.
4.2.5 For motors rated 1200 kW and above a form of differential protection should be
provided. One of the following methods may be employed:
a) A single 'core balance' CT located in the main terminal box of the motor through
which are passed all six winding ends, the star point being made 'outside' the
protected zone. This arrangement which is very sensitive to winding earth faults,
requires only two wires to be taken back to a relay mounted in the motor starter.
b) Three core balance CTs in the main motor terminal box, through each of which
are passed the two ends of a single winding, the star point being made outside
the protected zone. Two wires have to be taken back to the starter to relays for
each of the three CTs. This scheme is very sensitive both to phase and earth
faults in the motor
4.2.6 For motors rated above 750 kW, winding RTD's should be provided. It is usual to
provide six platinum resistance temperature elements, resistance 100 ohms at
0°C, three wire type, two being located in the slots of each phase.
4.2.7 Additional protection may be required by the project, e.g. Vibration, bearing
temperature, cooling air or water flow/ temperature. These devices may be
elected to Alarm Only or alternatively configured with two stages, i.e. Alarm
before Trip.
a) Feeders of 63 amps rating and below may be simple fuse switches provided that
the earth loop impedance permits earth fault clearance within the time limit set by
applicable codes. Where a remote control is required a contactor feeder may be
provided. At ratings above 63 amps a contactor feeder arrangement should be
provided together with separate sensitive earth fault protection, co-ordinated with
the fuses to ensure that the contactor does not break currents above its rating.
b) Fault rated MCCBs may be used in place of a switch and fuse unit in which case
it may be tripped by a shunt trip coil instead of combining with a contactor to
incorporate the earth fault feature.
4.4.1 Transformer primary side protection should comprise IDMT overcurrent, high set
instanteous overcurrent and earth fault relays.
4.4.2 The primary side overcurrent relay provides overcurrent protection to the
transformer and cables as well as back up to the secondary side switchboard
incomer protection.
4.4.3 The zone of protection of the primary side earth fault relay extends only across
the primary side cables to the primary winding of the transformer.
A restricted earth fault relay should be provided for transformers rated 1000 kVA
and above.
Both types of earth fault relay should trip the primary side breaker directly and the
secondary side breaker via a lockout relay.
Unrestricted earth fault protection is normally of IDMT type set to coordinate with
downstream relays and fuses. In resistance earthed schemes the set points of
the earth fault relays must be determined by the time and current rating of the
resistor usually requiring a definite time relay rather than an IDMT type.
4.4.8 All transformers should be fitted with an oil temperature alarm. For high voltage
transformers a winding temperature alarm and trip device should be provided.
4.4.9 For large transformers (5MVA and above) a biased differential current protection
scheme extending from the primary side switchgear through to the secondary
side switchgear may be provided in order to give the fastest possible
phase/phase and earth fault protection covering both primary and secondary
cabling as well as the transformer. Transformer differential relays are specially
designed to allow for transformer charging currents as well as providing the range
necessary to allow the relay setting to take account of the mismatch of the CTs
on the different voltage systems in addition to allowing for the range of current
variation due to tap changing.
4.5.1 All generators should be provided with Merz-Price circulating current protection
which will provide phase and (for solid or low resistance earthed systems) earth
fault protection. For low-voltage generators rated 1000 kVA and below this may
be reduced to a restricted earth fault scheme by using one c.t. in the neutral
instead of three phase connected CTs on the neutral side. For high resistance
earthed systems, core balance schemes as described for large motors should be
considered.
4.5.4 Reverse power protection should be provided for all generators used for parallel
operation.
4.5.5 Generator AVRs should be of the electronic type that inherently provides under
and over voltage, overfluxing and loss of field protection. In this case separate
protection relays for these functions are not required.
4.5.6 For generators rated 5 MVA and above which are used in parallel operation, a
field failure relay of the impedance measuring type (to detect asynchronous
operation) should be provided.
4.5.7 The generator control scheme appended to this design guide includes provision
for synchronising, automatic transfer, and interlocking and is based on
synchronising being carried out within the substation. For automatic start up and
transfer the generator diagram is used in conjunction with the corresponding
normal supply incomer diagram.
4.5.8 The generator manufacturer may recommend additional protection to that listed
above.
4.6.1 Low-voltage switchgear and high-voltage switchgear is not usually provided with
overcurrent or earth fault protection other than that given by the incoming circuit
protection. The rareness of switchgear failure, especially when fully insulated
bus is used makes further protection unattractive. A frame earth protection might
be provided but this is non-selective and has to disconnect the entire switchboard
for a fault on an individual section.
4.6.4 Trip receive relays should be provided at the switchgear such that the cause of
the trip is made apparent whenever the trip initiating contact is remote from the
switchgear. Such a relay may also be essential in order to act as an interposing
relay when long lengths of pilot are involved.
4.6.5 Lock-out relays should be provided in every case where a trip contact is self
resetting or where there is a multiplicity of individual tripping devices (say three or
more). In the case of only one or two tripping devices, individual hand reset
relays can suffice.