Professional Documents
Culture Documents
The field-testing and calibration of solid-state trip units can be performed by either primary
current injection method or secondary current injection method. Photo: YouTube.
The proper functioning of the trip unit can be tested using primary current injection, one phase at
a time. Photo: YouTube.
The primary current injection method is usually the preferred test
method because it includes the current sensors, wiring, and the
current conduction path in the circuit breaker with the test. However,
this method has one disadvantage in that it will not always detect
sensor wiring and polarity problems.
Solid-state trip units can be tested via secondary current injection using a test set specifically
designed for the device to be tested. Photo: Switchserve.
Secondary current injection tests are performed for the same reason
as primary current injection current tests, which is to verify the correct
functioning of a circuit breaker trip device during startup testing or
maintenance inspections.
Unlike primary injection, this test method does not verify the current
sensors, wiring, or circuit breaker current carrying components. This is
the main reason why the primary injection test method has superiority
over secondary injection testing.
Test set connections are made directly at the solid-state trip unit, as
these devices are almost universally equipped with test plug terminals
for conducting the test. The secondary test set injects a simulated CT
secondary current to allow checking of the trip unit operation without
the need for injecting primary current through the current sensors.
Secondary injection test set connections are made directly at the solid-state trip unit. Photo:
Square D.
The circuit breaker under test must be disconnected from the bus
prior to verifying the operation of solid-state trip units. The test set is
capable of passing enough current to check any desired calibration
point, and the breaker will trip during this process.
If any test shows that the solid-state trip unit is not functioning
properly, the trip unit should be replaced and the defective
unit labeled and removed from service until repaired. The technician
conducting the test should be familiar with the instructions of the
particular secondary injection test set for operating procedures to
determine whether the unit has indeed failed.
1. No-trip mode
The protective functions of the electronic trip device can be tested, but
the trip device won't send a trip signal to the circuit breakers trip
actuator. This test can be performed while the circuit breaker is
energized and carrying load current because a no-trip test won't
cause the circuit breaker to open.
2. Trip mode
The protective functions of the electronic circuit are tested just like a
no-trip mode test, except the trip unit will send a signal to the circuit
breakers trip actuator. This will cause the circuit breaker to open,
which is why this test is typically performed only when a circuit
breaker is withdrawn from its compartment and therefore
disconnected from the switchgear bus.
3. Self-test Mode
The self-test function does not verify the performance of the circuit breakers current sensors and
the associated current wiring. Photo: Eaton.
10 common elements found on modern solid-state trip units. Each manufacturer and style will be
different. Photo: TestGuy.
When a circuit breaker is in its test position, the closing of its main
contacts will not connect the associated load circuit with the
switchgear line bus. In any such case, a circuit breaker should never
be tested inside its switchgear compartment while personnel are
performing work on electrical equipment that is connected to the
associated load circuit.
References