Professional Documents
Culture Documents
TRANSFORMER
By,
Mr.B.L.Lingshettar(Director-Technical,Retd) HESCOM
Bright Engineers Services,Hubli
TESTS ON TRANSFORMER
Continuity Test
Insulation Resistance and Polarization Index
Capacitance and Tan Delta
Turns Ratio
Magnetic Balance
Winding Resistance
Partial Discharge Test
Sweep Frequency Response
Open Circuit and Short Circuit Test
Auxiliaries Of Transformer
Conservator
Breather
BH Relay (Oil & Gas Relay)
PRV (Pressure Relief Valve)
WTI & OTI
Cooling System
Continuity Test
POLARIZATION INDEX
10 minute IR reading
PI = --------------------------------
1 minute IR reading
The minimum PI value is 1.3 for safe operation.
If PI is less than 1.3 action to be taken for its improvement.
Turns Ratio
• It is the ratio of the number of turns in a higher
voltage winding to that in a lower voltage
winding.
Why the transformer turns ratio test needed?
Winding resistance measurements in
transformer are of fundamental
importance for the following purposes:
Questionable (500-1000) pC
Chemical Method
Acoustic Emission Method
Electrical Method
Sweep Frequency Response Analysis
It is to determine the frequency response of
windings.
The freq responses serve as the finger prints to
monitor the transformer condition.
It is obtained by application of sweep frequency
(sinusoidal) from 20Hz to 2MHz.
The windings have characteristic frequency
response for the applied signal at different
frequencies.
It is performed on one winding at a time.
Test Set Up
During test the transformer has to be electrically
isolated from all other electrical connections including
earth connections.
Needs to earth one end of every winding that is not
being tested , leave the other end open.
Response have to be measured across the
Y-connection terminal and neutral.
D-connection two line terminals.
Transformer Model for SFRA
Healthy transformer 33kV 10MVA
-1
dB
-9
-8
-7
-6
-5
-4
-3
-2
-1
1
20
0 UV 1.000e+00V2W W
1.00U
0e+003 1.000e+004 1.000e+005 f/Hz
Damaged Winding 400kV 100MVA
dB
-60
-5
-4
-3
-2
-1 NA 5 NB 10 N
20C 50 100 200 500 1000 f/kHz
What can SFRA detect?
Fingerprint (Reference Measurement) is important!!!
36 1,000
145 10,000
245 20,000
300 30,000
420 40,000
Permitted Tolerances
Performance factor Tolerance
4) Short circuit impedance for any tapping Not less than as indicated in 3