B6031I Series

Deep Well Pump Inverter


User Manual

GUANGZHOU BEDFORD ELECTRIC EQUIPMENT CO.,LTD.

V1.0.0
Preface

Thank you for purchasing our B6031I series deep well pump inverter, we will
provide you with a warm and attentive service.
B6031I series products is specifically designed for deep well pump, Some
models controllers can be set the parameter selection to control single-phase or
three-phase pumps.
This manual provides you the main features, parameter setting and operation
methods of B6031I series. Before operating Please read this manual and understand
the contents of this manual to ensure proper use of B6031I series.
Contents

1. SAFETY PRECAUTIONS..................................................................... 1
2. PRODUCT INTRODUCTION.............................................................. 2
2.1 Features...................................................................................................... 2
2.2 Model Specification................................................................................... 2
2.3 Selection Guide.......................................................................................... 2
2.4 External Dimension................................................................................... 4
3. ENVIRONMENTAL REQUIREMENT............................................... 5
4. WIRING................................................................................................... 6
4.1 Main Circuit Terminals Wiring..................................................................6
4.2 Control Circuits Terminals Wiring............................................................ 8
4.2.1 The Wiring of Water-level Auto Controlling Terminals.....................8
4.2.2 Additional Remarks of Control Mode............................................... 10
4.3 Wiring Main Circuits............................................................................... 11
4.3.1 Wiring of Main Circuits........................................................................ 11
4.3.2 Circuit Breaker......................................................................................11
4.3.3 AC Reactor (Optional)......................................................................... 11
4.3.4 Input EMC Filter (Optional)................................................................ 11
4.3.5 Output EMC Filter (Optional)............................................................. 11
4.3.6 Output Reactor..................................................................................... 11
4.3.7 Ground Wiring (PE)............................................................................. 12
5. OPERATION......................................................................................... 12
5.1 Keypad Description................................................................................. 12
5.2 Operation Procedure................................................................................ 12
5.2.1 The Display Interface Prefix Alphabet Meaning............................. 12
5.2.2 Power-on Initialization.........................................................................13
5.2.3 Parameter Setting................................................................................13
6. INSTRUCTIONS OF PARAMETERS GROUP............................... 14
7. APPLICATION GUIDANCE...............................................................16
7.1 Wiring and Setting for the Water-level of Deep Well and Upper
Reservoir Auto Controlling............................................................................16
7.1.1 System Wiring...................................................................................... 16
7.1.2 System Debugging Procedure.......................................................... 16
7.1.3 Relevant Parameter Setting...............................................................16
7.2 Wiring and Setting for the Water-level of Deep Well Auto Controlling
and Constant Pressure Water Supply............................................................. 17
7.2.1 System Wiring...................................................................................... 17
7.2.2 System Debugging Procedure.......................................................... 18
7.2.3 Relevant Parameter Setting...............................................................18
8. FAULT AND TROUBLE SHOOTING............................................... 19
8.1 Pump Running Fault and Trouble Shooting............................................ 19
8.2 Controller Running Fault and Trouble Shooting.....................................19
B6031I Series Deep well Pump Inverter User Manual

1. SAFETY PRECAUTIONS

B6031I is a new power electronic product, please read the operation manual
carefully before using to keep your safety and make sure proper operation.
In this manual, the safety precautions were sorted to “WARNING” and
“CAUTION”.

WARNING: Wrong using may result in death or serious personal injury.

CAUTION: Wrong using may result in the damage of controller or system.

WARNING
 Please don’t dismantle, change the product, or may cause electric shock, fire hazard and
personal injury;
 Please don’t open the cover during the running of controller;
 Please don’t put wire, bar of metal, filaments etc. into the controller so as not to cause a
short circuit or get an electric shock;
 Please don’t splash water or other liquid over the controller;
 Layout operations should be carried out by a qualified electrical professional, and construct
in accordance with the electrical code.

CAUTION
 Please don’t make withstand voltage testing for the controller;
 Never connect AC power to output UVW terminals;
 If the internal components of the controller were influenced or damaged by static, please do
not to touch;
 The motor, controller and power specifications should be matching, otherwise it could cause
abnormal operation even burn out the device;
 If the controller appears serious vibration, noise, heat or peculiar smell in the first operation,
please cut off the power immediately and contact suppliers or service center later;
 Please don’t install the controller in the environment with direct sunlight, rain, frost or snow
in case of deformation or damage.

Warm reminder:
If B6031ID(B2) is displaying “A033” on power, then put deep well pump into
the deep well as well as the actual water-level in the deep well is higher than the
horizontal line of the high water-level, “A033” fault will be removed.
If there is not using S1 and S2,please connect terminal S1, S2 to COM,or the
controller can’t be able to work.

1
B6031I Series Deep well Pump Inverter User Manual

2. PRODUCT INTRODUCTION

2.1 Features

◆Single-phase, three-phase selection function: Some models controllers can be


chosen to control single-phase or three-phase motor.
◆Power on restart: Running automatically when power on.
◆Sleep function: Sleep down when have no water consumption, to earn a better
energy saving.
◆Control method: The water-level of deep well and upper reservoir auto
controlling; The water-level of deep well auto controlling and constant
pressure water supply.
◆Various of water supply fault alarm function: High-pressure, low-pressure,
transducer, water shortage error etc..
◆Many fault protection function: Over-current, over-voltage, phase-failure,
over-load etc..

2.2 Model Specification

B6031I D-2 002

Power Symbol 002: 2HP 1Φ/ 0.75kW; 3Φ /1.5kW

Voltage Class 2: 220VAC

Grade of Protection: D IP20; B2 IP54

Series Number of Deep Well Pump Inverter

2.3 Selection Guide


Table2.3.1 B6031I list
Rated Input Input Max. Output Motor Power (kW)
Model No.
Voltage (V) Current (A) Current (A) 1Φ 3Φ
B6031ID(B2)-2001 8.2 4.5 0.37 0.75
1AC: 220V
B6031ID(B2)-2002 14.2 11.0 0.75 1.5
-15%~+15%
B6031ID(B2)-2003 23.0 15.0 1.5 2.2
B6031ID-2001 5.0 4.5 / 0.75
B6031ID-2002 3AC: 220V 7.7 7.0 / 1.5
B6031ID-2003 -15%~+15% 11.0 10.0 / 2.2

2
B6031I Series Deep well Pump Inverter User Manual
Rated Input Input Max. Output Motor Power (kW)
Model No.
Voltage (V) Current (A) Current (A) 1Φ 3Φ
B6031ID(B2)-2005 17.0 16.0 / 3.7
B6031ID(B2)-2007 21.0 20.0 / 5.5
B6031ID-2010 31.0 30.0 / 7.5
B6031ID-2015 43.0 42.0 / 11
B6031ID-2020 56.0 55.0 / 15
B6031ID-2025 71.0 70.0 / 18.5
B6031ID-2030 81.0 80.0 / 22
B6031ID-2040 112.0 110.0 / 30
B6031ID-2050 132.0 130.0 / 37
B6031ID-2060 163.0 160.0 / 45
B6031ID-2075 200.0 200.0 / 55
B6031ID(B2)-4001 3.4 2.5 / 0.75
B6031ID(B2)-4002 5.0 3.7 / 1.5
B6031ID(B2)-4003 5.8 5.0 / 2.2
B6031ID(B2)-4005 10.0 9.0 / 4.0
B6031ID(B2)-4007 15.0 13.0 / 5.5
B6031ID(B2)-4010 20.0 17.0 / 7.5
B6031ID(B2)-4015 26.0 25.0 / 11
B6031ID(B2)-4020 35.0 32.0 / 15
B6031ID-4025 38.0 37.0 / 18.5
B6031ID-4030 46.0 45.0 / 22
B6031ID-4040 62.0 60.0 / 30
B6031ID-4050 76.0 75.0 / 37
B6031ID-4060 3AC: 380V 90.0 90.0 / 45
B6031ID-4075 -15%~+15% 105.0 110.0 / 55
B6031ID-4100 140 150 / 75
B6031ID-4120 160 176 / 90
B6031ID-4150 210 210 / 110
B6031ID-4180 240 250 / 132
B6031ID-4215 290 300 / 160
B6031ID-4250 330 340 / 185
B6031ID-4270 370 380 / 200
B6031ID-4300 410 415 / 220
B6031ID-4340 460 470 / 250
B6031ID-4380 500 520 / 280
B6031ID-4430 580 600 / 315
B6031ID-4470 620 640 / 350

3
B6031I Series Deep well Pump Inverter User Manual

2.4 External Dimension

1. The dimension of B6031IB2

Model A(mm) B(mm) H(mm) W(mm) D(mm) Installation


(kW) Installation Dimension External Dimension Hole
0.75~2.2 (B2 models) - - 216 195 154 -
4~7.5 (B2 modes) - - 282 255 165 -
11-15 (B2 models) - - 370 350 221 -

2. The dimension of B6031ID

Figure2-4-1 Dimension (0 .75~18.5kW) Figure 2-4-2 Dimension (22~132kW)

4
B6031I Series Deep well Pump Inverter User Manual

Figure 2-4-3 Dimension (160~350kW)

Model A (mm) B (mm) H (mm) W (mm) D (mm) Installation


(kW) Installation Dimension External Dimension Hole
0.75~2.2 110 169.6 179.6 120.1 150.3 4.0
4~7.5 147.4 236 250 160 194.5 5.0
11~18.5 205.6 303.6 320 220 193.5 6.0
22~37 175 455 472 295 222 6.5
45~75 230 564.5 580 380 270 7.0
90~132 320 738.5 755 465 330 9.0
160~200 (Without base) 270 1233 1275 490 395 13.0
160~200 (With base) 1490 490 395
220~350 (Without base) 500 1324 1358 750 402 12.5
220~350 (With base) 1670 750 402

3. ENVIRONMENTAL REQUIREMENT

1. Environment temperature range: -10℃~+40℃. Controller will be derated if


ambient temperature exceeds 40℃.
2. Prevent rain drops, moist environment, oil fog, salt erosion, corrosive gas,
etc.
3. Prevent direct sunlight, keep away from radiation source.
4. Prevent violent vibration or sudden impact.
5. Lower than 1000m installation altitude, it will be derated when the altitude is
higher than 1000m.

5
B6031I Series Deep well Pump Inverter User Manual

CAUTION
 When moving the controller please lift by its base and don’t lift by the panel.
Otherwise may cause the main unit fall off which may result in personal injury.
 Install the controller on the fireproofing material (such as metal) to prevent fire.
 When power off, should not install the controller until the power indicator light
was extinguished, which can ensure the device has been discharged completely.
 Disconnect all power line before opening front cover of unit. Wait at least 5 minute
until DC Bus capacitors discharge.

4. WIRING

4.1 Main Circuit Terminals Wiring


1. The main circuit terminals wiring of B6031IB2 (220VAC)
R(L) S(N) T U V W
PE PE
POWER MOTOR
Figure 4.1.1 The main circuit terminals wiring of B6031IB2 (0.75-2.2kW)

SR T U V W
(+) (-) PB PE PE
POWER MOTOR
Figure 4.1.2 The main circuit terminals wiring of B6031IB2 (3.7-5.5kW)

2. The main circuit terminals wiring of B6031IB2 (380VAC)


R S T U V W
PE PE
POWER MOTOR
Figure 4.1.3 The main circuit terminals wiring of B6031IB2 (0.75-2.2kW)

SR T U V W
(+) (-) PB PE PE
POWER MOTOR
Figure 4.1.4 The main circuit terminals wiring of B6031IB2 (4.0-7.5kW)

S R T U V W
PE (+) PB (-) PE
POWER MOTOR
Figure 4.1.5 The main circuit terminals wiring of B6031IB2 (11~15kW)

3. The main circuit terminals wiring of B6031ID (220VAC)


L N U V W
AC220V MOTOR
Figure 4.1.6 The main circuit terminals wiring of B603I1D (0.72~2.2kW)

R
S T U V W
(+) (-)
AC220V MOTOR
Figure 4.1.7 The main circuit terminals wiring of B6031ID (3.7~5.5kW)

6
B6031I Series Deep well Pump Inverter User Manual
R S T U V W
(+) (-)
POWER MOTOR
Figure 4.1.8 The main circuit terminals wiring of B6031ID (7.5kW)

4. The main circuit terminals wiring of B603D (380VAC)


R S T U V W
(+)
POWER MOTOR
Figure 4.1.9 The main circuit terminals wiring of B6031ID (0.72~2.2kW)

R S T U V W
(+) (-)
POWER MOTOR
Figure 4.1.10 The main circuit terminals wiring of B6031ID (4.0~7.5kW)

(+) (-) SR T U V W
POWER MOTOR
Figure 4.1.11 The main circuit terminals wiring of B6031ID (11~18.5kW)

R S T U V W
P1 (+) (-)
POWER MOTOR
Figure 4.1.12 The main circuit terminals wiring of B6031ID (22~110kW)

5. Main circuit terminal’s function as following:


Terminal Symbol Function Description
L, N Terminals of single phase AC input
U, V, W Motor wiring terminal

PE/ Terminals of ground

R, S, T Terminals of 3 phase AC input


(+), (-) Reserved external terminals for braking units
(+), PB Reserved external terminals for braking resistance
P1, (+) Reserved external terminals for braking DC reactors
(-) Output terminals for minus DC bus voltage

Notice: it can’t wire to “U” “V” “W” terminal arbitrarily when connect it with
single phase motor. It need to take away the capacitance as figure 4.1.13 diagram, and
wire according to the figure 4.1.14 diagram.

Notice that the “L” “N” in picture is not the same “L” “N” as the terminal of inverter
Figure 4.1.13 Diagram of single phase motor wiring with capacitance

7
B6031I Series Deep well Pump Inverter User Manual

Figure 4.1.14 Diagram of inverter drive after dismantling the capacitance of single phase motor

In order to keep safety and prevent electric shock and fire, PE must be grounded
with ground resistance. Furthermore, reliable grounding is the simplest, most
effective and minimum cost solution for EMC problems, so it enjoys priority in all
EMC methods.

4.2 Control Circuits Terminals Wiring

Figure 4.2.1 Control circuits terminals wiring


4.2.1 The Wiring of Water-level Auto Controlling Terminals
1. Water-level sensors for deep well connecting wiring
There are three signal leads of deep well as given (Figure4.2.2) for detecting
water-level. The longest signal line is ①, which is corresponding to the common port,
is connected to the “COM” of controller B6031ID(B2). The signal line ② that is
corresponding to the horizontal line of low water-level need to be connected to the
terminal “S1” of controller B6031ID(B2). The shortest line is ③, which is
corresponding to the horizontal line of high water-level, is connected to the terminal
“S2” of controller B6031ID(B2).

8
B6031I Series Deep well Pump Inverter User Manual

Figure4.2.2 water-level sensors for deep well connecting wiring


Remark: When the actual water-level in the deep well is lower than the
horizontal line of low water-level, “S1” will be disconnected to “COM” as well as the
controller B6031ID(B2) will be displaying “A033” and will automatically stop the
pump to prevent the pump from idling. “S2” will not be connected to “COM” and the
controller B6031ID(B2) will not clear out fault “A033” until the actual water-level in
the deep well is higher than the horizontal line of high water-level. And then, the
controller B6031ID(B2) will automatically start the pump. Until the actual
water-level in the deep well is lower than the horizontal line of low water-level, “S1”
will be disconnected to “COM” as well as the controller B6031ID(B2) will be
displaying “A033” and will automatically stop the pump to prevent the pump from
idling. The controller B6031ID(B2) will automatically control the pump in this cycle
way.

2. Water-level sensors for upper reservoir connecting wiring


There are three signal leads of upper reservoir as given (Figure4.2.3) for
detecting water-level. The longest signal line is ①, which is corresponding to the
common port, is connected to the “COM” of controller B6031ID(B2). The signal line
② that is corresponding to the horizontal line of low water-level need to be connected
to the terminal “S3” of controller B6031ID(B2). The shortest line is ③, which is
corresponding to the horizontal line of high water-level is connected to the terminal
“S4” of controller B6031ID(B2).

9
B6031I Series Deep well Pump Inverter User Manual

Figure4.2.3 water-level sensors for upper reservoir connecting wiring


Remark: When the controller B6031ID(B2) cleared out fault “A033” (When
there is the water in the deep well) and the actual water-level in the upper reservoir is
lower than the horizontal line of low water-level, “S3” will be disconnected to
“COM” as well as the controller B6031ID(B2) will automatically start the pump and
the upper reservoir will be injected the water. Until the actual water-level in the upper
reservoir is higher than the horizontal line of high water-level, “S4” will be connected
to “COM” as well as the controller B6031ID(B2) will automatically stop the pump to
prevent water overflow . Until the actual water-level in the upper reservoir is lower
than the horizontal line of low water-level, “S3” will be disconnected to “COM” as
well as controller will automatically start the pump, and the upper reservoir will be
injected the water. The controller will automatically control the pump in this cycle
way.
4.2.2 Additional Remarks of Control Mode
1. the water-level of deep well and upper reservoir auto controlling
Please connect the water-level sensor of deep well and upper reservoir as shown
in Figure4.2.2 and Figure4.2.3 as well as setting the parameter b00.06=0.
2. the water-level of deep well auto controlling and constant pressure water
supply
Please connect the water-level sensor of deep well as shown in Figure4.2.2.
Please install the pressure tank, pressure transmitter and so on to the water pipe and
set the parameter b00.06=5.

10
B6031I Series Deep well Pump Inverter User Manual

4.3 Wiring Main Circuits


4.3.1 Wiring of Main Circuits

B601I
Series

Figure4.3.1 High-performance main circuit wiring


4.3.2 Circuit Breaker
It is necessary to connect a suitable circuit breaker between 3 phase AC power
supply and B603 series intelligent constant water supply controller. The capacity of
breaker is 1.5~2 times to the rated current of controller.
4.3.3 AC Reactor (Optional)
In order to prevent the rectifier damage resulted from the large current, AC
reactor should be installed at the input side. It can also prevent rectifier from sudden
variation of power voltage or harmonic generated by phase-control load.
4.3.4 Input EMC Filter (Optional)
EMC filter can minimize the interference of the surrounding device which may be
disturbed by the cables when the controller is working.
4.3.5 Output EMC Filter (Optional)
EMC filter should be installed to minimize the leak current caused by the cable
and minimize the radio noise caused by the cables between the controller and motor.
4.3.6 Output Reactor
When the distance between the B6031I controller and motor is more than 50m,
the controller may be tripped by over-current protection frequently because of the
large leak current resulted from the parasitic capacitance with ground. So as to avoid
the damage of motor insulation, the output reactor should be installed.

11
B6031I Series Deep well Pump Inverter User Manual

4.3.7 Ground Wiring (PE)


In order to keep safety and prevent electric shock and fire, PE must be grounded
with ground resistance. Furthermore, reliable grounding is the simplest, most
effective and minimum cost solution for EMC problems, so it enjoys priority in all
EMC methods.

5. OPERATION

5.1 Keypad Description

Figure5.1.1 Keypad schematic diagram


5.2 Operation Procedure
5.2.1 The Display Interface Prefix Alphabet Meaning
H: Operating frequency
P: Test value of pump outlet pressure
L: Set value of pump outlet pressure
A: Output current
d: DC-link voltage

12
B6031I Series Deep well Pump Inverter User Manual

5.2.2 Power-on Initialization


Firstly the system initializes during the controller power-on, and LED displays
“CAP-S”. After the initialization is completed, the controller is on stand-by status.
5.2.3 Parameter Setting
Three levels of menu are: 1. Function code group (first-level); 2. Function code
(second-level); 3. Function code setting value (third-level)
▲ At the primary interface, press <</SHIFT or >>/SHIFT will switch over
display running/stop status monitoring parameters;
▲ At the primary interface, press PRG/ESC will enter the first-level menu then
press PRG/ESC will return to the primary interface;
▲ At the first-level menu, press DATA/ENT will enter the second-level menu. In
second-level menu can also press PRG/ESC and DATA/ENT return to
first-level menu or enter third-level menu;
▲ At third-level menu, press both PRG/ESC and DATA/ENT can return to the
second-level menu, difference is: pressing DATA/ENT will save the
parameters into the controller and return to the second-level menu with
shifting to the next function code automatically; while pressing PRG/ESC
will directly return to the second-level menu without saving the parameters,
and keep staying at the current function code.
Example 1: Change factory pressure setting 3.0 bar to 2.5 bar
Method 1: Enter parameter setting
Operation flow chart:

13
B6031I Series Deep well Pump Inverter User Manual

Figure 5.2.1 Operation flow chart


Method 2: Direct setting at the primary interface (constant pressure water supply
mode)
Press △ or ▽ at primary interface, the system will switch-over to display
setting pressure, press △ or ▽ again, the setting pressure increase/decrease, mean
while the system trace the setting pressure. After complete the pressure setting ,
please press DATA/ENT to save the value.
Directly setting constant speed running frequency in the mode of constant speed
is the same as the method of directly setting pressure.
Example 2: During the running of controller, press <</SHIFT or >>/SHIFT to
scroll through the parameters in left or right order until there are two upper lights on,
can check the feedback pressure value.

6. INSTRUCTIONS OF PARAMETERS GROUP


Function Setting Factory
Name Description
Code Range Setting
Br00 Group Application Function
Start/Stop 0: Water-level automatic control through
b00.00 0 0
Control Way keypad start/stop

14
B6031I Series Deep well Pump Inverter User Manual
Function Setting Factory
Name Description
Code Range Setting
Water-level of
Deep Well and
000.0~ Water-level of deep well and upper reservoir
b00.01 Upper Reservoir 50.00Hz
060.00 auto control run frequency value
Auto Controlling
Run Frequency
Pressure Setting 0.0~100.0
b00.02 3.0bar Set according to the actual requirements of user
Value bar
Single phase or three phase motor selection
b00.03 Phase Selection 0~1 1
0: Three phase 1: Single phase
Motor Rotating
b00.04 0~1 0 0: Forward 1: Reverse
Direction
Restart After
b00.05 0~1 1 0: Invalid 1: Valid
Power-on
0: The water-level of deep well and upper
reservoir auto controlling
b00.06 Control Mode 0~6 5
5: The water-level of deep well auto controlling
and constant pressure water supply
Maximum
0.0~100.0 E.g. If the rated max. range of transducer is 10
b00.07 Transducer 16.0bar
bar bar, b00.07 should be set to10.0
Setting Range
When the pressure is higher than this preset
High Water
0.0~100.0 value, the controller alarms, halts and displays
b00.08 Pressure Alarm 10.0bar
bar “HP”; when the pressure is lower than this
Value
preset value, breakdown recover and running
Low Water When the pressure is lower than this preset
0.0~100.0
b00.09 Pressure Alarm 0.5bar value for a Low Pressure Running Time, the
bar
Value controller alarms, halts and displays “LP”;
Low Pressure restart automatically from breakdown after 10
b00.10 00~300s 20s
Running Time minutes’ downtime
000.0~
b00.11 Reserved 000.0 Need to set as 0.000
100.0
b00.12 Reserved 0~30000 0
b00.13 Reserved 01~60 40
0: No action
b00.14 Restore Defaults 0~2 0 1: Set to default
2: Clear error records
Password of Don’t try to enter or will cause abnormal
b00.15 0~65535 00000
Group br08 operation and damages.

15
B6031I Series Deep well Pump Inverter User Manual

7. APPLICATION GUIDANCE

7.1 Wiring and Setting for the Water-level of Deep Well and Upper Reservoir
Auto Controlling

7.1.1 System Wiring

Figure7.1.1 Wiring for the water-level of deep well and upper reservoir auto controlling system

7.1.2 System Debugging Procedure

Figure7.1.2 Debugging Flow Diagram


7.1.3 Relevant Parameter Setting
Sheet 7.1.1 Parameter setting of the water-level of deep well and upper reservoir auto controlling
Function Factory
Recommend Description
Code Setting
Adjust the running frequency value of the water-level of deep
b00.01 50.00 xx.xx well and upper reservoir auto controlling according to the rated
frequency of the motor

16
B6031I Series Deep well Pump Inverter User Manual
Function Factory
Recommend Description
Code Setting
According to the connecting motor setting, the single phase
b00.03 1 x
motor is set to 1, three phase motor is set to 0
Motor rotating direction, set according to the actual motor
b00.04 0 x wiring of spot. Make sure the motor is running in forward
direction
Restart after power-on, considering unattended management, set
b00.05 1 x
to 1
Choose the water-level of deep well and upper reservoir auto
b00.06 5 0
controlling

7.2 Wiring and Setting for the Water-level of Deep Well Auto Controlling and
Constant Pressure Water Supply

7.2.1 System Wiring

Figure7.2.1 Wiring for the water-level of deep well auto controlling and constant pressure water supply system

1) The pressure transmitter of figure7.2.1 is our company two wire current type
pressure transmitter.

17
B6031I Series Deep well Pump Inverter User Manual

7.2.2 System Debugging Procedure

Figure7.2.2 Debugging flow diagram


7.2.3 Relevant Parameter Setting
Sheet 7.2.1 Parameter setting of the water-level of deep well auto controlling and constant pressure water supply
Function Factory
Recommend Description
Code Setting
b00.02 3.0 xx.x Set value of pump outlet pressure
According to the connecting motor setting, the single phase
b00.03 1 x
motor is set to 1, three phase motor is set to 0
Motor rotating direction, set according to the actual motor
b00.04 0 x wiring of spot. Make sure the motor is running in forward
direction
Restart after Power-on, Considering unattended management,
b00.05 1 x
set to 1
Choose the water-level of deep well auto controlling and
b00.06 5 5
constant pressure water supply
Setting according to the rated measuring range of the pressure
b00.07 16.0 xx.x
transmitter
High water pressure alarm value, Prevent system from damage
b00.08 10.0 x.x
caused by high water pressure
Low water pressure alarm value, prevent pump from damage
b00.09 0.5 x.x
caused by an hydrous idling
After running for a preset time when the water pressure is low,
b00.10 20 xxx
the controller halts and alarms to prevent the pump from idling

18
B6031I Series Deep well Pump Inverter User Manual

8. FAULT AND TROUBLE SHOOTING

8.1 Pump Running Fault and Trouble Shooting


Fault
Fault Type Reason Solution
Code
 Check the installation of pressure
transmitter;
1. Abnormal sensor;
 Check the motor whether rotates in
2. Motor rotates in the reverse
Low water right direction;
LP direction;
pressure  Check the parameter b00.09
3. Insufficient water inflow;
(setting value too big);
4. There is air inside the pump
 Check the pump whether is vent
out the air inside
 Check the installation of pressure
1. Abnormal sensor;
High water transmitter;
HP 2. The parameter b00.08 setting
pressure  Check the parameter b00.08
value is too small
(setting value too small)
1. Pressure transmitter
disconnected;  Check the cable between pressure
Sensor
E022 2. Wrong pressure transmitter wiring; transmitter and controller;
fault
3. Pressure transmitter short circuit;  Check the sensor whether is normal
4. Pressure transmitter break down
 Check whether there is water in the
Water 1. No water in the deep well
deep well
A033 shortage 2. Water-level sensors in the deep well
 Check whether the water-level
fault is broken
sensors is broken.

8.2 Controller Running Fault and Trouble Shooting


Fault
Fault Type Reason Solution
Code
IGBT Ph-U
E001 1. Acc/Dec time is too short;
Fault (OUT1)  Increase Acc/Dec time;
2. IGBT module fault;
IGBT Ph-V  Check external equipments and
E002 3. Malfunction caused by
Fault (OUT2) eliminate interference;
interference;
IGBT Ph-W  Ask supplier for support
E003 4. Grounding is not properly
Fault (OUT3)
Over-current 1. Acc time is too short;
 Prolong Acc time;
When 2. Low input voltage;
E004  Check the power supply;
Acceleration 3. The power of controller is
 Select bigger power controller
(OC1) small

19
B6031I Series Deep well Pump Inverter User Manual
Fault
Fault Type Reason Solution
Code
Over-current 1. Dec time is too short;
 Prolong Dec time;
When 2. Load is too heavy;
E005  Increase braking unit;
Deceleration 3. The power of controller is
 Select bigger capacity controller
(OC2) small
Over-current 1. Sudden change of load;
 Check the load;
When Constant 2. Low input voltage;
E006  Check the power supply;
Speed Running 3. The power of controller is
 Select bigger capacity controller
(OC3) small
Over-voltage
1. High input voltage;  Check the power supply;
When
E007 2. Regenerative energy from  Avoid to restart the motor until it
Acceleration
the motor is too large stop running completely
(OV1)
Over-voltage
1. Dec time is too short;  Increase Dec time;
When
E008 2. Load is too heavy;  Increase braking unit;
Deceleration
3. High input voltage  Check the power supply
(OV2)
Over-voltage
When Constant 1. High input voltage;  Install input reactor;
E009
Speed Running 2. Load is too heavy  Increase braking unit
(OV3)
DC Bus
 Check the grid’s input power
E010 Under-voltage 1. Low input voltage
supply
(UV)
2. Low input voltage;
3. Wrong setting of motor  Check the power supply;
parameter;  Set the rated current of motor
Motor Overload 4. Motor locked-rotor or properly;
E011
(OL1) sudden big change of load to  Check the load, adjust the value of
small load; torque boost;
5. The power of motor is too  Select proper power motor
small
1. Acc time is too short;  Prolong Acc time;
2. Restart the motor when it is  Avoid to restart the motor until it
Controller
E012 decelerating; stop running completely;
Overload (OL2)
3. Low input voltage;  Check the power supply;
4. Load is too heavy  Select bigger capacity controller
Input Phase Open-phase occurred in power Check the wiring, installation and the
E013
Failure (SPI) supply power supply
Output Phase Open-phase occurred at output Check the output wiring, cable and
E014
Failure (SPO) side of main circuit motor

20
B6031I Series Deep well Pump Inverter User Manual
Fault
Fault Type Reason Solution
Code
1. Sudden over-current;
2. Input/output side has short
circuit;
Rectify 3. Cooling fans of controller
E015 stopped or damaged;  Refer to measures of over-current;
Overheat (OH1)
4. Ambient temperature is too  Check the wiring;
high;  Replace cooling fans;
5. Wires or connectors of  Decrease the ambient
control board are loose; temperature;
6. Auxiliary power supply unit  Check and reconnect;
is damaged or low driving  Ask supplier for support
IGBT Overheat voltage for IGBT;
E016
(OH2) 7. Power module bridge is
damaged;
8. Control board is abnormal
E018 Reserve
1. Wires or connectors of
control board are loose;
Current 2. Auxiliary power supply unit
 Check the wiring and connectors;
E019 Detection Fault is damaged;
 Ask supplier for support
(ITE) 3. Current detector is damaged
or amplifying circuit is
abnormal
E020 Reserve

EEPROM  Press STOP/RST to reset;


E021 R/W fault of control parameters
Fault(EEP)  Ask for support

21