Schedule-10 /Schedule-40 ® ®
• Welded Outlets FM
• Hydrostatic Pressure
Listed Approved Listed
• Side Wall Rupture
• Vibration Test
16100 S. Lathrop • Harvey, IL 60426 Customer Service:
11350 Norcom Rd. • Philadelphia, PA 19154 (800) 882-5543
2525 N. 27 th Ave. • Phoenix, AZ 85009 Fax 708-339-1806
S5 - 3
Victaulic® FireLock™ Fittings
10.03
2.0 CERTIFICATION/LISTINGS
EN 10311
Regulation (EU)
No. 305/2011
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
victaulic.com
10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved.
1
victaulic.com
4.0 DIMENSIONS
C to E C
to E
C to E
T
C C
to
to E E
10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 2
IPS CARBON STEEL PIPE
FIRE PROTECTION PRODUCTS 10.02
R
Style 005
FireLockTM
Rigid Coupling
with Vic-Plus Gasket System
TM
PRODUCT DESCRIPTION
FireLock™ Style 005 rigid Sprinkler Systems. Angle- ONLY on fire protection
coupling has a unique, pat- pad design permits assem- systems.
ented angle-pad design bly by removing one nut/
Vic-Plus Gasket System:
which allows the housings bolt and swinging the
Victaulic® now offers a gas-
to offset while clamping the housing over the gasket.
ket system which requires
grooves. By permitting the This reduces components
no field lubrication. The
housings to slide on the to handle during assembly;
Vic-PlusTM System (patent
angled bolt pads, rigidity is speeds and eases installa-
pending) is dry, clean, and
obtained. tion on pipe grooved to
non-toxic. It reduces
Patented Victaulic specifications.
The FireLock couplings assembly time substantially
provide rigidity for valve Style 005 FireLock cou- and eliminates the mess
connections, fire mains and plings with the Vic- and chance of
long straight runs. Support PlusTM Gasket System over-lubrication.
and hanging requirements are designed and rec-
correspond to NFPA 13 ommended for use
10.02-1D
DIMENSIONS SIZE
Nominal
Max.
Work.
Max.
End
Allow.
Pipe End @ Bolt/Nut
Dimensions
Inches/mm Aprx.
Inches Press. § Load Sep. † No. - Size Wgt. Ea.
Y Z PSI*/kPa Lbs.*/N In./mm Inches/mm X Y Z Lbs./kg
Actual mm
1¹⁄₄ 350 755 0.05 2.75 4.50 1.88 1.2
42,4 2413 3370 1,2 2 - ³⁄₈ ✕ 2 70 114 148 0,5
X 1¹⁄₂ 350 990 0.05 3.00 4.75 1.88 1.2
48,3 2413 4415 1,2 2 - ³⁄₈ ✕ 2 76 121 148 0,5
2 350 1550 0.07 3.50 5.25 1.88 1.6
60,3 2413 6900 1,7 2 - ³⁄₈ ✕ 2¹⁄₂ 89 133 148 0,7
Rated for wet and dry sprinkler 2¹⁄₂ 350 2270 0.07 4.00 5.75 1.88 1.9
systems at 350 PSI (2413 kPa) for 73,0 2413 10110 1,7 2 - ³⁄₈ ✕ 2¹⁄₂ 102 146 148 0,9
1¹⁄₄ - 4" (42,4 - 114,3 mm) sizes 350 2475 0.07 4.13 5.75 1.88 1.9
and 300 PSI (2068 kPa) for 4¹⁄₄ - 76,1 mm 2413 11010 1,7 2 - ³⁄₈ ✕ 2¹⁄₂ 105 146 148 0,9
8" (108,0 - 219,1 mm) sizes; 3 350 3365 0.07 4.63 6.13 1.88 2.1
Schedule 10 roll grooved or 88,9 2413 14985 1,7 2 - ³⁄₈ ✕ 2¹⁄₂ 118 156 148 1,0
Schedule 40 cut or roll grooved 4 350 5565 0.16 5.75 7.25 2.13 3.1
114,3 2413 24770 4,1 2 - ³⁄₈ ✕ 2¹⁄₂ 146 184 54 1,4
steel pipe. Style 005 is rigid and
does not accommodate expan- 300 4255 0.16 5.63 7.25 2.13 3.1
108,0 mm 2068 18940 4,1 2 - ³⁄₈ ✕ 2¹⁄₂ 143 184 54 1,4
sion, contraction or angular
deflection. 5 300 7290 0.16 6.88 9.00 2.13 4.5
141,3 2068 32445 4,1 2 - ¹⁄₂ ✕ 2³⁄₄ 175 229 54 2,0
300 6495 0.16 6.63 9.00 2.13 4.5
133,0 mm 2068 28900 4,1 2 - ¹⁄₂ ✕ 2³⁄₄ 168 229 54 2,0
300 7125 0.16 6.88 9.00 2.13 4.8
139,7 mm 2068 31715 4,1 2 - ¹⁄₂ ✕ 2³⁄₄ 175 229 54 2,2
6 300 10340 0.16 8.00 10.00 2.13 5.0
168,3 2068 46020 4,1 2 - ¹⁄₂ ✕ 2³⁄₄ 203 254 54 2,3
300 9200 0.16 7.63 10.00 2.13 5.5
159,0 mm 2068 40955 4,1 2 - ⁵⁄₈ ✕ 4¹⁄₄ 194 254 54 2,5
300 9955 0.16 8.15 10.00 2.13 5.5
165,1 mm 2068 44295 4,1 2 - ¹⁄₂ ✕ 2³⁄₄ 207 254 54 2,5
8 300 17525 0.19 10.50 13.13 2.63 11.3
219,1 2068 78000 4,8 2 - ⁵⁄₈ ✕ 4¹⁄₄ 267 334 67 5,1
* @ § † Refer to notes on page 2.
Victaulic® World Headquarters • P.O. Box 31, Easton, PA 18044-0031 • 4901 Kesslersville Rd., Easton, PA 18040 • 1-800-PICK VIC • FAX: 610/250-8817 • www.victaulic.com
1538 Rev.E 10/00 ® Registered Trademark of Victaulic © Copyright 1999 Victaulic Printed in U.S.A.
IPS CARBON STEEL PIPE
R
GROOVED COUPLINGS 06.05
Style 75
Coupling
PRODUCT DESCRIPTION
Style 75 is available where the Style 77, the Style 75 two identical pieces in all
moderate pressures are coupling is recommended sizes. Hot-dip galvanized
expected or weight consid- for service up to 500 psi and special coatings are
erations are a factor. Up to (3450 kPa) depending on available for all sizes.
50% lighter in weight than size. Housings are cast in
UL
®
ULC
FM
See Victaulic
publication 10.01
for details.
UL
®
ULC
FM
See Victaulic
publication 10.01
for details.
Exaggerated for clarity
1536 Rev.D 6/02 ® Registered Trademark of Victaulic © Copyright 2002 Victaulic Printed in U.S.A.
COOPLET®
Weld Outlets & Adapter Nipples
COOPLET® Threaded Weld Outlets - 300#
B
All Grooves are Cut Grooved
207 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX (323) 890-4456 • www.smithcooper.com
COOPLET® Grooved Weld Outlets - 300#
Bevel
37-1/2°
B
SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX (323) 890-4456 • www.smithcooper.com 208
FireLock™ V34, K8.0
Models V3401, V3402, V3405, V3406 40.15
2.0 CERTIFICATION/LISTINGS
0786
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
victaulic.com
40.15 2547 Rev M Updated 01/2020 © 2020 Victaulic Company. All rights reserved.
1
victaulic.com
Model
APPROVALS/LISTINGS
V3401 V3402 V3405 V3405 V3406 V3406 V3406
17/32” 17/32” 17/32” 17/32” 17/32” 17/32” 17/32”
Orifice Size (inches)
Orifice Size (mm) 14 14 14 14 14 14 14
Nominal K-Factor Imperial 8.0 8.0 8.0 8.0 8.0 8.0 8.0
Nominal K-Factor S.I. 2 11.5 11.5 11.5 11.5 11.5 11.5 11.5
Response Standard Quick Standard Standard Quick Quick Quick
Recessed Recessed Recessed
Deflector Type Upright Upright Pendent Pendent
Pendent Pendent Pendent
Adjustment up to ¾” up to ½” up to ¾”
Approved Temperature Ratings F°/C°
135°F/57°C 135°F/57°C
135°F/57°C 135°F/57°C 135°F/57°C
155°F/68°C 155°F/68°C
155°F/68°C 155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C
175°F/79°C 175°F/79°C
cULus 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C
200°F/93°C 200°F/93°C
200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C
286°F/141°C 286°F/141°C
286°F/141°C 286°F/141°C 286°F/141°C
360°F/182°C 360°F/182°C
135°F/57°C 135°F/57°C
135°F/57°C 135°F/57°C
155°F/68°C 155°F/68°C 135°F/57°C
155°F/68°C 155°F/68°C 135°F/57°C
175°F/79°C 175°F/79°C 155°F/68°C
FM 175°F/79°C 175°F/79°C 175°F/79°C None
200°F/93°C 200°F/93°C 175°F/79°C
200°F/93°C 200°F/93°C 200°F/93°C
286°F/141°C 286°F/141°C 200°F/93°C
286°F/141°C 286°F/141°C
360°F/182°C 360°F/182°C
135°F/57°C 135°F/57°C
135°F/57°C 135°F/57°C 135°F/57°C
155°F/68°C 155°F/68°C
155°F/68°C 155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C
175°F/79°C 175°F/79°C
NYC/MEA # 62-99-E 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C
200°F/93°C 200°F/93°C
200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C
286°F/141°C 286°F/141°C
286°F/141°C 286°F/141°C 286°F/141°C
360°F/182°C 360°F/182°C
135°F/57°C 135°F/57°C
135°F/57°C 135°F/57°C 135°F/57°C
155°F/68°C 155°F/68°C
155°F/68°C 155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C
175°F/79°C 175°F/79°C
CSFM # 7690-0531:112 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C
200°F/93°C 200°F/93°C
200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C
286°F/141°C 286°F/141°C
286°F/141°C 286°F/141°C 286°F/141°C
360°F/182°C 360°F/182°C
135°F/57°C 135°F/57°C
135°F/57°C 135°F/57°C
155°F/68°C 155°F/68°C 135°F/57°C
155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C
175°F/79°C 175°F/79°C 155°F/68°C
GOST-R 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C
200°F/93°C 200°F/93°C 175°F/79°C
200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C
286°F/141°C 286°F/141°C 200°F/93°C
286°F/141°C 286°F/141°C
360°F/182°C 360°F/182°C
135°F/57°C
135°F/57°C
155°F/68°C
155°F/68°C
175°F/79°C
VdS 175°F/79°C None None None None None
200°F/93°C
200°F/93°C
286°F/141°C
286°F/141°C
360°F/182°C
135°F/57°C
135°F/57°C
155°F/68°C
155°F/68°C
175°F/79°C
CE 175°F/79°C None None None None None
200°F/93°C
200°F/93°C
286°F/141°C
286°F/141°C
360°F/182°C
135°F/57°C
135°F/57°C
155°F/68°C
155°F/68°C
175°F/79°C
LPCB 175°F/79°C None None None None None
200°F/93°C
200°F/93°C
286°F/141°C
286°F/141°C
360°F/182°C
155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C
CCC
286°F/141°C 286°F/141°C 286°F/141°C 286°F/141°C 286°F/141°C 286°F/141°C 286°F/141°C
2 For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0
NOTE
• Listings and Approvals as of printing. All are approved open.
40.15 2547 Rev M Updated 01/2020 © 2020 Victaulic Company. All rights reserved.
victaulic.com 2
victaulic.com
NOTE
• Weather resistant recessed escutcheons available upon request.
40.15 2547 Rev M Updated 01/2020 © 2020 Victaulic Company. All rights reserved.
victaulic.com 3
victaulic.com
4.0 DIMENSIONS
17⁄16"/
37 mm
2½"/
64 mm
1¾"/ 1¾"/
45 mm 45 mm
2½"/
64 mm
15⁄16"/
33 mm
2 3⁄8"/60 mm
Max. Hole
2"/51 mm
Min. Hole
11⁄8"/
11⁄16"/ 5⁄8"/ 29 mm
18 mm 16 mm Typical Ceiling Tile
13⁄8"/
17⁄8"/ Finished Surface 34 mm
47 mm
MAXIMUM RECESS
2 15⁄16"/75 mm
MAXIMUM EXTENSION
23⁄8"/60 mm
Max. Hole
2"/51 mm
Min. Hole
13⁄8"/
15⁄16"/ 35 mm
24 mm 5⁄8"/
16 mm Typical Ceiling Tile
11⁄8"/
17⁄8"/ 29 mm
Finished Surface
48 mm
MAXIMUM RECESS
215⁄16"/75 mm
MAXIMUM EXTENSION
5.0 PERFORMANCE
Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards.
40.15 2547 Rev M Updated 01/2020 © 2020 Victaulic Company. All rights reserved.
victaulic.com 4
victaulic.com
6.0 NOTIFICATIONS
WARNING
• Read and understand all instructions before attempting to install any Victaulic
products.
• Always verify that the piping system has been completely depressurized and
drained immediately prior to installation, removal, adjustment, or maintenance of
any Victaulic products.
• Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious personal injury
and property damage.
• These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable
National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable
building and fire codes. These standards and codes contain important information regarding protection of systems from freezing
temperatures, corrosion, mechanical damage, etc.
• The installer shall understand the use of this product and why it was specified for the particular application.
• The installer shall understand common industry safety standards and potential consequences of improper product installation.
• It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system
and external environment.
• The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level,
and flow rate on materials to confirm system life will be acceptable for the intended service.
Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system
failure, resulting in death or serious personal injury and property damage.
40.15 2547 Rev M Updated 01/2020 © 2020 Victaulic Company. All rights reserved.
victaulic.com 5
victaulic.com
Temperature – ºF/ºC
Maximum
Sprinkler Victaulic Nominal Ambient Glass
Temperature Part Temperature Temperature Bulb
Classification Identification Rating Allowed Color
Ordinary A 135ºF/57ºC 100ºF/38ºC Orange
– M Open – No bulb
Available Wrenches:
V34 V34
Sprinkler Type
Recessed Open End
40.15 2547 Rev M Updated 01/2020 © 2020 Victaulic Company. All rights reserved.
victaulic.com 6
Fire Protection FPS-13
Fire protection
solutions
Pipe Hangers
Fig. 2 - Adjustable Band Hanger (B-Line B3170)
Fig. 2F - Adjustable Band Hanger Felt Lined for Copper Tubing (B-Line B3170F)
Size Range:
Fig. 2 - 21/2” (65mm) thru 6” (150mm) pipe
Fig. 2F - 21/2” (65mm) thru 6” (150mm) pipe
C
Material: Pre-Galvanized Steel
B
Function: Recommended for the suspension of non-
insulated pipe or insulated pipe with B3151 shield.
Fig. 2NFPA accomodates the reduced rod schedule of
the National Fire Pretection Association Pamphlet 13. D
D
Fig. 2F
Pipe Hangers
Fig. 2
Nominal Pipe Size Rod Size B C D Max. Rec. Load Approx Wt./100
Part No. in. (mm) A in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kg)
2-21/2 21/2" (65) 1/2"-13 * 53/4" (146.0) 41/4" (107.9) 15/8" (41.3) 600 (2.67) 41 (18.6)
2-3 3" (75) 1/2"-13 * 6" (152.4) 41/8" (104.8) 11/4" (31.7) 600 (2.67) 45 (20.4)
2-31/2 31/2" (90) 1/2"-13 * 73/8" (187.3) 51/4" (133.3) 21/8" (54.0) 600 (2.67) 52 (23.6)
2-4 4" (100) 5/8"-11 * 73/8" (187.3) 5" (127.0) 15/8" (41.3) 1000 (4.45) 59 (27.6)
2-5 5" (125) 5/8"-11 ** 9" (228.6) 61/8" (155.6) 21/4" (57.1) 1250 (5.56) 97 (44.0)
2-6 6" (150) 3/4"-10 ** 93/8" (238.1) 61/2" (165.1) 17/8" (47.6) 1250 (5.56) 139 (63.0)
Fig. 2F
Nominal Pipe Size Rod Size B C D Max. Rec. Load Approx Wt./100
Part No. in. (mm) A in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kg)
2F-21/2 21/2" (65) 1/2"-13 * 53/4" (146.0) 41/4" (107.9) 15/8" (41.3) 600 (2.67) 41 (18.6)
2F-3 3" (75) 1/2"-13 * 6" (152.4) 41/8" (104.8) 11/4" (31.7) 600 (2.67) 45 (20.4)
2F-31/2 31/2" (90) 1/2"-13 * 73/8" (187.3) 51/4" (133.3) 21/8" (54.0) 600 (2.67) 52 (23.6)
2F-4 4" (100) 5/8"-11 * 73/8" (187.3) 5" (127.0) 15/8" (41.3) 1000 (4.45) 59 (27.6)
2F-5 5" (125) 5/8"-11 ** 9" (228.6) 61/8" (155.6) 21/4" (57.1) 1250 (5.56) 97 (44.0)
2F-6 6" (150) 3/4"-10 ** 93/8" (238.1) 61/2" (165.1) 17/8" (47.6) 1250 (5.56) 139 (63.0)
* 3/8 nut is used when requested. ** 1/2 nut is used when requested.
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
ATR - All Threaded Rod - 120” (3.05m) Lengths (TOLCO Fig. 100)
Fig. 99 - All Threaded Rod Cut To Length
Size Range: 3/8"-16 thru 11/2"-6 rod in 120” lengths or cut to length
Threaded Accessories
Material: Steel
Maximum Temperature: 750°F (399°C)
Finish: Plain or Electro-Galvanized. Contact B-Line for alternative finishes and materials.
Order By: Figure number, rod size, length and finish
Part No. - Size x Length Threads Recommended Load Approx. Wt./100 Ft.
ATR Fig. 99 Per Inch Lbs. (kN) Lbs. (kg)
ATR 1/4” x 120 99-1/4” x length 20 240 (1.07) 12 (5.44)
ATR 3/8” x 120 99-3/8” x length 16 730 (3.24) 29 (13.15)
ATR 1/2” x 120 99-1/2” x length 13 1350 (6.00) 53 (24.04)
ATR 5/8” x 120 99-5/8” x length 11 2160 (9.60) 89 (40.37)
ATR 3/4” x 120 99-3/4” x length 10 3230 (14.37) 123 (55.79)
ATR 7/8” x 120 99-7/8” x length 9 4480 (19.93) 170 (77.11)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B656-3/8 x 1/4 3/8"-16 & 1/4"-20 1" (25.4) 300 (1.33) 3.7 (1.68)
B656-1/2 x 3/8 1/2"-13 & 3/8"-16 11/4" (31.7) 730 (3.25) 6.6 (2.99)
B656-5/8 x 1/2 5/8"-11 & 1/2"-13 11/4" (31.7) 1350 (6.00) 11.6 (5.26)
B656-3/4 x 5/8 3/4"-10 & 5/8"-11 11/2" (38.1) 2160 (9.61) 20.6 (9.34)
B656-7/8 x 3/4 7/8"-9 & 3/4"-10 13/4" (44.4) 3230 (14.37) 39.4 (17.87) B656
Hanger Rod
Size Range: 3/8"-16 thru 1"-8 rod
Not Included
Material: Malleable Iron
Overall
Function: Used for coupling two threaded rods together Length
of equal rod sizes, with inspection hole.
Finish: Electro-Galvanized. Contact B-Line for alternative finishes
and materials.
Order By: Figure number and finish
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
7158 3/8” Vertical 1/4-20 x 1" #3 4” 0.060” 1,500 lbs 0.096” 1,475 lbs
7184 3/8” Side 1/4-20 x 1" #3 4” 0.060” 1,500 lbs 0.096” 1,475 lbs
7160 3/8” Vertical 1/4-20 x 1-1/2" #3 4” 0.060” 1,500 lbs 0.096” 1,475 lbs
7186 3/8” Side 1/4-20 x 1-1/2" #3 4” 0.060” 1,500 lbs 0.096” 1,475 lbs
7154 3/8” Vertical 12-24 x 1-1/2" #5 4” 0.060” 1,500 lbs 0.096” 1,475 lbs
7188 3/8” Side 1/4-20 x 2" #3 4” 0.060” 1,500 lbs 0.096” 1,475 lbs
7201 3/8” Side 12-24 x 1-1/2" #5 4” 0.060” 1,500 lbs 0.096” 1,475 lbs
7164 1/2” Vertical 12-24 x 1-1/2" #5 8” 0.250” 4,050 lbs 0.250” 3,800 lbs
Steel Vertigo is recommended to be installed with the Universal Steel & Wood Nut Driver. For UL and FM listings, Steel Vertigo must be installed with a retaining nut.
WOOD VERTIGO
ANCHOR SIZE/ MOUNT SCREW SHANK EMBED. UL MAX. UL TEST FM MAX. FM TEST
CAT NO. ROD DIA. DIRECTION SIZE & LENGTH DEPTH PIPE SIZE LOAD PIPE SIZE LOAD
CONCRETE VERTIGO
ANCHOR SIZE/ MOUNT SCREW SHANK ANSI DRILL EMBEDMENT FM MAX. FM TEST
CAT NO. ROD DIA. DIRECTION SIZE & LENGTH BIT DIAM. DEPTH PIPE SIZE LOAD
Vertigo™ Approval Summary
Depending on fastener application and governing building code, the ultimate load capacities should be reduced by a minimum safety factor to determine the allowable working load.
NFPA 13 Fire protection fastening requirements are five times the weight of the liquid (water) filled pipe plus 250 lbs. Consult the engineer of record.
8
H A N G I N G S Y S T E M
A One Piece Self-drilling Screw Style Mechanical Anchor (Steel and Wood)
✁
P R O J E C T S U B M I T TA L
P R O D U C T A P P R O VA L S A N D L I S T I N G S
Project Submittal
Factory Mutual Research Corporation (FM Approvals) - File No. J.I. 3015153
Underwriters Laboratories (UL) - File No. EX1289
International Conference of Building Officials (ICBO) - Pending