Overview list
Protection
This setup menu consists of the protection setup.
1020 Overcurrent 1
No. Setting Min. setting Max. setting Factory
setting
1021 Overcurrent 1 Setpoint 50.0% 200.0% 115.0%
1022 Overcurrent 1 Time 0.10 s 100.00 s 10.00 s
1023 Overcurrent 1 Relay output A R0 (none) Option R2 (relay 2)
1024 Overcurrent 1 Relay output B R0 (none) dependent R0 (none)
1025 Overcurrent 1 Enable OFF ON ON
1030 Overcurrent 2
No. Setting Min. setting Max. setting Factory
setting
1031 Overcurrent 2 Setpoint 50.0% 200.0% 120.0%
1032 Overcurrent 2 Time 0.10 s 100.00 s 5.00 s
1033 Overcurrent 2 Relay output A R0 (none) Option R1 (relay 1)
1034 Overcurrent 2 Relay output B R0 (none) dependent R0 (none)
1035 Overcurrent 2 Enable OFF ON ON
Control
This setup menu consists of the synchronisation setup and the regulation setup.
Input
This menu consists of parameters for configuration of the inputs.
System
The menu includes parameters for the system setup.
4040 Controller
No. Setting Min. setting Max. setting Factory
setting
4041 Controller Power -100% 100% 100%
4042 Controller VAr -100% 250% 30%
4043 Controller Power factor (ind.) 0.60 1.00 0.90
4044 Controller Water level 0% 250% 100%
regulation
4121 Counters
No. Setting Min. setting Max. setting Factory
setting
4121 Counters Running time 0 20000 0
4122 Counters CB operations 0 20000 0
4123 Counters Reset kWh counter OFF ON OFF
4230 Language
No. Setting Factory
setting
4231 Language English English
Deutsch -
Français -
Español -
4590 Horn
No. Setting Min. setting Max. setting Factory
setting
4591 Horn Time 0.0 s 999.9 s 0.0 s
4592 Horn Enable OFF ON OFF
4610 Relay 1
No. Setting First/min. Second/max. Third Factory
setting setting setting setting
4611 Relay 1 Function Alarm Alarm/sync. Limit Alarm
Block - reset
4612 Relay 1 Off delay 0.0 s 999.9 s - 5.0 s
4620 Relay 2
No. Setting First/min. Second/max. Third Factory
setting setting setting setting
4621 Relay 2 Function Alarm Alarm/sync. Limit Alarm
Block – reset
4622 Relay 2 Off delay 0.0 s 999.9 s - 5.0 s
4630 Relay 3
No. Setting First/min. Second/max. Third Factory
setting setting setting setting
4631 Relay 3 Function Alarm Alarm/sync. Limit Alarm
Block – reset
4632 Relay 3 Off delay 0.0 s 999.9 s - 5.0 s
4640 Relay 4
No. Setting First/min. Second/max. Third Factory
setting setting setting setting
4641 Relay 4 Function Alarm Alarm/sync. Limit Alarm
Block – reset
4642 Relay 4 Off delay 0.0 s 999.9 s - 5.0 s
4650 Relay 5
No. Setting First/min. Second/max. Third Factory
setting setting setting setting
4651 Relay 5 Function Alarm Alarm/sync. Limit Alarm
Block – reset
4652 Relay 5 Off delay 0.0 s 999.9 s - 5.0 s
4660 Relay 6
No. Setting First/min. Second/max. Third Factory
setting setting setting setting
4661 Relay 6 Function Alarm Alarm/sync. Limit Alarm
Block – reset
4662 Relay 6 Off delay 0.0 s 999.9 s - 5.0 s
4670 Relay 7
No. Setting First/min. Second/max. Third Factory
setting setting setting setting
4671 Relay 7 Function Alarm Alarm/sync. Limit Alarm
Block – reset
4672 Relay 7 Off delay 0.0 s 999.9 s - 5.0 s
4680 Relay 8
No. Setting First/min. Second/max. Third Factory
setting setting setting setting
4681 Relay 8 Function Alarm Alarm/sync. Limit Alarm
Block – reset
4682 Relay 8 Off delay 0.0 s 999.9 s - 5.0 s
Jump button
A number of menus can only be entered using the jump menu.
This is the backup password. If it is changed keep the new password in a safe
place.
6100 Application
No. Setting Description Factory setting
6100 Application Mode 0 Normal (3 phase) Normal (3 phase)
6100 Application Mode 1 Split phase -
6100 Application Mode 2 Single phase -