Don’t design an open office

www.unitileindia.com with a closed floor.

In today's world with demanding work environment and people being result driven; Time is critical,

Technology is crucial and CORPORATE IMAGE is all important. The need of the hour is OPTIMAL usage of

SPACE with FLEXIBILITY being the key word.

Intelligent offices are dependent on sophisticated electronic equipments. With the rapidly changing

technology, optimum operation of these equipments requires not only wires, cables, temperature and

environmental controls but also quick access to services for relocation, expansion or upgradation.

Paradigm-B
Mumbai

..........
UNITILE ACCESS FLOOR SYSTEMS

UNITILE Access floors have the ability to adapt as technology progresses or business needs change. It provides the

easiest of installations, structural integrity and safety. A range of finishes available ensure an aesthetically excellent floor

with high performance, guaranteeing exceptional value for money.

UNITILE Access floors create a plenum space, where high concentrations of power / data cabling and other mechanical

services are concealed between the building floor slab and the raised access floor.

These underfloor services remain easily accessible due to the modular design of raised access floor system,

thus reducing reconfiguration costs and time of the distribution of critical building services.

UNITILE SOLID FILL UNITILE WOOD CORE UNITILE PERFORATED & GRATING

UNITILE Solid fill (USF) Panels : UNITILE Wood core (UWC) Panels : UNITILE Perforated & Grating Panels :
USF panels measure 600mm x 600mm. The panels are 600 x 600mm square with a Perforated and Grating Panels use the
Panels are resistance welded before being high-density chipboard core fully bonded underfloor plenum to deliver over twice the
filled with a lightweight cementi- and encapsulated within a casing of CFM of average floor tiles with a minimum
tious infill. Each panel has hemispherical corrosion-resistant galvanized steel. The open area of 26 & 46 % respectively. They are
reinforcing pockets on the underside to panels are engineered to fine dimensional easily interchangeable with solid panels and
enhance structural strength. USF panels are tolerances for modular control, accurate increase the ability to manage airflow
non-combustible and are coated with alignment of grids and inter-changeability of requirements & heat density by providing
electrostatic epoxy paint. The USF panels panels and also for prevention of creep. superior cooling and ventilation for critical
may be fitted into any UNITILE under- applications. UNITILE Perforated & Grating
structure and a wide range of floor coverings Panels come with a factory applied epoxy
are available. powder coat finish to prevent corrosion and
is available in standard or heavy duty load
ratings with or without dampers and their
surface covering finish is tailored to match
finish of the solid panel.
.....Ž.....
www.unitileindia.com

A few inches can give a business


room to grow
The under-structure is the load bearing element on
which the access floor panels rest. It allows the floor to
be installed at heights of between 65mm and 1000mm
or more in special cases. Unitile under-structures
ensure rigidity, lateral stability and quiet performance
with a solid, secure feel under the feet. All systems and
under-structures offer an exceptionally high degree of
accessibility.

UNITILE ACCESS FLOOR UNDERSTRUCTURE


A comprehensive variety of under-structures to suit various Unitile panels is available
to meet all the differing requirements in each industry.

+ Edge Support Rigid Grid System


Edge support under-structure provides maximum floor
stability. It reduces all lateral movements and also
ensures integrity of the floor on removal of panels for
access to services in the sub-floor. Stringers are
mechanically fastened to the pedestal head and panels
are then placed on the grid formed. This system is ideal
for high finished floor heights.

+ Snap Lock Rigid Grid System


Snap lock under-structure is suitable for general office
and computer room applications. It provides high
stability by utilizing stringers which hold the floor and
pedestal head in position when panels are removed.
Stringers snap on and off without tools.

..........
+ Corner - Lock System
This system is suitable for the widest variety of office applications.
Each floor panel is mechanically secured to the pedestal head at all
four corners ensuring maximum rigidity and lateral stability. Access
to the sub-floor is very simply achieved by releasing the fasteners
and lifting the panel.
+ Low - Lock System
Identical performance features as the UNITILE Corner lock system,
used for finished floor height as low as 65mm. With this system the
range of vertical adjustment is therefore limited.
+ Gravity Lay System (Woodcore)
The under-structure system suitable for high density woodcore
panels encapsulated in GI can be Gravity lay or Rigid grid. Access
to the sub-floor is very simply achieved by lifting the panels directly,
suitable for a finished floor height of upto 1000mm.
+ Corner Lock System (Woodcore)
The pedestal head of the Corner lock understructure is unique in
design and this system can accommodate bare panel without
stringers. It is provided with in built locator to lock the panel bottom
in position avoiding lateral movements. Corner lock systems are
normally used for open office plans and large perimeter areas and
are suitable for a maximum finished floor height of up to 1000mm.
..........
UNITILE ACCESS FLOOR - SYSTEM SELECTION GUIDE
PANEL DIMENSION : 600 X 600 MM / 600 X 400 MM (FOR CEMENTITIOUS PANEL ONLY)
PANEL TYPE OF CONCENTRATED ULTIMATE UNIFORM ROLLING* PEDESTAL RANGE OF
UNDER LOAD CONCENTRATED DISTRIBUTED LOAD AXIAL FINISHED FLOOR
STRUCTURE - LOAD LOAD - LOADING HEIGHT
Kgs (lbf) Kgs (lbf) Kgs /Sqmt Kgs (lbf) Kgs (lbf) (FFH)
(Minimum) (lbf/Sqft)
UNITILE - CEMENTITIOUS PANELS
INTERMEDIATE LOADS
USF - 800 CORNER LOCK (CL) 360 (800) 900 (2000) 1080 (220) 180 (400) 2200 (4840) 65-1000 MM
EDGE SUPPORT RIGID GRID
(ESRG) 360 (800) 900 (2000) 1080 (220) 180 (400) 2200 (4840) 65-1000 MM
SNAP LOCK RIGID GRID
(SLRG) 360 (800) 900 (2000) 1080 (220) 180 (400) 2200 (4840) 225-450 MM
USF - 1000 CORNER LOCK (CL) 450 (1000) 1125 (2500) 1350 (275) 225 (500) 2200 (4840) 65-1000 MM
EDGE SUPPORT RIGID GRID
(ESRG) 450 (1000) 1125 (2500) 1350 (275) 225 (500) 2200 (4840) 65-1000 MM
SNAP LOCK RIGID GRID
(SLRG) 450 (1000) 1125 (2500) 1350 (275) 225 (500) 2200 (4840) 225-450 MM
HEAVY DUTY LOADS
USF - 1200 CORNER LOCK (CL) 540 (1200) 1350 (3000) 1620 (330) 270 (590) 2200 (4840) 65-1000 MM
EDGE SUPPORT RIGID GRID
(ESRG) 540 (1200) 1350 (3000) 1620 (330) 270 (590) 2200 (4840) 65-1000 MM
USF - 1500 CORNER LOCK (CL) 675 (1500) 1690 (3750) 2025 (410) 315 (690) 2200 (4840) 65-1000 MM
EDGE SUPPORT RIGID GRID 675 (1500) 1690 (3750) 2025 (410) 315 (690) 2200 (4840) 65-1000 MM
UNITILE GI ENCAPSULATED WOOD / CALCIUM SILICATE CORE PANELS
INTERMEDIATE LOADS
UWC - LIGHT GRADE CORNER LOCK (CL) 150 450 670 - 1080 100-1000 MM
UWC - MEDIUM GRADE CORNER LOCK (CL) 300 900 800 - 1800 100-1000 MM
EDGE SUPPORT RIGID GRID
(ESRG) 300 900 800 - 1800 100-1000 MM
HEAVY DUTY LOADS
UWC - HEAVY DUTY CORNER LOCK (CL) 450 1350 1200 - 1800 100-1000 MM
EDGE SUPPORT RIGID GRID
(ESRG) 450 1350 1200 - 1800 100-1000 MM
UWC - EXTRA HEAVY CORNER LOCK (CL) 450 1350 1200 - 1800 100-1000 MM
DUTY
EDGE SUPPORT RIGID GRID
(ESRG) 450 1350 1200 - 1800 100-1000 MM
NOTE :Extra Heavy Duty : This grade is also required to sustain a total load of 11 KN applied equally on 4 points, each point 25mm sq. on a 200 mm x 200 mm square
configuration at any point on the system. This system shall have a factor of safety TWO times for 5 minuets without collapse.
*ROLLING LOAD IMPOSED THROUGH WHEEL OF 6" Dia x 2 " WIDTH, MADE OF MOULDED URETHANE TREAD, AT THE CENTER OF THE PANEL FOR 10,000 PASSES
NOTE :
1. Panels with higher Ultimate Loading / Safety factor can also be made available, contact sales for further details.
2. Higher finished floor height systems of upto 1500mm are also available.
3. All the above specifications of UNITILE cementitious panels ( USF) are conforming to MASTERSPECS -USA ( 096900 - Section 10270 ) and test methods as recommended by CISCA.
4. All the specifications of UNITILE GI encapsulated wood / Calcium silicate core panels (UWC/WCS) are conforming to MOB PF2 PS - UK and its recommended test methods.
5. Fire performance: As per BS 476: Part 6: Index of Performance(Class 1) and BS 476: Part 7: Spread of Flame(Class 0).
6. The uniform load rating of an access floor panel as specified here should not be confused with the "Uniform live load" as specified in seismic zone application.
7. It is our constant endeavour to enhance the product quality and performance standards of the above systems for our valued customers, which may lead to change in product specification without any notice or intimation.

.....‘.....
Floor Surface Finishes :
The covering of the panel is subject to wear and tear by usage and the finish has to be
selected depending on the application and traffic the floor would be subjected to.
The top surface of each panel may be covered with a variety of either loose lay at site
or permanently factory bonded finishes.
Conductive : Static Dissipative : Anti Static Laminate :
(PVC) (PVC/HPL) (HPL)
Thickness : 2.0 & 3.0mm Thickness : 2.00 mm(PVC), Thickness : 1.5mm
*Resistivity Range : 1.5mm(Laminate) * Resistivity Range :
2.4 x 104-1 x 106 Ohms *Resistivity Range : 1x109-2x1010 Ohms
1x106- 1x109 Ohms

*Electrical Resistivity:
As per ASTM F -150 / NFPA 99 / ANSI S7.1 but modified for surface to ground. To place one
electrode on the Access floor panel surface and to attach the other electrode on the pedestal.
Resistance to be tested at 500V.

Accessories :
A variety of accessories are available to enhance the performance of our floor systems. They ensure the true functionality and
flexibility as well as integrity of the floor to the building and services.

Perforated Panel : Panel lifter :


(with Antistatic finish) : Special 2 cup suction
26% opening with & without panel lifting tool for
volume control damper for heavy load
monitoring airflow. carrying capacities.

Grating Panel : Electro-Flex :


(with Antistatic finish) : Concealed electrical monument
46% opening With & box to accommodate plug-in
without volume control damper facility for power data and voice.
for monitoring airflow.

Vision Panel : Kold Lok :


Panels with special factory For sealing Raised Access
made cut out and factory fitted Floor cable cut outs and
with floor grade vision panel for assured control of plenum air
monitoring services. leakage for maximizing cooling.

Special Panels : Grommets :


Panels with special factory Enables wire & cables to pass through
made cut-outs with cover floor panels. It allows wires to neatly &
for cable outlets. safely penetrate from the cavity
below the floor to the location.

.....’.....
Mumbai :
Unit No 2-G, Laxmi Industrial Estate,
New Link road, Andheri (West),
Mumbai 400053.
Tel: +91-22-2630 5270/72
Fax: +91-22-2630 5273
www.unitileindia.com Email : sales@unitileindia.com
Baroda :
A-47, Jay Ranchod Society,
Behind Vrindavan Township,
Makrand Desai Road, Sayed Vasna,
Vadodara 390015.
Tel : +91-093762 33899/093762 37818
Email : sales@unitileindia.com
Bangalore :
Gala No 58, SL No 35/2,
Singasandra Gramathana,

solutions
Begur Hobli, Hosur Road,
Bangalore 560068.
Tel: +91-80-3295 6871
Telfax : +91-80-4110 0518
Email : sales@unitileindia.com

Chennai :
S-1, Shastri Nagar, IInd Avenue,
M. G. Road, Adyar,
Chennai 600020.
Tel : +91-44-24464907
Telfax : +91-44-42144907
Email : sales@unitileindia.com
Delhi :
A-19/2, Road no 2,
(Block A), Mahipalpur Extension,
New Delhi 110037.
Tel: +91-11-32470859
Telfax: +91-11-26789191
Email : sales@unitileindia.com
Hyderabad :
Plot No 66, Telecom Nagar,
1st Floor, Gachibowli Village,
Serilingampally Mandal, R. R. District,
Authorised Distrubutor / Dealer Hyderabad 500 019.
Tel : +91-40-2300 6301/2300 5033
Email : sales@unitileindia.com
Pune :
103, 104, Sanskruti Pratibimb,
Mayur Colony, Kothrud, Pune 411 029.
Tel : +91-093250 01633
Email : sales@unitileindia.com

Design by Vijay Thigale Cell : 98207 31803 vijaythigale@rediffmail.com

You might also like