Professional Documents
Culture Documents
com
Abstract
Alternative energy sources are becoming more cost effective, and many utilities are now providing incentives for alternative power. Placing these
alternative energy sources, as well as other smaller traditional energy sources, on the distribution power system, allows the development of a new
paradigm related to distributed generation (DG). The size and site of the DG will have an effect on the voltages and operations of the distribution
power system in the future. This paper discusses a procedure for evaluating the impact of site and size on both the original distribution power
system as well as a reconfigured power system after a fault. Validation of this work is done using the IEEE 37 node distribution feeder and the
results and trends are presented.
© 2008 Elsevier B.V. All rights reserved.
0378-7796/$ – see front matter © 2008 Elsevier B.V. All rights reserved.
doi:10.1016/j.epsr.2008.01.020
1538 S. Kotamarty et al. / Electric Power Systems Research 78 (2008) 1537–1545
place a DG in radial as well as networked systems with respect The objective is finding the optimal location in the distribu-
to the power losses. tion system for placing the DG that results in the least voltage
This research work, does not consider the various kinds of deviations; this objective was achieved by taking the required
DG. Additionally, the analysis is for steady-state operations. voltage at each node to be 1.0 p.u., for all the DG nodes mod-
A contingency analysis is done with the DG placed at various eled as PV. The analysis is performed for three different sizes of
locations on the feeder with different penetration levels and with DG, one-third, half, and two-thirds of total load capacity. Three
the contingencies at different locations. In this paper, the best different contingencies were considered with a DG placed at
location and size of the DG is determined by the comparison four different locations and modeled as a PV node and a PQ
of the voltage deviations at each node of the system based on node.
where the DG was placed.
3. Test case
2. Problem statement
The analysis presents the work done on the IEEE 37-node
Most distribution systems have been designed to operate distribution feeder [12]. The system consists of various types of
with the main source as the only supplier of the loads with loads including spot loads, single phase and three-phase loads,
the power flowing from the source to the end of the feeder, balanced and unbalanced loads, delta-connected loads, con-
that is, radial. However, DG involvement has changed the con- stant power, constant current, constant impedance, and KVAR
vention of the power flow being radial. Now the power flow type loads. It also has a substation transformer and an inline
can be reversed-with the DG sending power in either direction delta–delta transformer. Additionally, this test system incorpo-
from where it is placed. The power flow differs with a change rates both overhead and underground lines. The layout of the
in DG location and size and loading conditions. Knowing the feeder is shown in Fig. 1.
impact of size and placement of the DG’s on systems with a The locations of the DG placements and the contingencies
change in the loading conditions, due to the reconfigurations on the system are shown using the circles. The contingency
after the fault, is valuable. A study can be done to see the locations in this paper are selected randomly. It is selective pri-
impact of DG on criteria like voltage, losses, reliability, and oritization, as only three random locations are selected to look
economics. Focusing on the optimal placement and size of a at the impact of the size, location, and model of DG on the
DG in a distribution system to keep the system in an econom- intermediate state of the system after a fault, with the system
ical and secured state is paramount. With rapid penetration of reconfigured after the removal of the faulty section and before
DG into distribution systems, assessing power system impacts restoration of the system. The impact of the DG is observed
accurately is critical, so that these DG units can be applied in a with the change in the system load after the fault. The anal-
manner that avoids causing degradation of power quality, reli- ysis is done such that an estimate of the best location among
ability, and control of the utility system. On the other hand, the selected locations is obtained. It is a contingency analysis
DG has great potential to improve distribution system perfor- done looking at all the possible faults, which would give the
mance. Thus, studying the changes that a DG causes with a
change in its location, size, and the loading conditions is imper-
ative.
This work is done on the IEEE 37-node feeder, which is
unbalanced. The unbalanced power flow was run on the feeder
for different cases and situations. A technical evaluation is done
to look at the impacts of the DG with a change in the loca-
tion, size and the loading conditions due to the reconfigurations
caused by the faults on the voltage profile of the system. This
work deals only with changes in the voltage profile of the DG
before and after the reconfigurations caused by the faults and
does not consider the type of fault, as it assumes that the system
is reconfigured after the isolation of the fault.
This research work focuses on the impacts of the DG after the
reconfiguration of the system after a fault. It gives the analysis of
the impact of the DG location and size on the state of the system,
after a contingency, with a change in the system topology and
the loading conditions.
This work mainly focuses on the intermediate state of the sys-
tem between fault stabilization where a fault occurs and steady
state, and the faulty part of the system is isolated, and the system
is reconfigured to continue operation. It demonstrates how the
DG impacts the system voltage due to its size, placement, and a
change in the loading conditions due to a fault. Fig. 1. IEEE 37 node distribution test feeder.
S. Kotamarty et al. / Electric Power Systems Research 78 (2008) 1537–1545 1539
Table 2
Cumulative voltage deviations without contingencies
Contingency location No. of nodes Cumulative voltage deviations (p.u.) Cumulative voltage deviation per node (p.u.)
Fig. 3. Comparison of voltage deviations before and after the fault without DG.
The cumulative size norm is defined as “the total cumu- and PV). Table 1 contains the case scenarios considered in
lative voltage deviation obtained by adding the cumulative this analysis.
voltage deviations of all the equal sized DG’s at the location (5) The node with the least voltage deviation norm was con-
selected to be the best for the placement of the DG.” sidered to be the best location of the DG according to the
Equal sized DG’s are placed in one group, and their cumu- cumulative voltage deviation norm.
lative voltage deviation is obtained. The cumulative voltage (6) Using the cumulative size norm, the best size of the DG was
deviations for DG penetrations of 1/3, 1/2 and 2/3 of the obtained.
total load are obtained.
The definition of cumulative size norm shows that the best 5. Results
size for a DG would be that value where the value of the sum
of the cumulative voltage deviations of all the equal sized 5.1. Test case 1: effect of a fault on system voltage
DG’s is the least. It indicates that at that size the voltage
profile has the least deviations considering the presence of Whenever a fault occurs, the voltages at all the nodes change
the DG. due to the change in the loading conditions as a result of contin-
(4) The DG was sited at four different nodes (742, 709, 734 and gency. This section discusses the effects of the faults at various
741) on the feeder. The voltage deviation norm is calculated locations on the voltage deviations in the system without a DG.
for one site and one size with and without contingencies. Table 2 presents the values of the cumulative voltage
The contingencies are line contingencies for lines 704–720, deviations for the different contingencies. Fig. 3 shows the com-
703–727, and 734–710. It is assumed that the nodes affected parison between the cases with and without the contingencies at
by the line contingency are not available. For example, for different places. The voltage deviation decreases for all the con-
line contingency 704–720, nodes 720, 707, 724, 722, 706, sidered contingencies. The voltage deviations have decreased
and 725 are not available. The above analysis was done for from the base case irrespective of the location of the fault. How-
other sites and sizes with the two different DG models (PQ ever, the change in the voltage deviation is different for different
Table 3
Cumulative voltage deviations without contingencies
DG type DG size Cumulative voltage deviations (p.u.) Cumulative voltage deviations per node (p.u.)
faults, as the loss of load in each case is different. This increase 5.3. Test case 3: effect of the placement of the DG on the
in the voltage can be accounted for by the decrease in the load, voltage profile in the presence of a fault
due to the fault.
This section discusses the effect of the DG and the contin-
5.2. Test case 2: effect of the DG placement on the voltage gency on the system. In this paper, the system is considered
profile without a contingency reconfigured after the isolation of the fault. Three different loca-
tions for the contingencies are examined.
This section addresses the impact of the type, size, and place- A decrease in the voltage deviation occurs for all the con-
ment of the DG units at different locations on the feeder without sidered contingencies with the inclusion of DG. The voltage
a contingency. deviations have decreased from the base case irrespective of the
Table 3 shows the changes in the cumulative voltage devia- location of the fault. However, the change in the voltage devi-
tions for the different types, sizes, and locations of the DG on ation is different for different faults as the loss of load in each
the system. The cumulative voltage deviation without the DG is case is different. As shown in Table 1, 11 case scenarios are
observed to be 1.0737 p.u. or 0.0767 p.u. per node. investigated.
Fig. 4 shows the effect the DG has on the improvement of
the voltages regardless of the size, type or location of the DG. 5.3.1. DG as PQ node
It shows the comparison between cases with different DG sizes, Table 4 presents the results obtained for the cumulative
models, and locations and without a DG. The presence of the voltage deviations with the DG modeled as a PQ node at dif-
DG in the system improves the voltage profile, compared to a ferent DG locations and sizes for the case scenarios described
system without a DG, independent of other factors. However, in Table 1. Table 4 shows clearly that the voltage deviations
the DG modeled as a PV node gives less voltage deviations than are the least at node 741 with the DG modeled as a PQ
those with the DG modeled as PQ. node.
Table 4
Cumulative voltage deviations with the DG (PQ) placed at different nodes
Case Dg size Fault location No. of nodes Cumulative voltage deviations (p.u.) Cumulative voltage deviations per node (p.u.)
between nodes
DG at 742 DG at 709 DG at 734 DG at 741 DG at 742 DG at 709 DG at 734 DG at 741
Total cumulative voltage deviations (p.u.) 7.4288 5.1241 4.4104 4.3619 0.2201 0.1517 0.1303 0.1283
1542 S. Kotamarty et al. / Electric Power Systems Research 78 (2008) 1537–1545
Fig. 5. Cumulative voltage deviation comparison using a PQ model based on location of the DG and different case scenarios.
Table 5
Cumulative voltage deviations with the DG (PV) placed at different nodes
Case Dg size Fault location No. of nodes Cumulative voltage deviations (p.u.) Cumulative voltage deviations per node (p.u.)
between nodes
DG at 742 DG at 709 DG at 734 DG at 741 DG at 742 DG at 709 DG at 734 DG at 741
Fig. 5 shows the graphical representation of Table 4. Fig. 6 shows the graphical representation of Table 5.
Fig. 6. Cumulative voltage deviation comparison using a PV model based on location of the DG and different case scenarios.
S. Kotamarty et al. / Electric Power Systems Research 78 (2008) 1537–1545 1543
Table 6
Best locations for different DG models
Fault location DG size Best location with DG as a PQ node Best location with DG as a PV node
Table 7
Best size of the DG at node 734
Contingency cases Cumulative voltage deviations (p.u.) Cumulative voltage deviations per node (p.u.)
Fig. 7. Comparison of the total cumulative voltage deviation based on DG size for the selection best location using the PV model.
the voltage deviations differs with the change in the DG type and analyzed for the optimal size at this location using the cumulative
size. Node 741 gives better results for the DG modeled as a PQ size norm. Equal-sized DG’s are placed in one group, and their
node, whereas node 734 gives better results for DG modeled as a cumulative voltage deviation is obtained. The voltage deviations
PV node. DG modeled as PV node would lessen the cumulative of cases 0, 3, 6, and 9 from Table 1 are added to get the cumulative
voltage deviation norm, as compared to modeling the DG as a PQ voltage deviation with a DG penetration of 1/3 of the total load.
node as is evident from the tables above. The voltage deviations Similarly, the cumulative voltage deviations for DG penetrations
at node 734 with DG as PV are smaller than the deviations at of 1/2 and 2/3 of the total load are obtained. Table 7 shows results
node 741 with DG as PQ. for the DG size.
Fig. 7 gives a graphical representation of the above table. A
5.5. DG size DG penetration of 2/3 of the total load placed at node 734 would
give the least total cumulative voltage deviations.
The best size of the DG will be the size having the least
cumulative voltage deviation. As the DG as a PV node at 734 6. Conclusions
gives better results with respect to voltage deviation, the best
size for this location will be selected. The three faults with the The majority of the previous work focuses on looking at the
three different DG sizes and the DG placed at node 734 were impact of the DG size and location on the system voltage with-
1544 S. Kotamarty et al. / Electric Power Systems Research 78 (2008) 1537–1545
out a fault or after the system is restored from the fault. This (6) The best size of the DG at the best location for the given
paper focuses on looking at the system voltages in the presence test system was shown to be a DG penetration of 2/3 of the
of a DG with the system configured after the removal of the total load.
faulty part of the system and before the restoration of the sys-
tem. The work done in this paper focuses on the assessment of Acknowledgements
the size and the location impact of the DG with a change in the
loading conditions due to a contingency on unbalanced distri- This work was supported by the United States Office of Naval
bution systems. The optimal location and the size of the DG are Research under Grants N00014-02-1-0623 and N00014-03-1-
selected from the results obtained from the unbalanced distribu- 0744.
tion power flow. A contingency analysis was done taking three
contingencies, three different sizes and four different locations
for the DG on each of the feeders with the power flow run taking References
both types of models for the DG, PQ, and PV, into considera-
[1] T. Ackerman, G. Anderson, L. Soder, Distributed generation: a definition,
tion; the results were analyzed for the best location and size of Electr. Power Syst. Res. (2000) 195–204.
the DG. [2] CIGRE WG 37-23: Impact of increasing contribution of dispersed gener-
Previous work has normally modeled DG as a PQ node only. ation on the power system, Final report. Electra, September 1998.
Typically, DG is modeled as a PQ node with negative injections [3] CIRED WG04: Dispersed generation-preliminary report, CIRED ’99 Nizza
into the network for simplicity. However, in this research, the (Fr), and 2–5 Giugno 1999.
[4] H.L. Willis, W.G. Scott, Distributed Power Generation, Marcel Dekker,
DG was modeled also as a PV node, and a comparison of the New York, 2000.
models is also done to see the effect of the DG model on the [5] P.P. Barker, R.W. de Mello, Determining the impact of distributed genera-
system before and after the fault. However, this kind of work tion on power systems. Part 1. Radial distribution systems, in: Proceedings
is not feasible on large systems, as it is difficult to handle the of IEEE PES Summer Meeting, vol. 3, Seattle (USA) July 16–20, 2000,
different cases and the different inputs. The results presented pp. 1645–1656.
[6] G. Celli, E. Ghiani, S. Mocci, F. Pilo, A multiobjective evolutionary algo-
lead to these conclusions: rithm for the sizing and the siting of distributed generation, IEEE Trans.
Power Syst. 20 (2) (2005).
(1) The system voltages increased for a system with a fault, [7] C.L.T. Borges, D.M. Falco, Impact of distributed generation allocation
as compared to the system without a fault. As the and sizing on reliability, losses and voltage profile, in: Proceedings of
faulty part is removed from the system, the load on 2003 IEEE Bologna Power Tech Conference, Bologna, Italy, June 23–26,
2003.
the system reduces, increasing the voltages at all the [8] K. Nara, Y. Hayashi, K. Ikeda, T. Ashizawa, Application of Tabu search
nodes. to optimal placement of distributed generators, in: Proceedings of IEEE
(2) The voltage deviations on the system reduced considerably PES Winter Meeting, vol. 2, Columbus (USA), February 28–2, 2001, pp.
with the presence of the DG in the system irrespective of 918–923.
the type of the DG. However a comparison of the voltage [9] G. Carpinelli, G. Celli, F. Pilo, A. Russo, Distributed generation siting and
sizing under uncertainty, in: Proceedings of 2001 IEEE Porto Power Tech
deviations shows that modeling the DG as a PV node reduces Conference, 10–13 September, Porto, Portugal, 2001.
the deviations further. [10] J.A. Greatbanks, D.H. Popovic, M. Begovic, A. Pregelj, T.C. Green, On
(3) The results also showed that placing the DG at the optimization for security and reliability of power systems with distributed
junction nodes or at the downstream nodes reduced the generation, in: Proceedings of 2003 IEEE Bologna Power Tech Conference,
deviations considerably more than with the DG placed Bologna, Italy, June 23–26, 2003.
[11] C. Wang, M.H. Nehrir, Analytical approaches for optimal placement of
at upstream nodes on the feeder, as the DG placed fur- distributed generation sources in power systems, IEEE Trans. Power Syst.
ther away from the source helped in providing voltage 19 (4) (2004).
support to the downstream nodes. Even with the recon- [12] Radial Distribution Test Feeders, http://www.ewh.ieee.org/soc/pes/
figured system, a DG placed further away from the dsacom/testfeeders.html.
source helped increase the voltage at all the downstream [13] S. Khushalani, N. Schulz, Development of three-phase unbalanced power
flow using PV and PQ models for distributed generation and study of the
nodes. impact of DG models, IEEE Trans, Power Syst. 22 (3) (2007) 1019–1025.
(4) DG modeled as a PV node gave lesser deviations at all the
nodes as compared to the DG modeled as a PQ, as the DG Sujatha Kotamarty received her Master’s Degree from the Electrical and Com-
puter Engineering Department from Mississippi State University in May of 2006.
modeled as a PV was able to control the voltages at the She received her B.Tech. degree from J.N.T.U, Andhra Pradesh, India, in 2003.
nodes reducing the voltage deviations as compared to the Her research interests are power system analysis and the economics of power
DG modeled as a PQ. Also, according to the way the PQ systems. She is now working for Electric Reliability Council of Texas, Taylor,
and PV nodes are defined, the PV model has some voltage TX.
control to keep the voltages within the limits whereas in the Sarika Khushalani finished her Ph.D. degree in Electrical and Computer Engi-
PQ model there is no control for the voltage. Thus, for large neering Department from Mississippi State University in the fall of 2006. She
DG’s, the PV model is better than the PQ model to reduce received her B.E. degree from Nagpur University and M.E. degree from Mumbai
the voltage deviations. University, India, in 1998 and 2000, respectively. She was involved in research
activities at IIT Bombay, India. Her research interests are in computer applica-
(5) The best location of the DG may be size dependent and tions in power system analysis and power system control. She was also a Honda
topology dependent. More studies need to be done to provide Fellowship Award recipient at MSU. She is now working for Open Systems
a definite trend here. International in Minneapolis, MN.
S. Kotamarty et al. / Electric Power Systems Research 78 (2008) 1537–1545 1545
Noel N. Schulz received her B.S.E.E. and M.S.E.E. degrees from Virginia puter applications in power system operations including artificial intelligence
Polytechnic Institute and State University in 1988 and 1990, respectively. techniques. She is a NSF CAREER award recipient. She has been active in the
She received her Ph.D. in EE from the University of Minnesota in 1995. IEEE Power Engineering Society and is serving as Secretary for 2004–2007.
She is the recipient of the TVA Endowed Professorship in Power Systems She was the 2002 recipient of the IEEE/PES Walter Fee Outstanding Young
Engineering. She has been an Associate Professor in the ECE Department at Power Engineer Award. Dr. Schulz is a member of Eta Kappa Nu and Tau
Mississippi State University since July 2001. Her research interests are in com- Beta Pi.