15.1 GENERAL
15.1.1 Certification
Machines designed in accordance with IEC 60079 shall be duly certified by a ‘Notified
Body’.
NOTE: ‘Notified Body’ was previously called ‘Authorised Certification Body’.
The certification shall not be invalidated by additional features as indicated in this DEP.
Examples of these are:
drain holes (2.6.1)
protective systems (11.8)
noise abatement measures (9.17)
Zone 2 Ex ‘n’ (preferred) not allowed where the nominal voltage exceeds 6.6 kV
not for centrifugal/screw hydrocarbon gas compressors
Ex ‘e’ not allowed where the nominal voltage exceeds 6.6 kV
not for centrifugal/screw hydrocarbon gas compressors
Ex ‘d’
Ex ‘p’
Zone 1 Ex ‘e’ only allowed for LV motors
Ex ‘d’
Ex ‘p’